Actulux SVM 24V-5A Specification sheet

User manual and
installation instruction
Control Panel for Fire Ventilation
SVM 24V-5A / SVM 24V-8A
Fire ventilation
Comfort ventilation
24VDC max. 5A/8A
1 re ventilation group, 1 comfort group
Connection for manual control points, wind- and rain sensor, comfort switches, smoke detectors
Possibility for bus connection of 35 control panels
#211731

23
Control for Fire and Comfort Ventilation Type SVM 24V-5A / SVM 24V-8A Control for Fire and Comfort Ventilation Type SVM 24V-5A / SVM 24V-8A
Address of installation
Name:
___________________________________________________________________________________________
Address:
___________________________________________________________________________________________
Phone no.:
___________________________________________________________________________________________
Contact person:
___________________________________________________________________________________________
Date of installation:
___________________________________________________________________________________________
Installation
Number of control panels and type (ex. SVM 24V-5A):
___________________________________________________________________________________________________
Number of re ventilation groups:
___________________________________________________________________________________________________
Type of opening system:
___________________________________________________________________________________________________
Type of opening system:
___________________________________________________________________________________________________
Type of opening system:
___________________________________________________________________________________________________
External controls (AFA-CCS):
___________________________________________________________________________________________________
Comfort control:
___________________________________________________________________________________________________
Wind- and rain sensor:
___________________________________________________________________________________________________
230V power supply from group:
___________________________________________________________________________________________________
Manufacturer:
Actulux A/S
Håndværkervej 2
9560 Hadsund
Denmark
Tlf.: +45 98 57 40 90
Fax: +45 96 15 28 00
e-mail: [email protected]
www.actulux.com
Table of contents
Address of installation / Description of installation ..........................................................................2
General description ............................................................................................................................4
Safety rules during installation and operation ...................................................................................5
Explosion danger................................................................................................................................5
Installation..........................................................................................................................................5
Yearly legal requirement of maintenance and control .......................................................................5
Connection to motor- (actuator) outputs and line monitoring ...........................................................6
Current limiter type LIP. ....................................................................................................................7
Operation and connection of re switches.........................................................................................8
Connection of smoke-/heat detectors.................................................................................................9
Comfort ventilation - connection and settings...................................................................................9
Diagram control panel and connections ........................................................................................10-11
External LEDs on the front panel (LED board).................................................................................12
Internal LED indication on the main board .......................................................................................12
Fuse specications .............................................................................................................................12
Complete jumper settings ..................................................................................................................13
Connection of more control panels to one re group (bus connection).............................................14
Connection of weather sensor / Close all function ............................................................................15
External signal transfer, connection of AFA systems and other systems...........................................15
Special functions................................................................................................................................16
Cable sizes .........................................................................................................................................16-17
Part nos. and accessories....................................................................................................................18
CE Declaration of conformity ...........................................................................................................19
Technical specications. ....................................................................................................................20
Rev 0.04 26-09-2017

45
Control for Fire and Comfort Ventilation Type SVM 24V-5A / SVM 24V-8A Control for Fire and Comfort Ventilation Type SVM 24V-5A / SVM 24V-8A
General description
The control panel can be used for electrical opening of e.g. skylights, smoke hatches or similar in
connection with re- and comfort ventilation.
The control panel has different inputs with line monitoring which can be activated by e.g. re switches,
smoke detectors, heat detectors, AFA systems and CCS systems.
For control of the indoor climate (comfort ventilation) manual switches, weekly timer, room thermostat
and outdoor weather sensors can be connected.
By means of LEDs in the the front panel the control indicates the operating condition (ok operation
and error- and alarm condition), just as it by means of the built-in potential free relay contacts can re-
lay operating information about ok operation and error- and alarm condition to other systems in the
building.
The polarity of the motor supply is reversed when opening or closing.
The control panel has built-in 72 hours battery back-up.
By a unique bus system consisting of a 3 wire cable the control panels can be mutually connected so
that up to 35 control panels can be connected and operate as an integrated system.
If the temperature in the control panel exceeds 75°C, the control panel will enter ALARM condition.
Connection of cables to the in- and outputs of the control panel is described in the connection drawing
on page 10-11.
A more detailled connection to the individual in- and outputs is described in the individual sections in
this manual. Selection of cable sizes on page 16-17.
By means of jumpers and dip switches the control panel has different setting possibilities for in- and
outputs. These settings are indicated in a complete table (please see section with jumper settings on
page 13).
Examples of types of openings systems and the max. power consumption which can be connected to
the control panel:
Type: 24V power supply:
SA Power Single 4A
SA Power Double 8A (2x4A)
SA Power Large 8A
SA Power Mini 2.5A
Rotary 100 2,5A
Others See specication of max. power consumption on the opening
system
Safety rules during installation and operation
The control panel may only be installed and maintained by personnel authorized for installation of
automatic electrical re ventilation equipment.
Explosion danger
The control panel is supplied with back-up batteries, which contain large amounts of energy which can
be released as explosion in case of wrong handling - the following safety rules must therefore always
be observed:
• Νever short-circuit a back-up battery.
• Do not use external chargers on installed batteries. If unauthorized chargers are used explosive
gasses can be released from the battery.
• Do not drop back-up batteries as strong acids can be released if they are broken.
Installation
The control panel can weigh up to 7 kg and must be installed on a stable wall. The mounting holes for
wall mounting are placed on the metal plate underneath the platic lid.
All cables are connected according to the drawing on the central pages and are dimensioned according
to table page 16. Keep in mind that the operating voltage from the control panel is 24V and that the
max. voltage drop is 15% which demands correct cable dimension according to table on page 17.
Please be aware that it often may be required (in order to keep the demands on the CE marking of the
complete installation or another law) that the control panel is supplied with 230V AC from separate
powerline with its own ground error circuit interruper, and that a repair interrupter is mounted on the
motor line.
After connection the control panel must charge the batteries min. 12 hours before complete testing.
Yearly requirement of maintenance and control (authorized)
The functions of the control panel and the opening system must be tested by authorized personnel
at least once a year. The control panel informs when the maintenance should be done. Then the
external LEDs on the front panel are running. The control panel and opening system are of course
still full operating. Please call a service technician at your earliest convenience in order to carry out
the maintenance and to test the control and opening system, in order to prepare it for another year
of operation. The legal requirements for this must be observed and the testing and control must as a
minimum include the following:
• Control that all opening systems move to full opening when the re function is activated
- should not be carried out if the wind is more than 6 m/sec. as there might be a risk that the
opening system cannot close automatically.
• Control of the batteries. If the batteries are replaced it is important to use the same type as the
batteries are carefully chosen to be able to deliver the current, for which the control is specied.
• Control of in- and outputs on the control.
• Control of re switches and smoke- and heat detectors.
The batteries should be replaced as required, however at least every third year!
Use the same brand.

67
Control for Fire and Comfort Ventilation Type SVM 24V-5A / SVM 24V-8A Control for Fire and Comfort Ventilation Type SVM 24V-5A / SVM 24V-8A
Jumper J2 mounted in pos. »Motor line«
Line monitoring between terminal 2-3.
Jumper J3 (actuator output) is set according to
the number of termination resistors (27KΩ) to
be detected – 1 to max. 4 lines can be detected
by moving jumper J3 – this means that the cable
installation between the control panel and the
actuators can be established in series connection
(cable connection from e.g. skylight 1, further
to skylight 2, etc.), or parallel connection (cable
connection from each skylight to the control), or
a combination of these. However, as mentioned
max. 4 different lines can be detected each
terminated with a 27KΩ resistor.
For SVM 24V-5A the max. allowed current is
5A, For SVM 24V-8A it is 8A.
Jumper description
J3 Number of connected 27Kohm terminal
resistors for actuator output
J2 Chooses line monitoring through motor
terminals 2-3 (Mot Mon) or separate
wire terminals 1-3 (Ext Li Mon), or no
line monitoring when J2/J3 is removed
F1 Fuse 8A for actuator output
#111960
#111961
AWR-24
NC
24V
NO
COM
AC/DC
Next LIP
Next LIP
Blue
Brown
2 channel LIP 6
Max. Torque 0.5 Nm
2,2KΩ
Blue
1 Cannel LIP 7
M2
21
5
6
LIP #2
M1
8
7
34
Brown
Keyboard
#121615
Max. Torque 0.5 Nm
See page 12
}
61
Fit J1 in last BVT for
OPENCLOSE
RED
ALARM
GRE
OK
YEL
FAILURE
J1
BUZZER ON/OFF
RED
RED
RED
BL
Yellow LED
RED
RED
J15
Fire switch type BVT.
DIP settings see page 13
24V Out
PS1
Remove resistors when
LD7 BUS failure (red). Lit when local unit is not recieving signal.
BRA
TEMP DETECT
SERVICE TIMER
SNITCH
FAIL RELAY M.
WEEK OPEN
AG MODE
SPRINKLER
BUS COMFORT
BU S FIR E
123 4 6 75 8 119 10
Extern a l fir e switch
Green LED
mounting priorityswitch
LD3 Weather sensor active (red). Lit when weather sensor is active.
LD6 Line failure smokesensor (red). Lit for line fail. on smokes.
comfort features
Con. Fire. Sw
FAIL SAFE
Min
Const.
BATT LOW
Puls
variable
YEL
RESET
LINE FAILAC FAIL
BUS Slave
Ext 3 wire monitor (line 1)
LD2 Actuator closing (green). Lit when actuator is closing.
LD5 Line failure fire switch (red). Lit for line failure on fire switch.
END termination
YEL YEL
BAT +
BAT -
ON
→
START termination
DOME OPEN
BLUE
PS +
PS -
-
+
+
Black 2,5mm2
-
Puls
Max.
Potmeter for
- 24VDC +
Batteries 2x 12V - 7,2 Ah
24V Red 2,5mm2
Connection
→
J5 J6 J7
SLAVEMASTER
SVM 24V - 5A/8A
END TERM.
A3 B1 B2
BUZZER
B3
→
→
Serial Out
next unit.
Connection to
→
2120
Gnd
2322
Weather
Gnd
24V
A2
→
A1
Serial In
Connection from
Bus connection for serial connection
up to 35 pcs. control units.
of terminal 23
18
Up
17
Smoke
16
Gnd
19
Down
13
24V
ALARM
Fail. 24V
1211
FIRE
Gnd
15
Reset
14
COM
7
NO
NC
98
Failure OutAlarm Out
NC
5
COM
4
NO
6
3
OK 24V
10
START TERM.
L1 Out
L1 In
No.1
L2
L1 In
L2 Up
2,2KΩ
Fire switch BVT No. 1
10 KΩ
1 32 6 74
prev. unit.
→
Extra relay print #111655
GRE
DIP NO
→
1
RED
LD1 Actuator open (red). Lit when actuator is opening.
LD4 Line failure actuator (red). Lit for line failure on actuator.
each 30V 0,5A
Potential free ALARM switch.
Max 48V 0,5A
heat sensors
Smoke or
Down
(Close all)
10 KΩ
L1 Out
Comfort
1234
2
J4
Set J11 for batteri backup
provides 4 additional
OFF
Firemands Priority Switch
Max 48V 0,5A
Potential free Failure switch.
line monitoring
(only last sensor)
1 23 4 7
6
Nr.2-20
Switch
Wind and rain sensor
Max. 8A
FUSE F1 - fast
J 34
J2
12
Line 1
1
2
N1
3
13 A Autofuse
PE L1
1
Blue
2
M1
Brown 1
2
7
6
10 KΩ
potential free switches
6
LIP #1
5
Actuator
Actuator
24VDC 150W/200W
NTC
J9
Without keyboard jumper mounted
Com + NO connected on alarm.
Com + NC connected on failure.
REMOTE
Motor line monitor
Power Supply 180-250 VAC
no: 111894
SWM Add-on
Power
Open
Close
LED 1 Green
LED 3 Red
LED 2 Red
GND
LED
OPEN
CLOSE
1
J1
J1
2
J11
Red LED
BUS Master
345
6
To start communication
LD3 + LD2 flashes for
5 sec. when flatcable
is connected.
LD1 (power) will
illuminate when power is on.
If LD2 (fireswitch) illuminates
linefault on fireswitch.
If LD3 (fireclose) illuminates
linefault on fireclose.
Connection diagram SVM24
Drawing: 211704 N
Jumper J2 in pos. »Ext 3 wire«.
Line monitoring between terminal 1-3:
With jumper J3 (actuator output) it is chosen, how
many lines (number of 27KΩ) you wish to detect - the
same way as the motor line.
This setting demands 3 wire cable from motor output
to motor.
Jumper J2/J3 is not mounted - No line monitoring
for actuator output.
Current limiter type LIP function and setting (if mounted)
The current limiter type LIP (mounted on the opening system) is used as current limiter between the
24V/48V DC supply and 1 or 2 actuators. When the adjusted current limit is reached, the speed of the
actuators is reduced. When the max. power on the actuator is exceeded, the actuator stops. On the
24V /48V types (LIP5, LIP6 or LIP7) max. 3 times overload cut outs in the same direction is allowed.
After that it will not be possible to run in this direction again, before the motor has run in the opposite
direction. This in order to protect the actuator gear mechanism.
Please note that when opening, the red LED in the LIP must light. This indicates that polarity to
actuator is correct.
M1M2Mn
27K Ohm
(Only last
actuator)
J3
J2
4
3
2
Actuator
Motor line monitor
Ext 3 wire monitor (line 1)
3
-
Line 1
12
+
1
24V Out
Actuator
+
A4
REV:
SHEET:
Denmark
SCALE:
2 OF 3
DWG NO.:
DRAWN BY: PSP
DATE: 26-09-17
TITLE:
DK 9560 Hadsund
Haandvaerkervej 2
1:1
211704_02
Actulux A/S
www.actulux.com
SIZE:
Phone int.: +45 98 57 40 90
Fax int.: +45 96 15 28 00
e-mail: info@actulux.com
ENGELSK/TYSK
Connection to motor- (actuator-) output and line monitoring
The actuators (motors) must be connected to the actuator output on the output terminals 2-3.
It is possible to connect and disconnect the line monitoring on the actuator output (the factory setting is
“connected”). The cables to the actuators can be connected in series or parallel or a combination of these
(please see drawing with examples or connection diagramme on the central pages).
It is important to keep the right polarity of the cables - The actuators must always be connected through a
current limiter, e.g. the Actulux LIP or similar.
Cable monitoring (line monitoring) on the motor output
The control is equipped with 3 possible settings for cable
monitoring (line monitoring), which can be congured by
means of jumper J2.
* SA Power Large - parallel operation: Jumper OPT mounted - both motors stop at the same time if one stops because of overload.
** When DIP4 is OFF = Tandem mode - both motors stop at the same time if no current ows in one. (1.5 sec. reaction time)
*** Requires actuator with Reed. (3-core incl. black cable)
**** OFF = No delay between Master og Slave / ON = Seven sec. delay between Master og Slave.
Table of LIP settings
Opening System
24V/48V
3A/1,5A SA Power
Single, Double, Large
4A/2A SA Power
Single, Double, Large
2.5A/1,25A SA Power
Mini
2,5A/1,25A Rotary 100 LIP5/6
2A/1A SA Power Mini LIP7
DIP 1 ON OFF ON OFF
DIP 2 OFF ON ON OFF
Type Board
no.
Board
descrip.
Voltage and
function
DIP
1
DIP
2
DIP
3
DIP
4
DIP
5
DIP
6
DIP
7
DIP
8
LIP5 121315 A043 24/48V 1 channel 27K
ON Not mounted
LIP6 * 121330 A044 24/48V 2
channels
OFF ON** 27K ON M1-M2 delay =ON
LIP7
Basic
121305 LIP7 24/48V 1 channel
See
diagram
above
27K
ON Not mounted
LIP7
TA
121306 LIP7 24/48V 1 channel
Tandem
27K
ON
ON =
Com
OFF = Slave
ON = Master
OFF = Syncro Mode
ON = Tandem Mode ****
Not in
use
LIP7***
OC
121308 LIP7 24/48V
1 channel Syncro
m/position ind.
27K
ON
ON =
Com
OFF = Slave
ON = Master
OFF = Syncro Mode
ON = Tandem Mode **** Not in
use

89
Control for Fire and Comfort Ventilation Type SVM 24V-5A / SVM 24V-8A Control for Fire and Comfort Ventilation Type SVM 24V-5A / SVM 24V-8A
The Manual Control Point will generally contain the following:
• Breakable glass window and red control button is activated by
pressure - this puts the control panel in ALARM condition, by
which the motor output is activated (for normal service and testing
the lid can be opened with a key).
• RESET button which brings the control panel out of the alarm
condition and starts the closing sequence for about 180 seconds.
Please note that RESET does not cancel errors on the system, e.g.
line errors etc. These must be found and corrected.
• RED LED indicates that the control panel is in ALARM condition
and that the motor output either is or has been activated.
• YELLOW LED indicates faults on the system - please call for a
service technician.
• GREEN LED indicates that the system is in normal operation
condition without errors.
CONNECTION of the re switch is made as shown on the drawing.
The installation with re switches must be terminated with a 10KΩ or
27KΩ resistor in the last switch in order to establish the line monitoring
correctly – this can either be done by moving the factory mounted resistor
from the terminal strip to the last re switch or connect jumper J1 in
the re switch type BVT is mounted (by this a 10KΩ resistor is also
connected).
By means of DIP switches the control panel has different possibilities of
settings for the input to the re switch:
DIP 1 (Conf. resw.):
On = ALARM condition from 500-3KΩ, (indication of line error by direct
short circuit or open circuit).
Off = ALARM condition from 0-3KΩ (indication of line error by open
circuit).
DIP 2 (Failsafe):
On = Any line error on re switch or smoke detector puts the control panel
in ALARM condition. This function can be used if cables to re switches
and smoke detectors are not reproof.
Off = An error condition does not report ALARM condition.
BVT
Operation and connection of Manual Control Points
DIP NO
FAIL SAFE
OFF
Fail. 24V
ALARM
OK 24V
7
43
Fire switch type BVT
→
Con. Fire. Sw
BVT for line monitoring
2,2Ω
10 KΩ
4
3
2
1
J1
6
7
Fire switch BVT No. 1
Red LED
Yellow LED
Green LED
10 KΩ
2,2Ω
43
2
1
Gnd
11 12
24V
10 13
6
J1
76
FIRE
15
Reset
14
21
Fit J1 in last
2
1
ON
→
REV:
2 OF 4
Denmark
A4
SCALE:SHEET:
DWG NO.:
DRAWN BY: PSP
DATE: 26-09-17
TITLE:
DK 9560 Hadsund
Haandvaerkervej 2
1:1
211704_03
Actulux A/S
www.actulux.com
SIZE:
Phone int.: +45 98 57 40 90
Fax int.: +45 96 15 28 00
e-mail: info@actulux.com
ENGELSK
Ω
Ω
1 green LED OK (lights when OK and while closing)
2 yellow LED (lights on error)
3 red LED alarm (emergency opening)
4 ground (-)
5 not used
6 re switch reset
7 re switch emergency opening
Jumper J1 must only be set in the last or only re switch
Smoke- and heat detectors are connected as shown.
Line monitoring: Correct line monitoring can only be guaranteed with detectors
delivered from the supplier. Other detectors may have different internal resistances
and stand by power consumption.
Comfort ventilation – Connection and settings
The motor output can be controlled separately with a comfort switch.
For comfort ventilation there are the following possibilities:
Potentiometer in Puls pos.:
It is possible to press the »up« button 3 times, which each gives 6 seconds of opening
time - after that nothing happens – Continuous »up« signal gives 3x6 sec.=18 sec.
- One press on »down« closes the actuator completely for a period which is 18 sec.
longer than the complete opening time - In order to avoid »actuator pumping« max. 3
successive closing attempts will be allowed.
Potentiometer in Const. pos.:
As long as »up« signal or »down« signal are given, the actuators are running
Potentiometer in Puls variable pos.:
The time on the above mentioned pulse opening can be adjusted from 0-60 sec. on the
potentiometre.
When moving the potentiometer into the different positions the LED batt low will
ash for about 4 sec. to indicate when in puls mode. LED line fail ashes 4 sec. when
in constant and AC fail ashes when in puls varaiable.
Connection of smoke-/heat detectors
L1 Out
17
10 KΩ
Smoke or heat sensors
L1 Out
L2
Nr.2-20
L1 In
Gnd
16
L1 In
Nr.1
L2
Smoke
(Only last sensor)
A4
REV:
1:1
DWG NO.:
Denmark
SHEET: DRAWN BY: PSP
DATE: 26-09-17
TITLE:
SCALE:
DK 9560 Hadsund
Haandvaerkervej 2
211704_04
Actulux A/S
www.actulux.com
SIZE:
2 OF 3
Phone int.: +45 98 57 40 90
Fax int.: +45 96 15 28 00
e-mail: info@actulux.com
ENGELSK/TYSK
20
Gnd
18
Up
19
Down
Up
Down
Comfort
Switch Ch 1
Puls
variable
Min
Const.
Potmeter for
comfort feature
Max.
Puls
YELYEL YEL
AC FAIL LINE FAIL BATT LOW
Actulux A/S
211704_05
1:1
1 OF 2
SCALE:
DWG NO.:
Denmark
DRAWN BY: PSP
DATE: 26-09-17
TITLE:
DK 9560 Hadsund
Haandvaerkervej 2
www.actulux.com
SIZE: SHEET:
REV:
A4
Phone int.: +45 98 57 40 90
Fax int.: +45 96 15 28 00
e-mail: info@actulux.com
DANSK/ENGELSK/TYSK
Room thermostats, weekly timers, CCS and
other external control equipment for comfort
ventilation can be connected on the input of the
comfort control.

10 11
Control for Fire and Comfort Ventilation Type SVM 24V-5A / SVM 24V-8A Control for Fire and Comfort Ventilation Type SVM 24V-5A / SVM 24V-8A
#111960
#111961
AW R-24
NC
24V
NO
COM
AC/DC
Next LIP
Next LIP
Blue
Brown
2 channel LIP 6
Max. Torque 0.5 Nm
2,2KΩ
Blue
1 Cannel LIP 7
M2
21
5
6
LIP #2
M1
8
7
34
Brown
Keyboard
#121615
Max. Torque 0.5 Nm
See page 12
}
61
Fit J1 in last BVT for
OPENCLOSE
RED
ALARM
GRE
OK
YEL
FAILURE
J1
BUZZER ON/OFF
RED
RED
RED
BL
Yellow LED
RED
RED
J15
Fire switch type BVT.
DIP settings see page 13
24V Out
PS1
Remove resistors when
LD7 BUS failure (red). Lit when local unit is not recieving signal.
BRA
TEMP DETECT
SERVICE TIMER
SNITCH
FAIL RELAY M.
WEEK OPEN
AG MODE
SPRINKLER
BUS COMFORT
BU S FIRE
123 4 6 75 8 119 10
Extern al fir eswitch
Green LED
mounting priorityswitch
LD3 Weather sensor active (red). Lit when weather sensor is active.
LD6 Line failure smokesensor (red). Lit for line fail. on smokes.
comfort features
Con. Fire. Sw
FAIL SAFE
Min
Const.
BATT LOW
Puls
variable
YEL
RESET
LINE FAILAC FAIL
BUS Slave
Ext 3 wire monitor (line 1)
LD2 Actuator closing (green). Lit when actuator is closing.
LD5 Line failure fire switch (red). Lit for line failure on fire switch.
END termination
YEL YEL
BAT +
BAT -
ON
→
START termination
DOME OPEN
BLUE
PS +
PS -
-
+
+
Black 2,5mm2
-
Puls
Max.
Potmeter for
- 24VDC +
Batteries 2x 12V - 7,2 Ah
24V Red 2,5mm2
Connection
→
J5 J6 J7
SLAVEMASTER
SVM 24V - 5A/8A
END TERM.
A3 B1 B2
BUZZER
B3
→
→
Serial Out
next unit.
Connection to
→
2120
Gnd
2322
Weather
Gnd
24V
A2
→
A1
Serial In
Connection from
Bus connection for serial connection
up to 35 pcs. control units.
of terminal 23
18
Up
17
Smoke
16
Gnd
19
Down
13
24V
ALARM
Fail. 24V
1211
FIRE
Gnd
15
Reset
14
COM
7
NO
NC
98
Failure OutAlarm Out
NC
5
COM
4
NO
6
3
OK 24V
10
START TERM.
L1 Out
L1 In
No.1
L2
L1 In
L2 Up
2,2KΩ
Fire switch BVT No. 1
10 KΩ
1 32 6 74
prev. unit.
→
Extra relay print #111655
GRE
DIP NO
→
1
RED
LD1 Actuator open (red). Lit when actuator is opening.
LD4 Line failure actuator (red). Lit for line failure on actuator.
each 30V 0,5A
Potential free ALARM switch.
Max 48V 0,5A
heat sensors
Smoke or
Down
(Close all)
10 KΩ
L1 Out
Comfort
1234
2
J4
Set J11 for batteri backup
provides 4 additional
OFF
Firemands Priority Switch
Max 48V 0,5A
Potential free Failure switch.
line monitoring
(only last sensor)
1 23 4 7
6
Nr.2-20
Switch
Wind and rain sensor
Max. 8A
FUSE F1 - fast
J 34
J2
12
Line 1
1
2
N1
3
13 A Autofuse
PE L1
1
Blue
2
M1
Brown 1
2
7
6
10 KΩ
potential free switches
6
LIP #1
5
Actuator
Actuator
24VDC 150W/200W
NTC
J9
Without keyboard jumper mounted
Com + NO connected on alarm.
Com + NC connected on failure.
REMOTE
Motor line monitor
Power Supply 180-250 VAC
no: 111894
SWM Add-on
Power
Open
Close
LED 1 Green
LED 3 Red
LED 2 Red
GND
LED
OPEN
CLOSE
1
J1
J1
2
J11
Red LED
BUS Master
345
6
To start communication
LD3 + LD2 flashes for
5 sec. when flatcable
is connected.
LD1 (power) will
illuminate when power is on.
If LD2 (fireswitch) illuminates
linefault on fireswitch.
If LD3 (fireclose) illuminates
linefault on fireclose.
Connection diagram SVM24
Drawing: 211704 N

12 13
Control for Fire and Comfort Ventilation Type SVM 24V-5A / SVM 24V-8A Control for Fire and Comfort Ventilation Type SVM 24V-5A / SVM 24V-8A
LED/colour Symbol Operation possibilities for: Alarm/
re
Comfort
operation
LD1/red Actuator open (red). Lights when actuator opens
LD2/green Actuator close (green). Lights when actuator closes
LD3/red Weather sensor active (red). Lights when weather sensor is active Yes No
LD4/red Line error on actuator (red). Lights when actuator has line error Yes Only close
LD5/red Line error on re switch (red). Lights when re switch has line error,
ashes when SVM Add-on has line error.
Yes Only close
LD6/red Line error on smoke detector (red). Lights when smoke detector has
line error, ashes at temperatures above 75°
Yes Only close
LD7/red Bus error (red). Lights when BUS signal from other controls
is missing. Only relevant if J24 or J25 is mounted. Flashes if
connection to Add-on PCB is missing
Yes Only close
Green
Board + Front
lights if everything is ok
switched off by local error on this control
ashes by error message from other controls received by bus
Yes Yes
Yellow
Board + Front
Fault
lights by local error on this control
or by error message from other controls received by bus
Yes Only close
*Yellow
Board + Front
Line error
ashes by local error on this control
or by error message from other controls received by bus
Yes Only close
*Yellow
Board + Front
AC error
ashes by local error on this control
or by error message from other controls received by bus
Yes Only close
Red
Board + Front
Alarm
lights red constantly
Yes No
*Yellow
Board + Front
DC error
ashes by local battery error on this control
or by error message from other controls received by bus
Blue
Board + Front
Lights blue constantly in open condition (when windows are open)
ashes when actuator is moving up and down
Lights with* Time for yearly service - please call for supplier (ashes fast) Yes Yes
Fuse specications
Placement
Fuse value
24V
F1 8A fast ading fuse 1 pc. for 24V motor output
Text on board Factory
mounted
Mounted / ON function Dismounted / OFF function
DIP 1 Conf. Fireswitch No Fire switch active from 500-3KΩ.
A short circuit of the smoke detector
input will generate a line error
Fire switch active from 0-3KΩ.
A short circuit of the smoke detector
input will generate alarm
DIP 2 Failsafe No Line error on re switch or detector
puts the control in alarm
Normal mode
DIP 3 Temp. Detekt No Line error on motor line
(upper resistor area) = alarm
Normal mode
DIP 4 Ser Yes Active Inactive
DIP 5 Snitch No LED’s “remember” errors (line
errors, AC/Batt. error, bus error). The
LED’s can only be switched off/reset
again by setting dip switch off
Normal mode
DIP 6 Fail Relay No Failure relay works as indication that
skylight is open
Normal mode (works as failure
relay)
DIP 7 Week open No Weekly open (2 sec.) /close
(5 sec.) cycle activated
Weekly open/close not activated
DIP 8 AG Mode special No Special “Fire close” button enabled Normal mode
DIP 9 Sprinkler No Motor output closes by active
detector (opens by activating the re
switch)
Normal mode - motor output opens
by ative detectors or re switches
DIP 10 Bus comfort No The control reacts on comfort signal
via bus activity
The control does not react on
comfort signals via bus activity //
NB! Always reaction on weather
signal and failures via bus activity
and own comfort signal
DIP 11 Bus re No The control reacts on alarm signal
via bus activity
The control does not react on alarm
signal via bus activity
//NB! Always reaction on weather
signal and failures via bus activity
and own alarm signal (detector or
re switch)
DIP 12 BRA Mode special No Special re switch/alarm mode and
comf. active at all failures
Normal mode
J3
(motor)
1 - 2 - 3 - 4 Pos. 1 Connect according to number of
27KΩ terminal resistors on actuator
No line monitoring
J2
(motor)
Mot Mon act. Yes 2 wire line monitoring via 27KΩ
terminal 2-3 No line monitoring
Ext Li Mon act. No 3 wire line monitoring with direct
motor connection actuator
J4(Bus) Start term. No First control panel in the bus network
See section concerning connection
of controls panels in bus connection,
page 14
J5(Bus) + Master No
J6(Bus) Slave No Middle and last control panel in the
bus network
J7(Bus) End term. No Last control panel in the bus network
J9 FOIL Yes in Basic Line monotoring of front cabinet Line error ashes
J11 BatSup->Ø23 No Battery backup of terminal 23 Terminal 23 only AC supplied
Others: Reset time = 180 sec. closing // Cut-off motor output and loading after 360 sec. // Comf. var (potetiometer): 1-60 sec.
Complete jumper settings
LEDs on main board and front panel

14 15
Control for Fire and Comfort Ventilation Type SVM 24V-5A / SVM 24V-8A Control for Fire and Comfort Ventilation Type SVM 24V-5A / SVM 24V-8A
Connection of more controls to one re group (bus connection)
By means of a bus communication it is possible to make 2 – 35 control panels to work as a complete
system. The control panels communicate with each other via a 3 wire bus connection. This could e.g. be a
3x0.5 mm² reproof cable.
Terminal no. A1, A2, A3 are for the incoming connection and B1, B2, B3 for the outgoing connection.
In the rst control panel start Bus J4 has to be on. This control is Master and J5 must therefore also be on.
The bus cable is connected on the output terminals B1, B2, B3 and lead to the next control panel which
is a slave, J6 must therefore be on. The cable is connected to the input terminals A1, A2, A3 of the next
control panel and further to the next slave control panel from terminal B1, B2, B3. In the last slave control
panel J7 and J6 must be on in order to terminate the bus connection.
ALARM: Alarms from Manuel Control Point smoke-/heat detectors are controlled locally. When DIP11 is
set the panel will go into alarm state if another control panel connected on the BUS enters alarm state
RESET: If the reset button on one control or in one re switch is activated, the reset function on all
connected controls is activated and starts the closing function on all motor output in approx. 180 sec.
COMFORT: The comfort control can work locally on each control panel. When DIP 10 is set the control
panel will react on any comfort signal send on the bus from another control panel.
If a wind- and rain sensor is connected, it will work on all control panels on the bus no matter dip settings.
Function description for control panels connected with bus connection
If more control panels are connected by means of a bus connection, the following are monitored/
communicated between the control panels:
- A detected bus error makes the LED LD7 on the main board light/ash.
- A detected bus error brings all controls on the bus connection in error condition (line error).
- If one of the control panels in the network goes into alarm condition, all go into alarm condition.
- If one of the control panels goes into a certain error condition (line error, AC error, battery error or
bus error), the other control panels also go into error condition – the type of the error is indicated
on the board of the front plate of all control panels – on the control panel(s) which have not caused
the error, the ok LED on the board of the front plate ashes at the same time as the error. On the
control panel(s) which have caused the error, the OK LED is switched off.
A4
REV:
SIZE:
www.actulux.com
DATE: 26-09-17
TITLE:
SCALE:
Denmark
1:1
DRAWN BY: PSP
DK 9560 Hadsund
Haandvaerkervej 2
2 OF 3
SHEET:
DWG NO.:
211704_06
Actulux A/S Phone int.: +45 98 57 40 90
Fax int.: +45 96 15 28 00
e-mail: info@actulux.com
ENGELSK/TYSK
BUS Master
MASTER
J6
Fireproof
J4
START termination
Slave
BUS connection
Fireproof
Serial InSerial In
Serial Out
Serial Out
B1A3 B2
A2 B3
A1
A3A2
A1 B3
B2B1
A3A2
A1 B3
B2
B1
B3B2B1A3A2
BUS connection
BUS Slave
A1
Last Control Panel on BUS
3x0,5mm²
Serial Out
Serial In
3x0,5mm²
First Control Panel on BUS
Master
START TERM.
J4
MASTER
J5
SLAVE
J6
END TERM.
J7
START TERM.
J4
MASTER
J5
SLAVE
J6
END TERM.
J7
END TERM.
J7
SLAVE
J5
START TERM.
START termination
BUS Master
BUS Slave
END termination
START termination
BUS Master
BUS Slave
END termination
END termination
Please notice
mounted jumpers
Slaver
0-33 Control Panels on BUS
Connection of weather sensor / Close all function
A weather sensor can be connected to the control panel.
The weather sensor is adjusted according to the instructions.
Actuators should be closed when the wind is above 6 m/s.
LED LD3 on the main board indicates active weather sensor - lights
as long as input is active.
As long as the weather sensor is active, motor inputs cannot be opened with
comfort switches.
The weather sensor closes on all controls which are connected through bus
connection.
On the input to weather station a weekly timer can be connected which makes
sure that everything is closed, e.g. by end of a working day.
Power Supply to terminal 22 and 23 is only AC supplied as standard.
If battery backup is needed, then mount J11 .
This is only possible at PCB V5 and following versions.
NOTE: Be aware of standby time due to current consumption.
External signal output, connection to Fire Alarm
Panel and other control systems
The control panel can forward alarm condition to external connected
systems by means of potential free contacts on the terminals 4 (com),
5(NC) and 6(NO).
The control panel can forward failure condition to external connected
systems by means of potential free contacts on the terminals 7 (com),
8(NO) and 9(NC).
Alarm and error contacts work parallel on all controls connected with
bus connection.
DIP6 (fail relay):
On = Fail relay changes function to indicate open/closed window.
How to make a connection from a Fire Alarm Panel
The control panel can receive potential free zero volt alarm signals from e.g.
AFA systems on the input to re switch or smoke-/heat detector
Terminal 16 and 17.
– Line monitoring resistor must be tted on the contact in the AFA system
Normally open
Supplied with Panel
#111960
#111961
AWR-24
NC
24V
NO
COM
AC/DC
Next LIP
Next LIP
Blue
Brown
2 channel LIP 6
Max. Torque 0.5 Nm
2,2KΩ
Blue
1 Cannel LIP 7
M2
21
5
6
LIP #2
M1
8
7
34
Brown
Keyboard
#121615
Max. Torque 0.5 Nm
See page 12
}
61
Fit J1 in last BVT for
OPENC LOSE
RED
ALARM
GRE
OK
YEL
FAILURE
J1
BUZZER ON/OFF
RED
RED
RED
BL
Yellow LED
RED
RED
J15
Fire switch type BVT.
DIP settings see page 13
24V Out
PS1
Remove resistors when
LD7 BUS failure (red). Lit when local unit is not recieving signal.
BRA
TEMP DETECT
SERVICE TIMER
SNITCH
FAIL RELAY M.
WEEK OPEN
AG MODE
SPRINKLER
BUS COMFORT
BU S FIR E
123 4 6 75 8 119 10
Extern a l fir e swi tch
Green LED
mounting priorityswitch
LD3 Weather sensor active (red). Lit when weather sensor is active.
LD6 Line failure smokesensor (red). Lit for line fail. on smokes.
comfort features
Con. Fire. Sw
FAIL SAFE
Min
Const.
BATT LOW
Puls
variable
YEL
RESET
LINE FAILAC FAIL
BUS Slave
Ext 3 wire monitor (line 1)
LD2 Actuator closing (green). Lit when actuator is closing.
LD5 Line failure fire switch (red). Lit for line failure on fire switch.
END termination
YEL YEL
BAT +
BAT -
ON
→
START termination
DOME OPEN
BLUE
PS +
PS -
-
+
+
Black 2,5mm2
-
Puls
Max.
Potmeter for
- 24VDC +
Batteries 2x 12V - 7,2 Ah
24V Red 2,5mm2
Connection
→
J5 J6 J7
SLAVEMASTER
SVM 24V - 5A/8A
END TERM.
A3 B1 B2
BUZZER
B3
→
→
Serial Out
next unit.
Connection to
→
2120
Gnd
2322
Weather
Gnd
24V
A2
→
A1
Serial In
Connection from
Bus connection for serial connection
up to 35 pcs. control units.
of terminal 23
18
Up
17
Smoke
16
Gnd
19
Down
13
24V
ALARM
Fail. 24V
1211
FIRE
Gnd
15
Reset
14
COM
7
NO
NC
98
Failure OutAlarm Out
NC
5
COM
4
NO
6
3
OK 24V
10
START TERM.
L1 Out
L1 In
No.1
L2
L1 In
L2 Up
2,2KΩ
Fire switch BVT No. 1
10 KΩ
1 32 6 74
prev. unit.
→
Extra relay print #111655
GRE
DIP NO
→
1
RED
LD1 Actuator open (red). Lit when actuator is opening.
LD4 Line failure actuator (red). Lit for line failure on actuator.
each 30V 0,5A
Potential free ALARM switch.
Max 48V 0,5A
heat sensors
Smoke or
Down
(Close all)
10 KΩ
L1 Out
Comfort
1234
2
J4
Set J11 for batteri backup
provides 4 additional
OFF
Firemands Priority Switch
Max 48V 0,5A
Potential free Failure switch.
line monitoring
(only last sensor)
1 23 4 7
6
Nr.2-20
Switch
Wind and rain sensor
Max. 8A
FUSE F1 - fast
J 34
J2
12
Line 1
1
2
N1
3
13 A Autofuse
PE L1
1
Blue
2
M1
Brown 1
2
7
6
10 KΩ
potential free switches
6
LIP #1
5
Actuator
Actuator
24VDC 150W/200W
NTC
J9
Without keyboard jumper mounted
Com + NO connected on alarm.
Com + NC connected on failure.
REMOTE
Motor line monitor
Power Supply 180-250 VAC
no: 111894
SWM Add-on
Power
Open
Close
LED 1 Green
LED 3 Red
LED 2 Red
GND
LED
OPEN
CLOSE
1
J1
J1
2
J11
Red LED
BUS Master
345
6
To start communication
LD3 + LD2 flashes for
5 sec. when flatcable
is connected.
LD1 (power) will
illuminate when power is on.
If LD2 (fireswitch) illuminates
linefault on fireswitch.
If LD3 (fireclose) illuminates
linefault on fireclose.
Connection diagram SVM24
Drawing: 211704 N
#111960
#111961
AW R-24
NC
24V
NO
COM
AC/DC
Next LIP
Next LIP
Blue
Brown
2 channel LIP 6
Max. Torque 0.5 Nm
2,2KΩ
Blue
1 Cannel LIP 7
M2
21
5
6
LIP #2
M1
8
7
34
Brown
Keyboard
#121615
Max. Torque 0.5 Nm
See page 12
}
61
Fit J1 in last BVT for
OPENCL OSE
RED
ALARM
GRE
OK
YEL
FAILURE
J1
BUZZER ON/OFF
RED
RED
RED
BL
Yellow LED
RED
RED
J15
Fire switch type BVT.
DIP settings see page 13
24V Out
PS1
Remove resistors when
LD7 BUS failure (red). Lit when local unit is not recieving signal.
BRA
TEMP DETECT
SERVICE TIMER
SNITCH
FAIL RELAY M.
WEEK OPEN
AG MODE
SPRINKLER
BUS COMFORT
BU S FIRE
123 4 6 75 8 119 10
Exter na l fire swi tch
Green LED
mounting priorityswitch
LD3 Weather sensor active (red). Lit when weather sensor is active.
LD6 Line failure smokesensor (red). Lit for line fail. on smokes.
comfort features
Con . Fire. Sw
FAIL SA FE
Min
Const.
BATT LOW
Puls
variable
YEL
RESET
LINE FAILAC FAIL
BUS Slave
Ext 3 wire monitor (line 1)
LD2 Actuator closing (green). Lit when actuator is closing.
LD5 Line failure fire switch (red). Lit for line failure on fire switch.
END termination
YEL YEL
BAT +
BAT -
ON
→
START termination
DOME OPEN
BLUE
PS +
PS -
-
+
+
Black 2,5mm2
-
Puls
Max.
Potmeter for
- 24VDC +
Batteries 2x 12V - 7,2 Ah
24V Red 2,5mm2
Connection
→
J5 J6 J7
SLAVEMASTER
SVM 24V - 5A/8A
END TERM.
A3 B1 B2
BUZZER
B3
→
→
Serial Out
next unit.
Connection to
→
21
20
Gnd
2322
Weather
Gnd
24V
A2
→
A1
Serial In
Connection from
Bus connection for serial connection
up to 35 pcs. control units.
of terminal 23
18
Up
17
Smoke
16
Gnd
19
Down
13
24V
ALARM
Fail. 24V
1211
FIRE
Gnd
15
Reset
14
COM
7
NO
NC
98
Failure OutAlarm Out
NC
5
COM
4
NO
6
3
OK 24V
10
START TERM.
L1 Out
L1 In
No.1
L2
L1 In
L2 Up
2,2KΩ
Fire switch BVT No. 1
10 KΩ
1 32 6 74
prev. unit.
→
Extra relay print #111655
GRE
DIP NO
→
1
RED
LD1 Actuator open (red). Lit when actuator is opening.
LD4 Line failure actuator (red). Lit for line failure on actuator.
each 30V 0,5A
Potential free ALARM switch.
Max 48V 0,5A
heat sensors
Smoke or
Down
(Close all)
10 KΩ
L1 Out
Comfort
1234
2
J4
Set J11 for batteri backup
provides 4 additional
OFF
Firemands Priority Switch
Max 48V 0,5A
Potential free Failure switch.
line monitoring
(only last sensor)
1 23 4 7
6
Nr.2-20
Switch
Wind and rain sensor
Max. 8A
FUSE F1 - fast
J 34
J2
12
Line 1
1
2
N1
3
13 A Autofuse
PE L1
1
Blue
2
M1
Brown 1
2
7
6
10 KΩ
potential free switches
6
LIP #1
5
Actuator
Actuator
24VDC 150W/200W
NTC
J9
Without keyboard jumper mounted
Com + NO connected on alarm.
Com + NC connected on failure.
REMOTE
Motor line monitor
Power Supply 180-250 VAC
no: 111894
SWM Add-on
Power
Open
Close
LED 1 Green
LED 3 Red
LED 2 Red
GND
LED
OPEN
CLOSE
1
J1
J1
2
J11
Red LED
BUS M aster
3456
To start communication
LD3 + LD2 flashes for
5 sec. when flatcable
is connected.
LD1 (power) will
illuminate when power is on.
If LD2 (fireswitch) illuminates
linefault on fireswitch.
If LD3 (fireclose) illuminates
linefault on fireclose.
Connection diagram SVM24
Drawing: 211704 N
#111960
#111961

16 17
Control for Fire and Comfort Ventilation Type SVM 24V-5A / SVM 24V-8A Control for Fire and Comfort Ventilation Type SVM 24V-5A / SVM 24V-8A
Special functions
Sprinkler function:
DIP 9 On - a special function comes in use where sprinkler systems are installed. With this function
activated, the actuator output closes, if smoke-/heat detector input is activated.
If the re switch is activated, the actuator output opens.
Weekly open/close:
DIP 7 On - the motor output opens shortly (3 seconds) once a week and closes immediately after -
This function is used to give the right tension on the packing of the skylights to keep them watertight.
Function of heat detector in LIP:
DIP 3 On - a heat detector 70-100° can be mounted in each LIP. If the temperatur is exceeded, the
control panel goes into alarm and the opening system is opening.
Special mode:
DIP 12 On - possible to use comfort switch also during line fault, low batt., no AC, Alarm only as long
as re input is active or detector is activated.
Cable sizes
It is very important to use the correct cable types and sizes to make sure that the re ventilation system
meets the standards and works correct in an emergency.
The two most important factors are the ability of the cables to resist heat and to make sure that the
voltage drop in the cables to the actuators do not exceed 15% at full load on the re ventilation hatches.
Fire resistant cables according to IEC 60331 must be used for the following functions:
Opening systems with actuators 24V 2 wires, see diagramme (3 wires by external line surveillance)
Fire switch 24V Min. 6 x 0,5 mm²
Smoke detector 24V Min. 2 x 0,5 mm²
Heat detector Min. 2 x 0,5 mm²
Cable between control panels (bus) 3 x 0,5 mm²
Normal cables can be used for the following functions:
Supply for control 230VAC e.g. 3 x 1,5 mm² PVIK-J
Comfort ventilation button 24V Min. 3 x 0,5 mm²
Wind- and rain sensor 24V Min. 4 x 0,5 mm²
Power
consumption
per group in
ampere
Cable cross section and amount of cores
2x1,5 mm² 2x2,5 mm²4x1,5 mm²
(2x1,5+2x1,5)
4x2,5 mm²
(2x2,5+2x2,5)
2x6 mm²5x2,5 mm²
(2x2,5+3x2,5)
2x10 mm²
2 74 m 123 m 148 m 246 m 295 m 307 m 292 m
4 37 m 61 m 74 m 122 m 148 m 154 m 244 m
6 25 m 41 m 50 m 82 m 98 m 102 m 164 m
8 18 m 31 m 36 m 62 m 74 m 77 m 124 m
Table for SVM 24V-5A/8A allowed voltage drop 15% = 3,6V

18 19
Control for Fire and Comfort Ventilation Type SVM 24V-5A / SVM 24V-8A Control for Fire and Comfort Ventilation Type SVM 24V-5A / SVM 24V-8A
Spare parts
no.
Name of part Description
121620 Control PCB Main board
211061 Power supply 150W 27VDC MW Power supply 230VAC/27VDC for 5A control
211071 Power supply 200W 27VDC MW Power supply 230VAC/27VDC for 8A control
211210 Circuit breaker 10A Automatic fuse 10A / input terminal
800248 Batteri 12V/7,2AH 151x65x98mm Battery for 24V / 5A controls / 8A controls
111789 Fire switch/reset IP40 Actulux Fire switch IP 40
111701 Replacement glass for BVT Replacement glass for re switch
111725 Fireswitch WSK/BVT in IP65 Box Fire switch built in IP65 box
111960 Rain sensor 250VAC / 24VDC Rain sensor closes everything when raining
111961 Wind and rain sensor 250VAC /24VDC Wind- and rain sensor closes everything when raining or
strong wind
111735 Heat detector+base 75 degree Heat detector 75 degrees temperature activation
111741 Heat detector+base 90 degree Heat detector 90 degrees temperature activation
111740 Smoke detector, optical Optical smoke detector
111742 Smoke detector, Ion detector Ion smoke detector for invisible smoke
111753 Comfort switch OPUS w housing Comfort switch Opus complete with housing
111758 Comfort switch FUGA w housing Comfort switch Fuga complete with housing
111760 Weekly timer 1 channel Weekly timer, can e.g. close everything in the evening
111761 Comfort sw.up/down OPUS IP44 Comfort switch Opus 44 white
111767 AUTO MAN switch OPUS w housin Switch Auto. man. OPUS white, activates room
thermostat or weekly timer
111770 Room thermostat RTR w.resis. Room thermostat for control of comfort ventilation
111655 Relay PCB extra 2Xoutp.in box Board with 2x2 extra relay outputs 30V 0,5A
111892 Transmitter for Wind and Rain Wireless weather signal together with #111894
111894 Remote control w/receiver SVM Remote control for comfort
121615 Priority switch + Add-on SVM Firemans button, override the alarm and closes
Part nos. and accessories

20
Control for Fire and Comfort Ventilation Type SVM 24V-5A / SVM 24V-8A
Manufacturer:
Actulux A/S
Håndværkervej 2
9560 Hadsund
Denmark
Tel.: +45 98 57 40 90
Fax: +45 96 15 28 00
e-mail: [email protected]
www.actulux.com
Technical specications SVM 24V-5A SVM 24V-8A
Power supply 230V AC / max. 1.2A 230V AC / max. 1.7A
Output supply 24-28 VDC 24-28 VDC
Motor outputs 1 pcs. (line detecton: 1-4 lines) 1 pcs. (line detecton: 1-4 lines)
Max. load 5A 8A
Operation temperture -15°C - +40°C -15°C - +40°C
Density IP 54 IP 54
Battery back-up (72h) Yes Yes
Batteries 2 pcs. 12V/7.2AH 2 pcs. 12V/7.2AH
Dimensions (WxDxH) 238 x 113 x 286 mm 238 x 113 x 286 mm
Weight incl. batteries 7,5 kgs. 7,5 kgs.
Colour White front / Black indication label White front / Black black indication label
Fire groups 1 pcs. with line detect. / Max. power consumption for re switches (LED+buzzer) = 17.6mA=
approx. 8 re switches
Comfort groups 1 pcs. unlimited number of comfort switches
Detector (smoke/heat) input 1 pcs. with line detection / Max. power consumption for detectors = 2.2 mA = approx. 22 pcs. detectors. Trigger point 30mA
Weather sensor input / close all Ye s Yes
Alarm output Yes - potential free contact, max. 48V / 0.5A Yes - potential free contact, max. 48V / 0.5A
Failure output Yes - potential free contact, max. 48V / 0.5A Yes - potential free contact, max. 48V / 0.5A
24V DC for external use 24V DC / max. 0.5A - at 230V operation 24V DC / max. 0.5A - at 230V operation
Bus communication Yes - connection of 2-35 pcs. control panels - line detection
Visual (LED) indication in front panel “OK” / “AC fault” / “Low battery” / “Line fault” / “Alarm” / “Comfort open”
Dip switch features “Service hours (LED’s ash in front panel)” / “Comfort opening interval” / “Temperature detection via motor output” /
“Extra line detection via 3 wire motor output” / Fail safe (alarm by line failure)” / “Sprinkler (close by alarm)” /
“Bus comm. settings (react on Bus comm.)” / “Potential free contact for comfort open”
Approvals / Conforms EN12101-10:2005 approved and certied - class A (double supply)
- envir. class 1 (to -15°C). Conform EN12101-9.
Primary supply: 27-28.5V DC rippel 600mw P/P
Secondary supply: 20-27V DC
Interruption time: less than 1.5 sec.
This manual suits for next models
1
Table of contents
Other Actulux Control Panel manuals