
NEUTRAL
SWITCHED LIVE
PERMANENT LIVE
TIMER ADJUSTER
INSTALLATION:
5.Wiring of Standard Model.
Requires Live and Neutral power supply. Refer to internal wiring label for correct connection or see
diagram 1 below.The fan can be either operated from a seperate pullcord switch fitted to the ceiling
of the room or can be connected to the light switch so that the fan will start when the light is
switched on.
6.Wiring of Pullcord Models - This model is not suitable for ceiling fixing.
Requires Live and Neutral power supply.This fan has its own integral pullcord on/off switch, refer to
internal wiring label for correct connection or see diagram 1 below.
7 . W i r i n g o f T i m e r M o d e l .
Requires a Neutral, Switch Live and Permanent Live supply. Refer to internal wiring label or diagram
2 below instruction for correct connection.The fan can be either operated from a seperate pullcord
switch fitted to the ceiling of the room or can be connected to the light switch so the fan will start
when the light is switched on.
LIVE
NEUTRAL
AV X 100 Q S, AV X10 0 QP MO DEL S
AVX100QT, AVX1 0 0QH
IMPORTANT NOTES:
(i) When installing a fan through an external wall, an external wall grille must be fitted at all times.
(ii) This fan must be installed by fixed wiring only.A flexible cord should not be used.
(iii) A double pole fused spur having a contact separation of at least 3mm in all poles MUST be used
and fitted with a 3A fuse.
(iv) For best results this extractor fan should be fitted at least 1.8 metres from the floor or if prefered
in the ceiling. Pullcord models are not suitable for installation in ceilings.
(v) Do not install the unit within a shower cubicle or anywhere else where there is a risk of being
sprayed with water (see our range of shower fans). Fan must be installed in the zone appropriate
to its IP rating (stated on the rating label) and level of circuit protection present. For further
guidance please refer to the zone diagram.
(vi) Switch off mains supply before making electrical connections.All installations must be in
accordance with building and wiring regulations, if in any doubt contact a qualified electrician.
(vii) This fan is double insulated and does not require an earth.
Switch off mains supply before making any electrical connections, if you
are in any doubt about the installation consult a qualified electrician.
This appliance may be used by children aged from 8 years and above and
persons with reduced physical, sensory or mental capabilities or lack of
experience and knowledge if they have been given supervision or
instruction concerning use of the appliance in a safe way and understand
the hazards involved. Children shall not play with the appliance.
Cleaning and user maintenance shall not be made by children without
supervision.
Precautions must be taken to avoid the back-flow of gases into the room
from the open flue of gas or other open-fire appliances when mounted
in outside walls or windows.
Fan must be disconnected from electrical power before any
maintenance or adjustment is carried out.
Zone diagram for locations
with a bath or shower
1. Cut a 112mm (41/2”) hole in the wall. If the fan is to be fixed in the ceiling ensure that the hole is
between the joists. Fit ducting flush to the plaster.
2. Remove the cover from the fan by removing the two small screw caps on the front cover and remove
the two retaining Philips screws.
3. Hold the body of the fan against the wall or ceiling and mark the four screw holes and cable entry.
IMPORTANT: Ensure the fan is square on the wall or ceiling.
4. Bring power cable into position. Leave 230mm (9”) of cable protruding to facilitate connection.
TRIM
CABLE
9mm
6mm
POWER
SUPPLY
Terminal 1 - Neutral Supply
Terminal 2 - Switched Live Supply
Terminal 3 - Permanent Live Supply
TERMINAL
BLOCK
Wiring for Remote Switching
Wire Preparation for connection toTimer and Humidity fans
NEUTRAL
LIVE
REMOTE
SWITCH
3 AMP
DOUBLE POLE
FUSED SPUR
NEUTRAL
SWITCHED LIVE
PERMANENT LIVE
DIAGRAM 2
DIAGRAM 1