ADEMCO 7720 User manual

[~DEIVICOJ
7720
SUBSCRIBER RADIO
INSTALLATION INSTRUCTIONS
Introduction
The 7720 self-contained subscriber radio is the subscriber end of a long Range
Radio alarm reporting system. As a communications link, by analogy to a
telephone-based system, the 7720 is comparable to a digital communicator
connected by telephone line to a central monitoring station.
a
Note to the Installer: Please read these Installation Instructions all
the way through and become completely familiar with them before
attemptingto install a 7720 subscriber radio.
N6376 l/92
www.PDF-Zoo.com
firealarmresources.com

SYSTEM
FEATUFiESm.._...I..._...e......_.._..._.....
.2
OPERATION .. . . . "_"....".. ." -........-.....-..... . -3..
GENERAL.”-----...-..- .”
.... . .-...I-- ..3
AMEhNA ....“_..._. --.-........-.-.---.----. -3
LOW BAllERY SHmDOWN --- :
LEDNDCATlONS ._._...“_.-_.__.. ... .._...s-.-.
RADIOFAULTLED PATTERNS..
...................3
SEITING THE JUMPER OKlO%. ....................4
REMOVING THE nxrs CWER ...................... ..s
WIRING,tmUNTlNG 8 PcwJERING.................5
PKGRAMMlNGTHE7720“...“...”.
..“........
PROGRAMTOOL..
C........
..............
USINGA772OP
PROGRAMMlNG QUESTIONS..
....................6
EXlTlNG PROGRAMMODE.......
. ...................9
ANTENNAhKwmNG
.. ._._."....I._ .". ..... .^.I .... 10
SELECTINGA SflE (FAST MODE).
.......... 10
STANDARD WIRE ANTENNA -mm__ ...10
ANTENNA CONNECTOR KIT m-w_. 10
EsTlffi TI-E 7720._...”.”.“.“-.“.*.-.“.--... .. .”.” 11
RADIOTRANSMISS~ TEST..... ..-_....
...I 1
SYSTEMTEST...“,,” ..-““.. .“““-“““.“-““““^ 11
STATUSS CohrMAND... ... ._.”...-.-....“.... 11
NOTES f OR UL INSTALLATIONS --12
Sf’ECFICATK)NS . ._-._-_._--...__.__.---.“-. 12...
COPWECTfONS
DIAGRAM-.
...._.._...._......_
..
13
SYSTEM FEATURES
Wlreless Reporting: All alarm and
status messages are transmitted to the
master station network via radio signals,
which means faster and more secure
reporting.
Integrated Electronics: The entire
radio link equipment, including interface,
transmitter, power supply, battery and
antenna, is housed in a single unit, requiring
only battery charging power and alarm
inputs from a standard 12 volt alarm panel.
Selection of Input Interfaces: The
7720 can monitor alarm inputs from
Ademco ACP, Ademco ECP. discrete 4
zone contact closures or their electrical
equivalent, or from external gate and
modulation inputs.
Compatibility: The 7720 is compatible
with existing installations using ADEMCO
equipment or other control panels. The
7720 can be used in conjunction with
digital communicators on the same
system,. both acting as backup to one
another (use an ADEMCO 659-EN tine
Monitor connected to a zone input to report
a line cut and backup a digital dialer), while
connecting the radio fault output to a zone
on the dialer.
Built-in LED Indicators: Three LEDs
are used to indicate message
transmissions, low battery conditions and
radio faults. A blinking yellow LED
indicates normal operation.
Built-in Tamper Protection: For
added protection, built-in cover tamper
switches will trigger an alarm whenever the
chassis cover is removed, thus protecting
against unauthorized access to the 7720.
The tamper zone number must be entered
in programming question 25 to enable
protection.
-2-
Antenna Included: The 7720 comes
with an omni-directional wire antenna, and
also features an optional antenna kit
(7720ANT) for using a 7625 antenna.
Programmable Features: The 7720
utilizes EEROM (Electrically Erasable
ROM) technology, which allows the 7720 to
be programmed with a 7720P Programming
Tool. The programming options include
channel assignments for Telco fault input,
inverted trigger inputs, delayed reporting
channels (16 second delay, if selected),
open/close/restore reporting channels,
etc.
Self-Diagnosing Transmitter:
Malfunctions of the transmitter, including
antenna fault, low output power, loss of
external power, low internal DC voltage and
internal radio-frequency circuit problems
can be reported on both the ACP/ECP
interfaces, as well as being transmitted to
the master station network. if the fault
does not predude such transmission. For
other alarm panels, faults can trigger
contact closures on a Form ‘C’ relay to
indite radio faults.
Power Supply: The 7720 is powered by
its own 12 volt battery, which can be
charged by an alarm panel’s output voltage
(14.0-14.2VDC). The charging input draws
approximately 50mA continuous and
40OmA peak current during transmission.
Low Battery Monitoring: The system
will notify the central station of a low
battery condition whenever the battery
voltage drops below 11.2V (& 5%).
Low Battery Shutdown: If for any
reason the battery voltage drops below
9.75 volts, the radio will automatically
shutdown. Refer to the LOW BATTERY
SHUTDOWN section for more information.
:-..
- \
www.PDF-Zoo.com
firealarmresources.com

OPERATION
GENERAL:
The 7720 receives alarm and
restore signals from the alarm control
panel and converts these signals to radio
messages which are transmitted to the
master station network, which in turn
relays the messages to the central station.
The 7720 can monitor either 4 traditional
zone inputs, or can process serial data
from panels which use either ACP or ECP
data formats. For traditional zone inputs,
the first two zones may be configured by
jumper to activate on either 0 volts or
activate on 4.512VDC; zones 3 and 4 are
hard-wired to activate on 4.512VDC.
Zones 1-4 can also be programmed to
invert their input signals.
Upon receiving an alarm, restore, or status
message, the 7720 will transmit the
message to the master station network
after a programmed delay of either 250
milliseconds or 16 seconds. The
transmissions will repeat for approximately
6 minutes (total of 60 messages) to ensure
that the alarm or other report will be
received by the central monitoring station.
The 7720 transmits periodic supervisory
messages to alert the central station to
system problems. A contact closure is
available to indicate a radio fault; this can
be either normally open or normally closed.
In addition, it can be selected to be ‘fail-
safe’ by programming the fault output to be
inverted (i.e. the relay is powered unless
there is a fault). The fault output is between
TBl-1 and TBl-2, which float with reference
to the rest of the circuit.
The n20 also provides status information
via its serial port, thus allowing radio
status to be displayed on command, using
either a 7720P Programming Tool or a
computer terminal. Refer to the TESTING
THE 7720 section for information regarding
the ‘s’ command and status messages.
ANTENNA:The 7720 can use either the
supplied wire antenna, or, by using the
optional 7720ANT connector kit, can use a
7625 omnidirectional antenna, 7625-3dB
antenna (if additional gain is required), a
7674 or 7674-13 YAGI antenna (if
directional antenna is required). The
supplied antenna mounts directly to the
7720. The other antennas can be mounted
remotely (if desired) using preassembled
coaxial cable available from ADEMCO (5’.
12’or 25’ lengths).
LOW BATTERY SHUTDOWN: If
battery voltage drops below 9.75 volts, the
7720 will automatically shutdown, and ALL
LEDs WILL BE OFF. When the battery is
recharged to 10.25 volts, the
LEDs will
begin to flash in rapid unison (see LED
table), until the battery is charged to 12.5
volts. During the charging cycle,
the
7720
&ill not transmit any
messages. The 7720 will resume normal
operation after the battery is fully charged.
LED INDICATIONS
STATE MEANING
SIN Flash With YEL solid =
Message
transmission
With YEL Rashing= HS
antenna test
‘EL Solid Transmission cylcle ON
Rapid Flash Test or FAST message
(1O/second)
Slow Flash Normal operallon
(1
Isecond)
Slower Flash Normal, but low ban. or DC
(1 per 3 set) charging condition detectec
JED Solid Radio Fault detected
Pattern
See Flash Patterns Table
U Consecutive Power On/Reset sequence
.lT Repeated twice before
entering normal mode.
Press [ENTER] during cycle
to enter Program Mode.
Rapid Battery not fully charged.
Unison Repeated about once eve?
(1
O/second) 2 seconds until battery is
charged to 12.5 VDC.
Slow
Unison
Radiois
not properly
@second) programmed. Will continue
until [ENTER] is pressed to
enter programming mode.
1
e
Y
I
RADIO FAULT LED FLASH PATTERNS
# FLASH REASON
1 SL
w-L-L Internal radio fault
2 SSL-L Power detected when
radio
should be off
3 S-L-S-L Full power not
attained
4 S-S-S-L bull power not sustained
after
transmission
5 S-L-L-S VSWR is bad
&Short flash (15OmS);L=Long flash (5OOmS)
&Fault code number.
See ‘S command in the
TESTING THE 7720 section for additional status
information.
-3-
www.PDF-Zoo.com
firealarmresources.com

SETTING THE JUMPER OPTIONS
(Set Before Installing)
(52) Zone Inputs Activate on High
or Low: If using zone input connections,
set the J2 jumper so that zone 1 8 2 inputs
are activated either with a ground or with a
positive voltage, whichever is required.
if the trigger level is set for positive
voltage, +4.5 to +12 volts must be applied
to zones 1 8 2 to trigger an alarm. If the
zone is connected to a normally high
voltage trigger (i.e. goes low on alarm),
invert this zone when programming
(questions 8 & 9).
if ground is selected, zones 1 812 are
intemaily pulled up to 5 volts through a 1Ok
ohm resistor. This voltage should normally
be pulled down (closed contact to ground)
and released for alarm (opening the
contact). if a normally open contact is
being used, invert this zone when
Programming (questions 8 8 9).
(31) Fault Output Select: The radio
fault output relay may be programmed for
either FAIL-SAFE mode (relay always
energized) or LOW CURRENT mode (relay
normally de-energized) by selecting Yes or
No to programming question 13: FLT REL
ON (Y/N). in addition, the relay can be set
for either N.O. or N.C. operation (in either
fail-safe or low current modes) using the Jl
jumper. When fail-safe mode is selected,
the relay will change states (and trigger a
dialer, if connected) in the event of pouver
loss. Note that fail-safe mode increases
the standby current by about lOmA, which
results in lower battery backup time (about
15%) in the event of power loss. Set the Jl
jumper to position A or position B,
according to the following table:
I Pos. A ]
I w I 1 ‘U.O.
VCC ’ K: 1
NC.
(53) ACP/ECP Select: If the ACP or
ECP interface will be used, then set the J3
jumper as indicated for the desired mode.
When connected to the 7720P
Programming Tool, the jumper should be
set in the ECP mode.
REMOVING THE COVER
qemove the 7720’s cover by inserting a
xxewdriver into the 4 removal points at the
mttom of the unit and gently releasing the
ocking tabs from the cover slots as shown.
000
0
F
c
.
c
RADIOFAULTLED
POWERMl3SAGE WAKINGLED
TRANSMITLED
ae
TRIGGERONGROUND
COMMONPIN
TRIGGERDN
4.SVDGl2vDc
Jl
RADIOFAULTCONTACTSPOS
A
COMhUN PIN
RADlOFAULT CONTACTSPOS
B
ND
ECPDATAFOR&MT
COMMONPIN
ACPDATAFORMAT
- JUMPER POSRIONS DIAGRAY-
:
-..
-4-
www.PDF-Zoo.com
firealarmresources.com

WIRING, MOUNTING & POWERING
NOTE: Use coior-coded wires for the power connections; it is recommended that the
positive connection be red and the negative connection be black.
WIRING AT THE CONTROL PANEL:
1. Using an ohm meter, measure the
resistance from the battery positive
terminal to the auxiliary power taksofl
point on the terminal board. if the
resistance is zero ohms, then this
auxiliary We-off point may be used. if
it is greater than zero ohms, then the
positive Power wire for the radio will
have to be spliced to the positive wire
coming from the battery.
IUPORTANT: If the take-off
point Is not fuwtd, a 1A lnllne.
fuse must be put In line at the
control.
2. Connect the negative wire to the
system negative point, which is also
the negative line from the battery.
MOUNTING
5. The 7720 is intended to be mounted to
a horizontal surtace, preferably on a
ceiling, or in an attic location on top of a
joist when using the supplied wire
antenna. if using the 7720ANT antenna
kit, the 7720 can be mounted to a
vertical surface such as a wall or beam.
After determining the best location for
strong radio communication with the
Master Station network using the FAST
Tool, mount the 7720 to a horizontal or
vertical surface, depending on the
antenna used. Be sure to allow access
to the programming port when
mounting.
POWERING UP:
6. After all wiring is complete and the unit
is mounted, apply power to the control
panel, then plug the 7720’s battery
cable into the connector next to the
terminal block. The LEDs will flash
3. Run the aiarm and power wires to the
transmitter location.
WIRING AT THE 7720:
4. The alarm and power wires can be
brought into the transmitter thru the consecutivety for a brief time to allow
base,orthntthecover.iftheyaretobe entry into programming mode. If the
brought thru the cover, cut out the 7720 has been programmed, the LEDs
optional wire entry port. Connect the will begin to flash according to their
functions. if the 7720 has not been
positive and negative power wires to TB
l-l and TB l-2, respectively. install the programmed, the LEDs will flash in
battery into the battery holder, but do unison indefinitely. Important: The
not plug in the battery cable yet panel must be powered before the
battery is plugged in.
LEDs and JUMPERS T
t-BATTERY (12V)
-WIRING
CONNECTIONS DIAGRAM-
-5-
www.PDF-Zoo.com
firealarmresources.com

PROGRAMMING THE 7720
USING A 7720P PROGRAMMING TOOL
The 7720P Programming Tool is powered by the 7720, and connects to the telephone
connector on the 7720 PC Board. Set the 7720 ACPIECP jumper to the ECP position.
Each key of the 7720P has two possible functions, a normal function and a SHIFT function.
To perform a normal key function, simply press the desired key. To perform a SHIFT key
function, press SHIFT key, then press desired function key.
.,-.
IAL & SHIFT KEY (shift
7720P NORM LED lit) FUNCTloNS
Key Normal Key Function SHIFT Key Function
BSESC [SS]: Press to delete entry [ESC]: Resets EEPROM defaults’
l/r [l): Scroll down programming [t]: Scroll up programming
IVY IN]: Press for ‘NO‘ answer. [Y]: Press SHIFT-Y for ‘YES” answer
SHIFT Press before pressing a SHIFT key function.. Will light SHIFT LED.
I
[ LED goes out once akey is pressed. Must press again for each I
I
1SHIFT function desired.
I I/A IAl: numUsed for enterina C.S. ID
I For enterina the number 2 I II
,T-=.
1#/ENTER 1!rariable ent
.* Active only when the ‘F
[#/ENTER]: Press to accept No SHIFT function
REVIEW?’ prompt is displayed.
After connecting the 7720P cable, power up the 7720 (apply power to the control panel and
plug in the battery connector).
Enter programming mode by pressing [ENTER] during the initial power up
period (while LEDs are flashing consecutively).
Pressing SHIFT-X will reset the 7720 to its initiil power up phase if it has already entered
normal mode. The following Warbe displayed:
Press [ENTER] again to begin the programming session. Programming is
accomplished by answering displayed questions. Most questions require only a IY]es or
[N]o response, while others require a numerical response (ID numbers, etc.). For numerical
responses, press [ENTER) to complete the entry and proceed to next question. A *?*
indicates an invalid entry. The current value is displayed on the second line in parenthesis
( ). To accept the current entry, simply press the ENTER key. Use the UP/DOWN arrow
keys to scroll-through the programming questions without changing any values.
-60
www.PDF-Zoo.com
firealarmresources.com

SUBSCRIBER INFORMATION
1.
ID * I
2.
Odd W/N) I
3.
15 MIN SUPU(V/N) I
Enter the 4-digit customer account number,
0001-9999.
Enter Y for odd flag (bit value 1). N for even
system flag (bit value 0).
Status reporting is always enabled. Enter
the desired intenral as follows:
Y = Short form: every 15 minutes @-hour
window for COM-FAIL report)
N = Short form: every hour (standard 24
hour reporting for COM-FAIL)
users skip to #6)
Enter Y if an AlarmNet installation. Enter N
for Private System users (skip to option 6).
Enter the primary central station’s system
ID number, l-7F. Not applicable for Private
System users.
PRIVATE SYSTEM USERS
(AlarmNet users skip
.to W8)
6. Routing Code 1
Enter the-Private system routing code, O-7.
Not applicable for AlarmNet users.
7. Channel # I
Enter the Private System channel number,
1-F. Not applicable for AlarmNet users.
INVERTED ZONE SELECTION
lnuert 21 W/N) 1
8.
9.
IO.
11.
12.
13.
I
lnuert 22 (Y/N)
lnuert 23 W/N)
‘Invert 24 (V/N)
\Invert TestWNI
.
FLT REL ON (Y/N)
For questions 6-12, press Y to invert the
input signal for desired zones l-4 8 Test
zone (question 12).
Press N for normal input signal.
Press Y if fail-safe mode is desired. In this
mode, the fault relay is normally energized
and will &energize in the event of a radio
fault. Note that fail-safe mode draws
slightly more standby current. See the
JUMPER SElTINGS section for setting the
relay output.
-7-
www.PDF-Zoo.com
firealarmresources.com

DELAY ZONE SELECTION
14.
Oeley 21 (YIN)
16.
17.
Delay 24 (Y/N) I
For questions 14-17. press Y for 16 second
reporting delay for desired zones l-4.
Press N for 250 ms reporting delay.
RESTORAC REPORTING ZONE SELECTION
Rest. 21 (V/N)
For questions l&22. press Y
to selectively
enable restoral reporting for desired zones
L
Rest. 22 (Y/N)
’ ld&Tamperzone. -
Press N to disable restoral reporting.
Rest. 23 (Y/N)
\Rest. .24 W/Nl
Rest. Tamp (Y/N)
A ‘yes’ entry has no affect if no tamper
zone number is entered in #25.
OPEN/CLOSE, TELCO 6 TAMPER ZONE SELECl’lON
23.
lo/C Zone
24.
I
Telco Chen
26.
HSRnt. 1st (Y/N) I
27.
I
Flt Letched(Y/N)
Enter the open/close reporting zone
number, 14. A [0] entry disabfes
open/close reporting.
Enter the physicat telco line fault zone, 14.
A [OJentry disables telco detection. If
this
zone Is the same as the open/close
zone, this selection will
automatically
be
set to “0”
and
telco
detectlon will be disabled.
Enter tamper zone, 58. A (01entry
disables tamper ~tection.
Press Y for 135 second interval antenna
test. Press N if no antenna test is desired.
Press Y if radio fault line is to be latched
high upon detection of transmission error.
Press N if a momentary closure upon
detection of transmission error is desired.
.-.
,’ -
-8-
www.PDF-Zoo.com
firealarmresources.com

Press Y if redundant reporting to a second
aentral station is desired. Press N if not
desired (skip to end).
REDUNDANT CENTRAL STATION REPORTING
28.
2nd CS (V or Nl I
1
29.
ZCS21 (Y/N)
30. 2CS 22 W/N) 4
For questions 29-35, press Y to selectively.
enable reporting to second wntral
station
for zones l-4, test
point zone , tamper and system status.
Enter N to disable reporting.
32.
35.
36.
2CS
24 (Y/N)
2CSlest W/N)
2CSTamp (Y/N)
2CSSys Rpt (Y/N)
I
2nd IO t
Enter the 4diiit customer acaxmt number
for the md central station, Oool-9999.
37.
2nd CSID A
E;&ti&y;d central station’s system
I-.
EXITING PROGRAM MODE
When the fast question is answered, the following will be displayed:
RLUIEW? I
To review the programming options
(to ensure that the correct responses have
been made),-press Y. The programming
questions will be displayed again, starting
with question 1. Use the UP/DOWN arrow
keys to scroll through the program fields
without changing any of the values. If a
value requires change, simply type in the
correct value. When the last field is
displayed, the REVIEW? question again
appears.
NOTE:
The programming options can be
globally reset to their factory default
values by pressing ESC at the REVIEW?
prompt. A confirmation prompt will appear.
PressYtore~et,orpressN~oretumto~
REVIEW? prompt. If Y is pressed, all
programmed values will be reset.
To exit program mode,
press N in
response to the REVIEW? question. The
772OPwill display:
DONE I
The Programming Tool can then be
disconnected, or can be used to trigger
test messages. Refer to the TESTING THE
7720 section.
-9-
www.PDF-Zoo.com
firealarmresources.com

ANTENNA MOUNTING
antenmbeiforeinsngths~.
To Install the
l
upplled antenna,
ftrst
replaoe~radio’SCOV0f.PUShltUanben~
inoDthe antenna receptacle until it bottoms
out. The antenna should be uwtlcal and
straight. Mate the antenna until it snaps
intothebc&edposition. Donotbedthe
anterma!
OPTIONAL ANTENNA CONNECTOR KtT (NO. -ANT)
The1720ANT~~lrit~~afaright~~type~adapter~,andanthe
hardrmremquirwd&amounttheameclw. ThiishauldbeusedanytimetheFASTToolor
oUwrcondknsdictatetkfuriaofafwmW antennalo&wt,oritisdesiituusea7625
of76253antemadiM#yonthera&
To InsWI the type “N” cmmmctor, first
mpkefheradWcuvew.Remaveth8plastk
insert from the cover by rotating it 4S”
counter-dockwlse and lifting out. RepW
wlththellwftpfovidedwllhlhe~kit
Tht3connedormaybeinstalledinMyoffarr
positions. Install so that the antanna is
tlvxtM4Nlerpointingupadown,nottDthe
side,whenthetraItsmineJris~ubutt
thecunneJcturusitlgthe4suwwsprovided.
lfa7625or762Hant#maisbbemoursd
directly, then mount the suppfii plastic
bradcettuthewdlabout3inchestromthetup
oftheantennalftieantennaistobemounoed
in a remote lucation. use AdemWplied
antenna cables. Do not attempt to make
arttennacablesyourself,anddonotrrndetany
-ttytosp6wthwn!
- 10 -
www.PDF-Zoo.com
firealarmresources.com

INSTALLATION NOTICE
for 7720 SUBSCRIBER RADIO
BATTERY CHARGING VOLTAGE
The n20 is powered from its internal battery. This battery can be charged
from a control panel whose output voltage (from either its auxiliaryoutput or
directly from its battery) is between 14.0 and 14.2VDC, or can be charged
from its own internal charging circuit when used with an Ademco 1324
(12VAC,40VA)WallTransformer.
The 7720’s charging input will draw approximately 5OmAcontinuous and
4OOmApeak current.
lf the control panel being used cannot supply
the requited voltage and current, a 1324 Transformer must be
used In order to guarantee battery life and radio performance.
If using the 1324 Wall Transformer, a suitable 11OVACreceptacle must be
located. The receptacle’scircuit should not be switchable or be in a location
where it is likelyto be tampered with. Make connections using 20 gauge or
largerwire, and connect to the 7720’sTD2terminals, locatedon the edgeof
the radiobetweenTBl andthe programmingjumpers (seediagrambelow).
If the control panel’s output voltage
Is
suitable for powering the 7720, the
panel’s output voltage connections can be made directly to the 7720 in
accordan& withthe 7720’sInstallationInstructions.
III 3
4
003Oml5
0 555.0575
B
1
.- !
ALARM DEVICE MANUFACWRINQ CD-
A~lONWPlTlWAY~
136 Eileen Way,8yoawt, New York 11701
N5376XX l/92
Copytight@
1992 PITTWAY~CORPOFWTlON
www.PDF-Zoo.com
firealarmresources.com

TESTING THE 7720
RADIO TRANSMISSION TEST
The 7720 is capable of sending a test
message, which can be received by the
central station to confirm the radio’s
communication link to the central station.
For AbrmNet users, the test message will
cause
the master station network to send
a ‘Field Triggered Diagnostic Message’ to
the central station. This message
provides network information as well as
signal strength and frequency
characteristics of the transmitted
messages. Refer to the AlarmNet User’s
Guide for detailed information concerning
these messages. The test message can
be transmitted in any of three ways.
1)The TEST INPUT (terminal 9) of the 7720
can be triggered with a voltage trigger,
which will initiate a 6-6 minute cyde (total
of 60 messages, repeated about once
every 3 seconds) of test message
transmissions. Note that once this cycle
has been initiated by a voltage trigger, it
can be turned off by using the 1 command
described in (2). Otherwise, the messages
will not stop until the end of the cycle.
2) A 7720P Programming Tool can be used,
if connected to the programming connector
of the 7720. To begin a cycle of test
message transmissions, press SHIFT-6 (T
command). This is a toggle function. To end
the transmissions before the end of the
cycle, simply enter the command again.
3) A computer terminal can be used, if
connected to the programming connector
of the 7720. To begin a cycle of test
message transmissions, press SHIFT-T (T
command). This is a toggle function. To
end the transmissions before the end of
the cycle, simply repeat the command.
SYSTEM TEST
Trigger an alarm by any convenient means
and observe the LED indicators on the
radio. The yellow LED should light solidly,
followed by the green LED flashing every
1-3 seconds at first, then slowing during
the 6 minute cycle. This indicates that sn
alarm message has been received at the
radio (yellow), and the transmitter has
been activated (green). The red LED
should not light.
If the zone is programmed for restore,
restore the circuit. The yellow LED should
light solidly and the green LED should flash
again, indicating transmission of the
restore message. The central station
receiver should display alarm/restore
messages for each triggered alarm/restore
performed.
If at any time the red LED lights, a radio
fault has been detected. This could be
caused by a faulty antenna connection, or
might be caused by low internal battery
voltage, or a failure in the radio’s power
cirouits (see LED FLASH PATTERNS on
page 3). The 7720P can display diagnostic
data (.S command) related to the status of
these conditions. See Status Command
section.
Replace the cover (if it was removed) and
perform a control panel system test.
STATUS “S” COMMAND
The status of the 7720 can be viewed on
either a 7720P Programing Tool or an
appropriate terminal when either device is
connected to the serial port of the 7720.
The status display includes zone input
status, test terminal status, tamper
status, battery condition, charging voltage
status and radio fault status. The 2-line
display takes the following form:
1234TeTmBaDcFlt
5555 5 5 + + 0
1234 The numbers 14 represent the four
zone inputs, and follow Ademco
High Speed Format codes:
: NewEvemt
Nw Opening ’
3 Restore
4 New Closing
5 Normal
i Previously Reported Event
Telco New Event
P T&o Previously Reported
Telco Restore
Te test terminal input codes:
1 Currently triggered but test
message cycle is pending due
to transmission of higher
priority message (alarm).
5 Normal (not triggered).
6
Currently triggered & message
cycle either in progress or
completed.
- 11 -
www.PDF-Zoo.com
firealarmresources.com

Tm Tamper status follows High Speed
FmnatcodesabouB.
6s Represents battery condition:
B-w v-w acceptaMe
z Battefy~balow11.2Vf5%
DC Represents chargii vottage:
DCchargingvoftageOK
z DCchargingvoftagebad&
tepot-
V DC charging voltage bad, not
reporled(re~windownot
wired)
A DC charging vobage restored,
not reported as restored
Flt Represenbts Radio Faults. See
LED Rash patterns too.
: Internal mdii fauw
RF power detected without a
vatid transmission*.
3 Forward power never
attainti’
4 RF power not sustained
throughout transmissiun”.
5 VSWR bad (check antenna,
connections and cable)
vsodes1&,2mqllim~dc%.
l
~Codes3&4auldbetheresult0fabad
wdkdlargedbanwy.lfbatt6fyisfoudto
becxmeurlitrcquiresfaclofysanlfae.
SPECIAL NOTES FOR U.L. INSTALLATIONS
The 7720 Remote Subscriber Unit can be used in systems Listed by Underwriter’s
Laboratories for Grada A and Grade B Central Station Mercantile Burgfary. The fofkrwing
additional requirements must be observed for the installation of subscrfber remote
equipment in such systems:
1. Instafhtion must be in a-rdanca with the National Efectrfcal ti and UL811.
2. The 7720 is intended to be connected to dry contact and voltage trigger outputs of a
Listed control unit
3. The772Omustbe ProgrammedaSfdlOWS:
a) Enable Restoraf signals
b) Enabfe high-sea&y sakbecking (programming question 28). The defauft is once
evmy 135 seconds.
4.
FOR GRADE A lNSTALl.AllONS:
A UL Listad communicator must monitor the
radic fault wtput (tmninals 10 & 11) of the 7720. A No. 859EN Teko Line MMlifs
output should ba connected BPan input zone of the 7720 unit. Premises openings and
dosmgs should be sent via the communicator.
5. FOR GRADE B
INSTALIATIONS:
All wiring between the 7729 and the control
panel must be endosad in rfgii conduit (outside walls) or ffexibte conduit (inside walls or
above ceilings) up to the room in which the transmitter is louated. The door and any
windows in this room should be protect& by a UL Listed intrusion detection device
wbiiisaxmacMtoaaoneofthe772O.
SPECIFICATIONS
Diinsions:
Pmm
Current drain:
FUSe:
Input triggaring levels:
-
12
-
8.5’ x 9.5 x 1.7.
14.914.2VDC, suppliad from battary in alarm panel. Voltages
belan14VM:willresultinreduwdbatterylifefwthe7720.
Candmd$ mA (with tzhrgedbatlefy)
3A (ADEk No. 90-12)
Zonesl&2:~bleOvottsor4.5to12volts~10k~
Zones3and4: 4.5to 12voltsinto lokobms
5 watts nominal
928.0125 MHz to 928.3375 MHz, 25 KHz channels
i5PPM
40 to +70 deg. celsius.
99% refativa humidty, non-condensing
bo10.000 ft operating, to 43,900 storage.
Integral 5/8 wave whip.
Optional external Type N connector
.-..
.--.,
www.PDF-Zoo.com
firealarmresources.com

SUMMARY OF CONNECTIONS DIAGRAM
TffiGERONGfUlMD r”t
CumoNPlN u-
TRGGERaN45M(;l2Wr: 5
0
CHANNEL
FREWENCI
1
0 warn25
2 0 928.037s
3 0 92ao62s
4 0 926.0675
5 0 926.112s
6 3 626.*375
7 0 Bze.1625
6 Cl 926.1875
0 C
ANTENNA
0 0
9 0 926.2m I
10 iz g qao~~oooti
O*WLINIYN-
11 ; g28 IAlNiMNElY t
h
immm ,
12
0 626.267s + u#uuuu----~,
13 0 926.312s
14 0 928.3375 ~d-----l I
RADIO f AULT
ZONESlAND d
TRIGGER LEVEL
SERIAL DAW
PROGRAMMING JACK
O-
n
ACPt ACPI
CHARGING
ECP ECP ZONE ZONE ZONE ZONE TEST RADIOFAULT
VOLTAGE @&)
IN OUT 4
-WIRING CONNECTIONS DETAIL-
- 13 -
www.PDF-Zoo.com
firealarmresources.com

.
“FEDERAL COMMUNICATIONS COMMISSION
(FCC) STATEMENT”
This equipment has been tested to FCC requirements and has been found
acceptable for use. The FCC requires the following statement for your
information:
This equipment generates and uses radio frequency energy and if not installed
and used properly, that is, in strii accordance with the manufacturer’s
instructions, may cause interference to radio and television reception. It has
been type tested and found to comply with the limits for a Class B computing
device in aazordance with the specifications in Subpart J of Part 15 of FCC
Rules, which are designed to provide reasonable protection against such
interference in a residential installation. However, there is no guarantee that
interference will not occur in a particular installation. tfthis equipment does
cause interference to radio or television reception; which can be determined by
turning the equipment off and on, the user is encouraged to try to correct the
interference by one or more of the following measures:
. tf using an indoor antenna, have a quality outdoor antenna installed.
l
Reorient the receiving antenna until interference is reduced or eliminated.
. Move the receiver away from the transmitter.
l
Move the antenna leads away from any wire runs to the transmitter.
l
Plug the transmitter into a different outlet so that it and the receiver are on
different branch circuits.
If necessary, the user should consult the dealer or an experienced
radio/television technician for additional suggestions.
The user or installer mayfind the following booklet prepared by the Federal
Communications Commission helpful:
‘Interference Handbook”
This booklet is available from the U.S. Government Printing office, Washington,
DC 20402. Stock No. 004-000-00450-7.
The user shall not make any changes or modifications to the equipment unless
authorized bj the installation Instructions or User’s Manual. Unauthorized
changes or modifications could void the user’s author&yto operate the
equipment.
TO
THE INSTALLER I
Regular maintenance and inspection (at least annually) by the installer and
frequent testing by the user are vital to continuous satisfactory operation of any
alarm system.
The installer should assume the responsibiliiy of developing and offering a
regular maintenance program to the user as well as acquainting the user with the
proper operation and limitations of the alarm system and its component parts.
Recommendations must be included for a specific program of frequent testing (at
- 14 -
www.PDF-Zoo.com
firealarmresources.com

THE LIMITATJONS OF THIS RADIO COMMUNICATIONS SYSTEM
While this 900 MHz Long Range Radio communications system is part of an
advanced and sophisticated security system, it does not offer guaranteed
protection against burglary or fire, nor does it guarantee communication 01
burglary or fire warning signals to a central station. Any alarm system, or any
communications system, whether commercial or residential, is subject to
compromise, or failure to warn, for a variety of reasons. Examples of some 01
these reasons are:
b Intruders may gain access through unprotected openings or have technical
sophistication to bypass an alarm sensor, and then disconnect an alarm
communicating radio transmitter.
b Signals sent by 900 MHz radio transmitters may be blocked by metal,
mountains, hills, foliage and other natural and man made obstructions before
they are received by a master receiving station or sent to a central station,
Even a path previously verified as acceptable -may periodically change its
characteristics.
1 Long-range radio communication transmitters will not work without power.
Radio transmitters require a battery to work properly in the absence of A.C.
power. A weak or dead battery, or improperly installed batteries may prevenl
these devices ,from functioning properly if A.C. power is disrupted for any
reason.
1 Radio communication systems are subject to external interference, natural or
man-made, intentional or coincidental, that may keep a signal or group oi
signals from being successfully received by a master receiving station or a
central station. In addition, one-way radio communication devices receive no
acknowledgment from a master receiving station that their signals are being
successfully received. Signals transmitted may clash with those transmitted
from other systems. While statistical estimates predict successful operation,
if the guidelines in the system manuals are followed, the operation of this
system is still probabilistic in nature and may be subject to random signal
failures.
1 Radio communication devices may change their characteristics over time.
Such parameters as frequency, modulation..and power should be properly
monitored periodically, with required adjustments made by qualified personnel.
1 Radio communication devices must be installed by qualified personnel,
Improper installation or selection of a transmitter’s location may cause
intermittent or unreliable performance.
4ny electronic or mechanical device can fail. The most common cause of an
alarm system or a radio communications system not functioning properly when
an intrusion or fire occurs is inadequate maintenance, maintenance that is
ntended to find such failures as soon as possible. This alarm and communication
;ystem should be tested weekly to be sure all sensors and transmitters are
workingproperly.
nstalling an alarm system may make one eligible for lower insurance rates, bul
in alarm system is not a substitute for adequate insurance. Honieowners,
lroperty owners, business owners and renters should continue to insure theil
lroperty and lives.
- 15 -
www.PDF-Zoo.com
firealarmresources.com

ADEMCO LIMITED WARRANTY
Alarm Device Manufacturing Company, a Division of Pittway Corporation, and it:
Idivisions, subsidiaries and affiliates (‘Seller”),
165
Eileen Way, Syosset, New
York 11791, warrants its products to be in conformance with its own plans ant
specifications and to be free from defects in materials and workmanship under
normal use and service for 18 months from the date stamp control on the produa
or, for products not having an Ademco date stamp, for 12 months from date oi
original purchase unless the installation instructions or catalog sets forth a
shorter period, in which case the shorter period shall appty. Seller’s obligatior
shall be limited to repairing or replacing, at its option, free of charge for materials
or labor, any product which is proved not in compliance with Seller’s
specifications or proves defective in materials or workmanship under normal use
and service. Seller shall have no obligation under this Limited Warranty OI
otherwise if the product is altered or improperly repaired or serviced by anyons
other than Ademco factory service. For warranty service, return produd
transportation prepaid, to Ademco Factory Service, 165 Eileen Way, Syosset,
New York 11791.
THERE ARE NO WARRANTIES, EXPRESS OR IMPLIED, OF
MERCHANTABILITY, OR FITNESS FOR A PARTICULAR PURPOSE OR
OTHERWISE, WHICH EXTEND BEYOND THE DESCRIPTION ON THE FACE
HEREOF. IN NO CASE SHALL SELLER BE LIABLE TO ANYONE FOR ANY
CONSEQUENTIAL OR INCIDENTAL DAMAGES FOR BREACH OF THIS OR ANY
OTHER WARRANTY, EXPRESS OR IMPLIED,OR UPONANY OTHER BASIS OF
LIABILITY WHATSOEVER, EVEN IF THE LOSS OR DAMAGE IS CAUSED BY
THE SELLER’SOWN NEGLIGENCE OR FAULT.
Seller does not represent that the products it sells may not be compromised or
circumvented; that the products will prevent any personal injury or property loss
by burglary, robbery, fire or otherwise; or that the products will in all cases
provide adequate warning or protection. Customer understands that a properly
installed and maintained alarm may only reduce the risk of a burglary, robbery,
fire or other events occurring without providing-an alarm, but it is-not insurance or
a guarantee that such will not occur or that there will be no personal injury or
property loss as a result. CONSEQUENTLY, SELLER SHALL HAVE NO
LIABILITY FOR ANY PERSONAL INJURY, PROPERTY DAMAGE OR OTHER
LOSS BASED ON A CLAIM THE PRODUCT FAILED TO GIVE WARNING.
HOWEVER, IF SELLER IS HELD LIABLE, WHETHER DIRECTLY OR
INDIRECTLY, FOR ANY LOSS OR DAMAGE ARISING UNDER THIS LIMITED
WARRANTY OR OTHERWISE, REGARDLESS OF CAUSE OR ORIGIN,
SELLERS MAXIMUM LIABILITY SHALL NOT IN ANY CASE EXCEED THE
PURCHASEPRICE OF THE PRODUCT,WHICH SHALL BETHE COMPLETE AND
EXCLUSIVE REMEDY AGAINST SELLER. This warranty replaces any previous
warranties and is the only warranty made by Seller on this product. No increase
3r alteration, written or verbal, of the obligations of this Limited Warranty is
authorized.
.
?SUDEMCO,
ALARM DEVICE MANUFACTURING CO-
A
OMSON
OF PlFlWAV
CDWCNWllON
t 165 Eileen Way, Syosset, New York 11791
N5376 l/Q2
Copyright @1992 Pfl-fVVAY CORPORATION
www.PDF-Zoo.com
firealarmresources.com
Other manuals for 7720
1
Table of contents
Other ADEMCO Radio manuals