ADS-tec StoraXe PowerBooster GSS0608 User manual

StoraXe PowerBooster
Compact storage system
GSS0608

Copyright © ads-tec Energy GmbH.
Copies and reproductions are only permitted with the permission of the author.
Changes and errors excepted.

StoraXe PowerBooster GSS0608
Table of Contents
1Transport and advance information
2Instruction sheet in case of fire
3Declaration of conformity
4Instruction manual
5Electrical diagram
6Instructions smoke detector
7 UN38.8 confirmation and MSDS


Preliminary information
Page 1of 14 GSS0608 Version: 1.3
Transport and
preliminary information
StoraXe PowerBooster
Compact Storage System
GSS0608
Version 1.3
Transport and preliminary
information

Preliminary information
Page 2of 14 GSS0608 Version: 1.3
Table of Contents
Table of Contents ................................................................................................................ 2
1Transport information .................................................................................................. 3
2Installation information ................................................................................................ 4
3Requirements regarding installation location ............................................................ 6
3.1.1 Environmental conditions 6
3.1.2 Requirements regarding installation location 6
4Technical data .............................................................................................................. 8
5Temporary storage of the battery modules ................................................................ 9
6Bottom view of unit .....................................................................................................10
7Checklist for commissioning......................................................................................11
8Contact.........................................................................................................................13
8.1 Support ADS-TEC 13
8.2 Company address 13
9Appendix: Extract of the electrical diagram ..............................................................14

Preliminary information
Page 3of 14 GSS0608 Version: 1.3
1 Transport information
(Detail from the instruction manual)
The battery modules are declared as dangerous goods when transported. Follow the relevant
instructions on the packaging.
The storage system is delivered in 3 parts:
•One pallet with storage system preassembled, without battery modules (approx. 800 kg
gross).
•Two pallets with 2x 4 battery modules, corresponding power and communication cables and
manual (2x 330 kg gross).
CAUTION
Risk of irreversible damage to the components!
Improper transport can irreversibly damage components.
Use only means of transport that are designed for the weight of the storage system
and battery modules.
Transport the battery modules to the final location separately from the storage
system.
Transport the storage system upright with the help of a forklift to the final location.
Bear in mind that the centre of gravity of the storage system is not positioned
centrally.
Move the storage system only when in a lifted state.
Use non-slip mats on any surfaces where the storage system will have to be set
down temporarily.
WARNING
Hazard from heavy loads!
If the storage system or the battery modules tip over or fall, they can cause serious
injuries.
Hazard from falling or tipping loads.
Risk of crushing hands and feet during transport.
The centre of gravity of the storage system is noted on the packaging as follows:

Preliminary information
Page 4of 14 GSS0608 Version: 1.3
2 Installation information
(Detail from the information of the housing manufacturer – german/english)
Lösen Sie die Befestigungsschrauben des vorderen Sockels.
Unscrew the fastening screws of the front panel.
Schieben Sie die Frontblende nach vorne
und entfernen Sie diese.
Slide the front panel forward and remove it.
Schieben Sie die seitliche Blende nach vorne und entfernen Sie diese.
Slide the side panel forward and remove it.
Blenden entfernen / Remove panels

Preliminary information
Page 5of 14 GSS0608 Version: 1.3
Lösen Sie die 4 Befestigungsschrauben und
entfernen Sie die Palette.
Loosen the 4 fastening screws and remove the
pallet.
Palette entfernen / Remove pallet

Preliminary information
Page 6of 14 GSS0608 Version: 1.3
3 Requirements regarding installation location
(Detail from the instruction manual)
The system is designed for stationary use in an outdoor area. Make certain that the specified
environmental conditions are maintained at all times. Use in non-specified environments,
e.g. on board ships, in explosive atmospheres or at high altitude (see the climatic environmental
conditions) is prohibited.
CAUTION
Hazard due to condensation!
Condensation may form if the system has not had sufficient time to settle to the
environmental conditions following transport or before it is put into operation
again. (Connection to AC supply is required.)
3.1.1 Environmental conditions
Observe the environmental conditions information in the technical data (4 Technical data).
3.1.2 Requirements regarding installation location
Please note that the battery system may not be set up and operated
•in buildings, garages, courtyards and other covered structures
•in areas where there is a risk of flooding
•in areas where there is a risk of fire and explosion
•in the vicinity of combustible materials
•and in areas with sandstorms
•in permanent residential areas
•in the vicinity of escape routes
.
Installation conditions:
•The "Commissioning requirements" checklist must be completed and signed
(7 Checklist for commissioning).
•The system is only suitable for outdoor installation.
•Observe the following floor space requirements for the system:
−The floor space is to be constructed at the installation location in accordance with the local
conditions and technical data (4 Technical data)
−Wind-protected (e.g. in the lee of a building)
−The floor space is exactly horizontal.
−Cable entry is from below.
−The floor space has the required load capacity for the 1.25 t weight of the system and has
to withstand this load permanently.
If applicable, also take into account the weight of the means of transport.
−Sufficient drainage is available.
•Earthing via ring earth electrode for flexible connection cable (min. 16 mm²) according to
national and local regulations and conditions must be in place.
•Note that ventilation openings must be kept clear.
−The air at the ventilation openings must be able to circulate freely.
−During the entire operating time, no leaves, dirt, etc. must be sucked in from the ventilation
openings.
•Protect the system against penetrating water (groundwater or flood hazard area).

Preliminary information
Page 7of 14 GSS0608 Version: 1.3
•Keep the existing housing doors closed.
•Observe the required minimum distances of 1.5 m to adjacent structures. Make additional
spacing allowances for open doors and any escape routes.
When installing in built-up areas, observe the local noise abatement regulations (Germany:
"Technische Anleitung zum Schutz gegen Lärm" (Technical Instructions for Protection against Noise),
abbreviated "TA Lärm"). Observe the resulting minimum distances to residential buildings.
Power connections:
Observe the information given in the electrical diagram (9 Appendix: Electrical diagram).

Preliminary information
Page 8of 14 GSS0608 Version: 1.3
4 Technical data
GSS0608
System
System type
AC coupled storage system with outdoor
cabinet
Control / functions
ADS-TEC Energy apps:
peak-shaving, optimisation of personal
consumption,
ADS-TEC master interface
Network connection Ethernet, RJ45, LTE
Inverter Integrated
Grid connection
Effective power
60 kW
Apparent power
60 kVA
Mains voltage
400 VAC
Grid type
TN-S with 3Ph + N + PE (stationary)
Grid frequency
50 Hz
Battery storage
system
Battery technology
Lithium-ion
Nominal energy content
84,6 kWh
Battery cells²
Cell chemistry
Lithium-NMC
General data
Installation location
Outdoor
Temperature range
-20 °C to +40 °C
Protection class
IP55
Guarantee of current market value
(battery cells)
Up to 10 years (in combination with BatX)
Vandalism class
IK10
Dimensions WxHxD
1430 x 2500 x 940 mm (+/-20 mm)
Weight
Approx. 1,250 kg (fully equipped)
Standards
List of the applied harmonised
standards
Wireless ETSI EN 301 908-1
V13.1.1; ETSI EN 301 908-13
V13.1.1
EMC ETSI EN 301 489-1 V2.2.3;
EN 61000-6-2:2005;
EN 61000-6-3:2021
Safety EN 62368-1:2014 + AC:2015;
EN 62311:2008;
EN 61439-1:2011
List of the applied regulations,
standards and applications
EMC ETSI EN 301 489-52 V1.1.0
Safety EN IEC 61439-7:2020;
IEC 62485-5:2020;
EN 62619:2017
Functional
safety EN 61508 series ed. 2
Miscellaneous VDE-AR-E 2510-2:2021
UN 38.3 Revision 7:2019
(on battery module layerl)

Preliminary information
Page 9of 14 GSS0608 Version: 1.3
5 Temporary storage of the battery modules
Observe the manufacturer specifications and safety data sheets of the battery cell.
•It is strongly advised that directive VDS-3103: 2019-06 also be observed.
•Store the battery modules in their original packaging in a dry, ideally air-conditioned indoor
space until installed.
•Avoid direct sunlight, large temperature fluctuations and frost.
CAUTION
Damage to property due to incorrect storage!
Store the battery modules properly in the original packaging until installation
according to the information in the battery module data sheet.
No direct sunlight, no large temperature fluctuations, no frost.
Storage temperature: 0 to + 40°C.
Avoid condensation.
Condensation can occur if the battery module has not been sufficiently
climatically adjusted after transport or before installation.

Preliminary information
Page 10 of 14 GSS0608 Version: 1.3
6 Bottom view of unit

Preliminary information
Page 11 of 14 GSS0608 Version: 1.3
7 Checklist for commissioning

Preliminary information
Page 13 of 14 GSS0608 Version: 1.3
8 Contact
8.1 Support ADS-TEC
The ADS-TEC support team is available for inquiries from direct customers between
8:30am and 5:00pm, Monday to Friday. The support team can be reached via phone or e-mail:
Phone: +49 7022 2522-203
Email: support.est@ads-tec-energy.com
Alternatively, you can contact us by completing a support form on our website www.ads-tec-
energy.com. Our Support team will then get in touch with you as soon as possible.
8.2 Company address
ads-tec Energy GmbH
Heinrich-Hertz-Str.1
72622 Nürtingen
Germany
Phone: +49 7022 2522-201
Email: energy@ads-tec-energy.com
Home: www.ads-tec-energy.com

Preliminary information
Page 14 of 14 GSS0608 Version: 1.3
9 Appendix: Extract of the electrical diagram

Instruction sheet - Operating regulations and rules of conduct
For handling lithium-ion batteries
Place the lled form clearly visible near the system!
Whoever operates a system is responsible for its proper operation
Information about the system
Designation and address of the system:
Operating company of the system:
Model (lithium-ion) and battery capacity (kWh):
Conduct in case of re
1. Report re
2. Get to safety
3. Make no attempts to
extinguish the re
Operational
contact person: ..........................
Fire brigade 112
Police 110
- Follow the instructions
- Help people in danger
- Clear the danger zone
- Wait for re brigades
- Make no attempts to extinguish the
re
- Close o danger zone over a large
area
Stay calm
Danger warning!
Batteries Risk of explosion
in case of re
Electrical
voltage

Operating regulations and rules of conduct
For handling lithium-ion batteries
Place the lled form clearly visible near the system!
Please provide this information sheet (or an information sheet according to
local regulations) to the local re protection ocer / to the control center for
the local re protection concept.
Table of contents