
WSS6 Series - IOM
WSS6 SERIES – IOM (REV. A 4/21) 20
CONTROLS CONTINUED
BOILERLESS CONTROL
The system can operate in boilerless mode by switching
Dip 1.5. If CO1 goes below the setting of Dip 1.6 the
compressor will be de-energized and control goes into
emergency heat mode staging on “W1”. The compressor
will be locked out for 60 minutes to prevent nuisance
cycling.
The set point for boiler less changeover temperature can
be adjusted by switching Dip 1.6.
WATER-COIL LOW TEMPERATURE CUT-OUT LIMIT
Jumpers JW1-CO1 provide field selection of the
temperature limit settings for CO1.
Not Clipped = 30°F Clipped = 10°F
CAUTION
For all applications below 50°F entering water
temperature, anti-freeze solution is required. Failure
to follow this warning could result in heat exchanger,
equipment or property damage.
ALARM RELAY SETTING
Jumper 3 (JW3 Alarm) provides field selection of alarm
relay terminal AL2 to be jumpered to 24VAC or to be
dry. The alarm relay is activated during lockout mode.
Not Clipped = AL2 Connected to “R”
Clipped = AL2 dry contacts (No connection)
DEHUMIDIFICATION MODE
The system can operate in Dehumidification mode by
switching Dip 1.4 on the WSCM module. In this mode,
the unit will run continuously in fan speed G2 when Y,O,
G calls are given to the board. Dehumidification mode
will not run in heating mode.
WSCM SAFETY FEATURES
ANTI-SHORT CYCLE PROTECTION
The WSCM module incorporates a 5 minute anti-short
cycle protection for the compressor.
RANDOM START
The WSCM module features a 5-80s random start upon
receiving a call to operate.
FAULT RETRY
While in Fault Retry Mode the LED will display a code
representing retry and the fault code. The unit will
initiate the Anti-short cycle timer and try to restart after
the delay. If 3 consecutive faults occur without satisfying
the thermostat the unit will go into hard lockout. The
last fault causing the lockout will be stored in memory
and displayed on the two digit LED display.
WATER-COIL LOW TEMPERATURE CUT-OUT (CO1)
The control module will recognize a CO1 fault during a
compressor run cycle if:
a) Thermistor temperature is below the selected set
point limit.
b) The thermistor temperature is rising at a rate less
than 2°F per 30s time period. The CO1 input is
bypassed for the first 120s of a compressor run
cycle. On the second and third retry CO1 is
bypassed for the initial 90s and 60s of run-time
respectively.
AIR COIL LOW TEMPERATURE CUT-OUT (CO2)
The control module will recognize a CO2 fault during a
compressor run cycle if:
a) Thermistor temperature is below the selected set
point limit.
b) The thermistor temperature is rising at a rate less
than 2°F per 30s time period. The CO2 input is
bypassed for the first 120s of a compressor run
cycle.
CONDENSATE OVERFLOW SENSOR
The condensate overflow sensor must sense overflow
levels for 30 continuous second to initiate a COF fault.
The condensate overflow sensor will be monitored
during the compressor run cycle.
LOW PRESSURE
The low pressure switch must be open and remain open
for 30 continuous seconds during the “on” cycle to be
recognized as a low pressure fault. The low pressure
switch input is bypassed for the initial 120s of
compressor run-time.
HIGH PRESSURE
If the high-pressure switch opens at any time, the
compressor relay is de-energized immediately.