Parameters description
Cd –Access code: it is necessary to unlock the parameters
so that they can be adjusted. To unlock them, enter the
value 28 in “Cd” for basic parameterization mode or 38 for
full mode. If this is not done, parameter values can only be
viewed and not changed. This parameter prevents unau-
thorized persons from changing programmed values.
SP –Setpoint (reservoir overheating temperature): sets
the maximum temperature allowed in the reservoir. NOTE:
This parameter is adjusted from the main screen, by holding
the “Set” key and using the “Up” or “Down” key.
td –Default displayed value: determines which temper-
ature will have priority for visualization on the display main
screen, “t1” temperature in the collector, “t2” temperature
in the reservoir, and “dd” temperature difference between
collector and reservoir (t1-t2).
r0 –Turn-on temperature difference (t1 –t2): deter-
mines the minimum temperature difference for turning on
the relay. For example, if it is set to “6°C”, the pump will turn
on when the temperature in the reservoir is at least 6 de-
grees lower than the temperature in the collector.
r1 –Turn-off temperature difference (t1 –t2): deter-
mines the minimum temperature difference for turning off
the relay. For example, if it is set to “2°C”, the pump will turn
off when the temperature between the reservoir and col-
lector is 2 degrees or less.
r9 –Pump relay minimum power-up delay: defines a
time period after powering up the device in which the pump
relay remains off, during this period the device will only in-
dicate the temperature value. This parameter also protects
the pump from constant starts in case of consecutive power
outages.
P0 –Collector´s antifreeze temperature (Turn-on the
pump): this parameter is used in very cold regions where
the water in the collector may freeze. In this parameter, the
user sets a minimum temperature in the collector to turn on
the pump, in order to circulate the water and try to prevent
it from freezing.
P1 –Collector´s superheat temperature (Turn-off the
pump): in this parameter, the user will program a maximum
temperature in the collector. When this value is exceeded,
the controller will keep the pump turned off, to prevent this
excessively hot water from going to the reservoir/pool.
h2 –Superheat temperature hysteresis (P1): in this pa-
rameter, the user will set a hysteresis for the overheating
protection of the reservoir.
P4 –Highest allowed setpoint: this parameter will limit
the highest setpoint/superheating temperature for the res-
ervoir.
P6 –Recirculation (Turn-on the pump for 25s every 25
min): if the user sets “YES” in this parameter, the pump will
turn on every 25 min to recirculate the water through the
piping. NOTE: the water will only recirculate if no protection
parameter is active and if the collector temperature is
greater than 20 °C and greater than the reservoir tempera-
ture.
P7 –Cooling: this parameter is used to cool the water in
the reservoir if it is warmer than the collector is. If set to
“YES”, the pump will turn on when the reservoir tempera-
ture is 3°C degrees higher than the collector temperature.
P8 –Maximum time of the activated pump, if activated
manually: In this parameter, it is possible to set a maximum
time in which the pump will remain on if it is activated man-
ually using the “A” key. This parameter is used to prevent
the pump from remaining on for a long time if the user does
not manually turn it off.
P9 –Maximum time of the activated pump, if activated
by the diference (t1-t2): in this parameter, it is possible to
program a maximum time the pump will stay on if it is
started by the temperature difference parameter (r0).
NOTE: Upon reaching the end of the time set in parameter
P9, the controller turns off the pump and the display will
show "P9" until the temperature difference (t1 - t2) is
smaller than the temperature difference set to turn off the
pump (r1).
–Parameters enabled in full mode (Cd = 38) –
FP –On/Off key function: defines the function of the
On/Off key, as follows:
- 0 –key disabled;
- 1 –key activates/deactivates standby mode: the
power key will turn-on/off the system's standby mode;
- 2 –key activates/deactivates the control action, but
keeps the display on showing the temperature.
bt –Lock changes 10s after the last keystroke: in this pa-
rameter, the user can enable a block for 10 seconds, as fol-
lows:
- oFF –function disabled;
- 1 –Lock all changes, except the Setpoint;
- 2 –Lock all changes.
Ed –Network address: this parameter defines the device
address in standard RS-485 communication with the ISX10
(Arcsys). If the system has two or more controllers, they
must not have the same “Ed” value.
bU –Lock remote changes (Arcsys or ArcSys Cloud): this
parameter, when set to “YES”, prevents changes to control-
ler parameters via Arcsys or ArcsysCloud.
A0 –Hysteresis of the reservoir temperature alarm: this
parameter defines the alarm temperature differential.
A1 –Low-temperature reservoir alarm limit (t2): defines
the lower temperature alarm limit for the reservoir. If this
limit is reached, the display will flash and the relay output
will be turned off.
A2 –High-temperature reservoir alarm limit (t2): defines
the upper temperature alarm limit for the reservoir. If this
limit is reached, the display will flash and the relay output
will be turned off.
SP Setpoint (reservoir overheating temperature)
td Default displayed value
r0 Turn-on temperature difference (t1 –t2)
r1 Turn-off temperature difference (t1 –t2)
r9 Pump relay minimum power-up delay
P0 Collector´s antifreeze temperature (Turn on the pump)
P1 Collector´s superheat temperature (Turn off the pump)
h2 Superheat temperature hysteresis (P1)
P4 Highest allowed setpoint
P6 Recirculation (Turn-on the pump for 25 s every 25 min)
P8 Max. time of the activated pump, if activated manually
P9 Max. time of the activated pump, if activated by the difference (t1-t2)
Parameters below only appear if Cd = 38
bt Lock changes 10s after last keystroke
bU Lock remote changes (Arcsys or ArcSys Cloud)
A0 Hysteresis of the reservoir temperature alarm
A1 Low-temperature reservoir alarm limit (t2)
A2 High-temperature reservoir alarm limit (t2)
A4 Alarm sending frequency
FL Temperature digital filter
C1 Collector sensor calibration
C2 Reservoir sensor calibration
tL Minimum historical reservoir temperature (t2)
tH Maximum historical reservoir temperature (t2)