AGS Parksafe Control Panel User manual

Installation & Operation Manual Parksafe
AGS Parksafe Panel - IOM Iss: 6 10-20 1
PARKSAFE
Ventilation Control Panel
Installation & Operation Manual
Please read this manual carefully and retain for future use.
The control panel is designed to be paired with Parksafe Nitrogen Dioxide (NO2) and Carbon Monoxide (CO)
gas detectors for installation in car parking facilities and enclosed garages. The control panel will monitor up to
16 gas detectors and automatically control ventilation systems according to gas levels and temperature.
The information contained within this manual should be referenced for typical installation and operation only.
For specific requirements that may deviate from the information in this guide –contact your supplier.

Installation & Operation Manual Parksafe
AGS Parksafe Panel - IOM Iss: 6 10-20 2
CONTENTS
IMPORTANT WARNING STATEMENTS .........................................................................3
Manufacturer’s Warranty..................................................................................................................... 3
INSTALLATION................................................................................................................4
Planning................................................................................................................................................... 4
Typical Installation Arrangement........................................................................................................ 4
Mounting ................................................................................................................................................. 5
Board Connections Diagram .............................................................................................................. 5
Board Connections Overview............................................................................................................. 6
Wiring your Detector............................................................................................................................. 7
Detector Chain ID Switches ................................................................................................................ 7
Creating a Detector Chain ................................................................................................................. 8
120 ohm Termination Resistance........................................................................................................ 8
Access Configuration Settings ............................................................................................................ 8
Settings Menu......................................................................................................................................... 9
Menu Options Explained...................................................................................................................... 9
Factory Set Condition ........................................................................................................................... 9
Quick Tips .............................................................................................................................................. 10
Specification......................................................................................................................................... 10
OPERATION...................................................................................................................11
First Power Up ....................................................................................................................................... 11
Home Screen Status & Condition Overview .................................................................................. 11
Temperature Status & Icon ................................................................................................................ 11
Silence & Reset .................................................................................................................................... 12
Accessing Detector Status Information .......................................................................................... 12
Detector Status .................................................................................................................................... 12
Gas Alarm Levels ................................................................................................................................. 12
General Maintenance ....................................................................................................................... 13
EOL or Service Indication ................................................................................................................... 13
Bump Testing ........................................................................................................................................ 14
Service Record..................................................................................................................................... 15
INSTALLATION DETAILS..............................................................................................16

Installation & Operation Manual Parksafe
AGS Parksafe Panel - IOM Iss: 6 10-20 3
IMPORTANT WARNING STATEMENTS
Please take the time to thoroughly read this user’s guide which should be retained for future reference.
It is recommended that this device be commissioned upon installation and serviced at least annually.
Do not apply lighter gas or other aerosols to detectors –this will cause extreme damage to the gas sensing elements.
High concentrations of alcohol found in many products may damage, deteriorate or affect the gas sensing elements of the
detectors –Avoid exposure near your devices.
This device is designed to detect the gas displayed on screen and in the designated zone area from any source of
combustion or dangerous level. It is NOT designed to detect smoke, fire or other gases and should NOT be used as such.
This device provides early warning of the presence of gas, usually before a healthy adult would experience symptoms. This
early warning is possible provided your alarm is located, installed and maintained as described in this guide.
Never ignore your device when in alarm. Actuation of your alarm indicates the presence of an error or significant issue that
requires immediate attention.
This device requires a continual supply of electrical power –it will not work without power.
This device should not be used to substitute proper installation, use and/or maintenance of fuel burning appliances including
appropriate ventilation and exhaust systems.
This device does not prevent dangerous gasses from occurring or accumulating.
This unit may not fully safeguard individuals with specific medical conditions. If in doubt, consult a doctor/physician.
Your product should reach you in perfect condition, if you suspect it is damaged, contact your supplier.
Manufacturer’s Warranty
Warranty coverage:
The manufacturer warrants to the original consumer purchaser, that this product will be free of defects in material and workmanship for a
period of three (3) years from date of purchase. The manufacturer’s liability hereunder is limited to replacement of the product with repaired
product at the discretion of the manufacture. This warranty is void if the product has been damaged by accident, unreasonable use, neglect,
tampering or other causes not arising from defects in material or workmanship. This warranty extends to the original consumer purchaser of the
product only.
Warranty disclaimers:
Any implied warranties arising out of this sale, including but not limited to the implied warranties of description, merchantability and intended
operational purpose, are limited in duration to the above warranty period. In no event shall the manufacturer be liable for loss of use of this
product or for any indirect, special, incidental or consequential damages, or costs, or expenses incurred by the consumer or any other user of
this product, whether due to a breach of contract, negligence, strict liability in tort or otherwise. The manufacturer shall have no liability for any
personal injury, property damage or any special, incidental, contingent or consequential damage of any kind resulting from gas leakage, fire
or explosion. This warranty does not affect your statutory rights.
Warranty Performance:
During the above warranty period, your product will be replaced with a comparable product if the defective product is returned together with
proof of purchase date. The replacement product will be in warranty for the remainder of the original warranty period or for six months –
whichever is the greatest.
Information on waste disposal for consumers of electrical & electronic equipment.
When this product has reached the end of its life it must be treated as Waste Electrical & Electronics Equipment (WEEE).
Any WEEE marked products must not be mixed with general household waste, but kept separate for the treatment, recovery and recycling of
the materials used. Please contact your supplier or local authority for details of recycling schemes in your area.

Installation & Operation Manual Parksafe
AGS Parksafe Panel - IOM Iss: 6 10-20 4
INSTALLATION
Planning
The Parksafe control panel is designed for installation into car parking facilities and enclosed
garages. It is designed to be paired with AGS Parksafe Gas Detectors (Nitrogen Dioxide and
Carbon Monoxide) that will be linked via MODBUS back to the control panel and monitor the
connected detectors in numbers up to 16 (per control panel) and automatically control ventilation
systems according to gas levels and an optional temperature level.
The Parksafe will make or break a dry contact internally on OUTPUT 1 and a second contact on
OUTPUT 2. This is to have a live feed to the ventilation system wired through the contact so that the
Parksafe can activate ventilation/ fans, this can either be via a direct live feed or via a run signal.
There is another output relay that will activate after OUTPUT 2 has been activated for an optional
extended period of time. This can be used for a link to the BMS or other external indication device.
The Parksafe also has a 0-10VDC output to allow the panel to drive VSD’s based on gas level
outputs. The Parksafe control panel is designed to be located in an office or other suitable area
within a carpark not accessible to the public.
Please refer to your detector manual for important information regarding coverage, location and
positioning including areas and conditions to avoid!
Typical Installation Arrangement
Place the control panel in accordance with regulations ensuring optimum access and monitoring.
The control panel should be located outside of the hazardous area that it is monitoring.
Easy accessibility is required both for status observation and alarm purposes.
Where connections may exceed 500 yards from one control panel –Contact your supplier!
The use of sound strobes are highly recommended!

Installation & Operation Manual Parksafe
AGS Parksafe Panel - IOM Iss: 6 10-20 5
Mounting
Unpack all the parts!
Designed for surface mounting, it must be installed by a licensed, insured contractor.
1. Carefully remove the front cover from the unit by
unscrewing the four bolts located at each corner. To do
this –use the socket wrench provided.
2. Mark the four screw holes located on the back of the
enclosure to the wall. Ensure the wall surface is flat to
prevent base distortion.
3. After executing the mounting and the connections –
replace the front cover and insert the security caps over
the four bolts.
Board Connections Diagram
Be careful when creating access for cables –Damage to boards will void any warranty!
Any damage attempting to remove the circuit board parts may void any warranty!
Wiring of different circuits shall be separated by means of routing, clamping or barrier!
All Class 2 wiring is to be installed within flexible tubing to maintain segregation between circuits!
For MODBUS communications, a shielded and twisted pair cable is used!

Installation & Operation Manual Parksafe
AGS Parksafe Panel - IOM Iss: 6 10-20 6
Board Connections Overview
1. POWER/ LINE IN 110-120Vac mains power should be supplied to the [POWER/LINE IN] connector
using a 3 core cable and fused at 3A. When mains power is supplied to the panel - a red LED
will illuminate located on the front cover.
2. OUTPUT 1 RELAY This relay output switches when any external gas detectors reach ‘pre-alarm’
status and the [0-10V OUTPUT] will send 5V to ventilation systems.
OUTPUT 2 RELAY This relay output switches when any external gas detectors reach ‘alarm delay’
status and the [0-10V OUTPUT] will send 10V to ventilation systems.
ALARM RELAY This relay output switches when any external gas detectors reach ‘alarm delay’
status for longer than the selectable 1-5 minutes time following the [OUTPUT 2] relay.
DAMPER RELAY This relay output can switch together with either OUTPUT 1, OUTPUT 2 or ALARM
relays - selectable in the settings menu.
3. DETECTOR CHAIN 12-24Vdc power and Modbus communication data is wired to Parksafe gas
detectors [DETECTOR CHAIN] - [+ / - / D+ / D-].
Up to 16 detectors can be connected, chained in parallel up to approx. 500 yards from the
panel depending on chain configuration, wire type for power and condition.
Connect detectors in a parallel (daisy chain) method. Any other way may cause
communication issues or damage to the overall system.
For MODBUS communications, a shielded and twisted pair cable is used. The shielding can be
of 2 types: braided [mesh of thin conducting wires] or foil (consisting of a thin sheet of metal
covering the twisted wires).
If you are encountering noise or irregular problems with a Modbus link, the problem is likely
related to grounding, incorrect shielding or wiring mains power next to Modbus wiring.
For more information refer to your Parksafe detector manual.
4. SOUNDER/ STROBE This relay output (24VDC) is for an external sounder alarms/ strobe lighting to
activate on alarm.
5. 24VDC This is a permanent 24Vdc power output for external auxiliary devices.
Max output: 200mA.
6. 0-10V OUTPUT This output can drive ventilation systems. Under normal operating conditions, this
output can send either 0 or 2V –selectable in the settings menu. The [0-10V OUTPUT] will send 5V
when [OUTPUT 1] relay is activated and 10V when [OUTPUT 2] relay is activated.

Installation & Operation Manual Parksafe
AGS Parksafe Panel - IOM Iss: 6 10-20 7
Wiring your Detector
Power and Modbus data are wired between detectors with the first
connected to a control panel DETECTOR CHAIN terminal.
For MODBUS communications, a shielded cable is used.
The shielding can be of 2 types: braided [mesh of thin
conducting wires] or foil (consisting of a thin sheet of metal
covering the twisted wires).
One example of such cable is BELDEN 3082A.
If you are encountering noise or irregular problems with a Modbus link, the problem is likely related
to grounding, incorrect shielding or wiring mains power next to Modbus wiring.
To ground the data cable, the shield should be connected to [-] of the chain terminals.
Reversing the [D+] and [D-] connections of any device can lead to the whole system to stop
working owing to reverse polarity found on the terminals.
Not appropriately grounding the device can give false readings, fail completely or turn into a
safety hazard!
Detector Chain ID Switches
When wiring multiple detectors in a chain it is important to identify each and
every detector installed for the control panel to receive and display accurate
data corresponding with the correct detector type.
The ID configuration diagram is printed onto detector boards for
quick reference. All detectors are factory set to ID1.
ID Switches must be configured for each and every detector connected to a
system to receive and display accurate data!
We recommend a plan, map and/or marking the detector enclosures detailing ID and location!

Installation & Operation Manual Parksafe
AGS Parksafe Panel - IOM Iss: 6 10-20 8
Creating a Detector Chain
Up to 16 Parksafe Detectors can be connected, chained in a parallel ‘daisy chain’ method up to
approx. 500 yards from the panel depending on chain configuration, wire type for power and
condition. Any other way may cause issues or damage to the overall system.
Remember to individually ID each connected detector by configuring the ID switches on the circuit
boards. Make a plan and/or map of the location of all detectors for tracing and locality purposes.
It is recommended that the cable of same color should be used to connect all [D+] terminals
together and similarly cable of same color to be used to connect all [D-] terminals together.
**Split chain example. **Single chain example
**Where connections may exceed 500 yards from one control panel –contact your supplier!
Remember to ID your detector!
120 ohm Termination Resistance
Signal communication issues may occur where the bus length is too long, high baud rates are used
or signal reflections are occurring. To avoid this, terminating at each end of a chain may help the
quality of the data signal by turning on the 120ohm terminal resistor switch.
Split chain Single chain
For more information refer to your Parksafe detector manual.
Access Configuration Settings
On the front display circuit board you’ll find a SETTINGS switch –when switched on, the screen will
display the settings menu –you can now configure your Parksafe system.
When changes have been made –turn the settings switch off and the panel will restart!

Installation & Operation Manual Parksafe
AGS Parksafe Panel - IOM Iss: 6 10-20 9
Settings Menu
The Parksafe panel has a touch screen which allows the engineer/user to configure the system.
Adjust the screen brightness. Change/select option.
(Press or slide the cursor up and down) (Press the blue option box or press and hold)
Menu Options Explained
FUNCTION
OPTION
Explanation
Auto Start
- ON
- OFF
In the event of a power loss - the Parksafe panel will
automatically restart when power is restored, or not.
0-10V Minimum Value
- 0 or 2V
0-10V terminal output under normal / safe conditions.
Alarm Time Delay
- 1 to 5
Time (minutes) for alarm relay to switch when detectors
reach alarm status. (Following second relay: Output 2).
Damper Follows
- Output 1
- Output 2
- Alarm
The Damper relay output can switch together with
either [OUTPUT 1], [OUTPUT 2] or the [ALARM] relays.
Temperature Alarm >
- 68 to 86°
- Off
All Relays will activate when the defined temperature
(F°) is exceeded. Select Off to disable function.
Factory Set Condition
Auto Start
- ON
Panel will restart following a power cut/loss.
0-10V Minimum Value
- 0V
No voltage output under normal condition status.
Alarm Time Delay
- 1
Following Output 2 relay switching, the Alarm relay will
activate after one (1) minute.
Damper Follows
- Output 1
Damper relay switches with [Output 1] relay.
Temperature Alarm >
- Off
Temperature alarm disabled.

Installation & Operation Manual Parksafe
AGS Parksafe Panel - IOM Iss: 6 10-20 10
Quick Tips
CONNECTION
The best way to connect devices in a MODBUS RTU is a ‘DAISY CHAIN’method.
MAXIMUM DISTANCE
You may encounter problems when powering gas sensors beyond 500 yards from one control
panel, in this instance, contact your supplier.
TERMINAL RESISTANCE
Signal communication issues may occur. To avoid this, terminating at each end of a chain may
help the quality of the data signal by turning on the 120ohm terminal resistor switches.
GROUNDING
If you are encountering noise or irregular or abnormal problems with a Modbus link, the problem is
likely related to grounding, incorrect shielding or wiring main power next to Modbus wiring.
CABLES TO USE
A shielded and twisted pair cable is used. The shielding can be of 2 types: braided [like a mesh of
thin conducting wires] or like a foil [consisting of a thin sheet of metal covering the twisted wires].
PROTECTION
High concentrations of alcohol found in many products may damage, deteriorate or affect the gas
sensing elements of Detectors –such as; wine; deodorants; stain removers; thinners etc.
IDENTIFICATION
Remember to individually ID each connected detector by configuring the ID switches on the circuit
board. Make a plan, map and/or note of the location of all connected detectors for tracing and
locality purposes.
Specification
Product
AGS Parksafe Ventilation Control Panel
Display
4.3” Touch Screen TFT
Power Input Voltage
100-120V AC
Current Consumption Approx.
48W max (fully loaded)
Internal Fuse
3.15A
Operating Temperature / RH Approx.
14 –122°F / 30-85% RH non-condensing
Audible Alarm Buzzer dB
65 dB (300mm distance in quiet conditions)
Maximum Gas Detectors
16 max
Gas Detector Wiring Length Approx.
± 500 Yards
Wire ratings:
18AWG min
Housing Material
Polylac PA-765
Flame Rating
UL 94
Approvals
CE, RoHS
O/All Dimensions (H x W x D) mm / inch
7.08 x 10 x 3.03”

Installation & Operation Manual Parksafe
AGS Parksafe Panel - IOM Iss: 6 10-20 11
OPERATION
First Power Up
Upon connecting mains power, the Parksafe control panel will load for approximately 60 seconds.
During this time the screen will display an ‘initialising’ screen. The panel will then begin establishing
signals with any Parksafe gas detectors.
Home Screen Status & Condition Overview
System OK.
Under normal/safe conditions.
System in ‘Pre-Alarm’ condition.
When detected gas reach pre-alarm levels.
OUTPUT 1 relay: activated.
0-10V output: 5V
Other relays and external devices may activate if configured to do so.
System in ‘Alarm Delay’ condition.
When detected gas reach dangerous alarm levels.
OUTPUT 2 relay: activated.
0-10V Output: 10V
Other relays and external devices may activate if configured to do so.
System in Alarm condition.
When gas levels remain dangerous beyond the alarm delay.
ALARM relay: activated.
Gas detector ID appears on screen.
The internal buzzer will sound to alert the user.
The detector ID of the first signal received will be displayed on screen only.
Temperature Status & Icon
This feature is factory set to off.
If enabled and the temperature levels detected exceed a
selectable threshold, the temperature icon appears and the
system enters an alarm state.
All relays/outputs will activate until the temperature (detected by
Parksafe Detectors) drops below the specified threshold –
adjustable in the configuration settings menu.

Installation & Operation Manual Parksafe
AGS Parksafe Panel - IOM Iss: 6 10-20 12
Silence & Reset
To silence the internal buzzer –press the Silence button on the front panel.
This will also silence any external audio sounders connected to the panel.
If the system reaches alarm condition –the panel will need to be reset when the gas
levels detected return to a safe level.
Check the detector status pages to identify where gas has been detected and if levels
have returned to a safe condition before resetting the system.
Accessing Detector Status Information
To access detector status information screens –
Press the ‘Gas Detection’section on screen any time.
Switch between pages by touching the relevant page button.
Each page can display up to 4 detectors as follows:
a. ID: The ID configured via switches on each detector board.
b. Serial Number: The unique serial number for that detector.
c. Gas: The target gas that the detector is monitoring.
d. Status: The status of gas levels, errors and messages.
e. Value: The concentration value of gas detected.
To return to the main screen, press the home button on screen.
Detector Status
GOOD
oGas levels are safe / No error conditions.
PRE ALARM
oGas detected has reached pre-alarm levels.
ALARM
oGas detected has reached alarm levels.
FAULT
oGas sensor module issue. Contact your supplier.
END OF LIFE
oThe gas sensing element has reached the end of its expected lifecycle.
SERVICE
oGas sensing element requires periodic bump test/service.
-- X --
oDetector signal lost, not installed or not configured correctly.
Gas Alarm Levels
GAS
GOOD
PRE-ALARM
ALARM
Carbon Monoxide (CO)
> 25 ppm
25 -100 ppm
> 100 ppm
Nitrogen Dioxide (NO2)
< 0.7 ppm
0.7 - 2 ppm
> 2 ppm

Installation & Operation Manual Parksafe
AGS Parksafe Panel - IOM Iss: 6 10-20 13
General Maintenance
Keep your Parksafe system in good working order follow these basic principles;
Remove any dust/debris from the outer enclosure regularly using a slightly damp cloth.
Never use detergents or solvents to clean your gas detection devices.
Never spray air fresheners, hair spray, paint or other aerosols near devices.
Never paint devices. Paint will seal vents and interfere with the device.
It is recommended that detectors are inspected and serviced at least annually from the date of
installation for optimum performance and protection due to sensitivity drifts!
High concentrations of alcohol found in many products may damage, deteriorate or affect the gas
sensor such as; wine; deodorants; stain removers; thinners etc. Other gases and substances to
avoid are; Corrosives (i.e. chlorine & hydrogen chloride); Alkali metals; Basic or acidic compounds;
Silicones; Tetraethyl lead; Halogens and halogenated compounds!
EOL or Service Indication
This message will appear on the home screen and indicates that a gas sensor module has reached
either its expected operational lifecycle (EOL) or that the detector(s) require its periodic service
check. Press the ‘GAS DETECTION’button on screen to identify the affected detector(s) and status.
No gas levels will be displayed for that detector during this time.
The expected operational life of a gas sensor module will depend on the type of gas your detector
is targeting and may vary depending on environmental conditions.
When a gas detector displays the ‘End of Life’ message contact your supplier immediately.
It is important to maintain the gas sensing elements of gas detectors for optimum performance,
protection and security of the system. When the detector displays the ‘SERVICE’ message contact
your supplier immediately. Parksafe gas detectors will still operate but its sensitivity can be inhibited
by external factors such as, dust; humidity; temperature fluctuations; cleaning products;
contaminants or sensor drift (ageing). All can cause a decline in sensitivity and eventual failure. It is
recommended that detectors are inspected and serviced at least annually from the date of
installation for optimum performance and protection.
Contact your supplier for more information.

Installation & Operation Manual Parksafe
AGS Parksafe Panel - IOM Iss: 6 10-20 14
Bump Testing
What is Bump Testing?
Bump testing is a term used for checking a gas detector is functioning correctly by exposing it to
the target gas. A known concentration of the target gas is applied to the device to trigger an
alarm condition and ascertain the detector is working safely.
Why is it Important?
A detector may visually appear in good order, but its sensitivity can be inhibited by external factors
such as, dust; humidity; temperature fluctuations; cleaning products; contaminants or sensor drift
(ageing). All can cause a decline in sensitivity and eventual failure.
The aim of the bump test is to make sure a gas detector is working at its optimum by briefly
exposing the unit to a known concentration of the target gas. The reading (if displayed) is
compared to the actual content of gas present, as stated on the test gas cylinder and if the
detector goes into alarm within an acceptable range of the actual concentration, usually within
10%, then it is working safely.
If the bump test results are not within the acceptable range, the gas detector must not be used
until a full calibration has been conducted.
Bump testing has a number of benefits for the end user:
Peace of mind that the system does actually detect the gas in question.
Allows the site to practice safe operations in a similar manner to the fire system.
Early indication of any issues.
How Often?
Regular bump tests are important to make sure the detector is able to detect a release of gas as
early as possible. A bump test usually takes seconds (gas type dependant) and is often completed
alongside a scheduled fire alarm test, however the frequency should be determined following a risk
assessment by the end user.
Current standards recommend that for new installations - it may be prudent to carry out a bump
test frequently, following a successful initial period and as confidence grows in the installation
concerned, the frequency could be reduced.
Remember, bump testing does not remove the need to have gas detectors inspected, calibrated
and serviced periodically by a trained engineer. You should not attempt this yourself and should
employ the services of a specialist company.
For more information on this, contact us.

Installation & Operation Manual Parksafe
AGS Parksafe Panel - IOM Iss: 6 10-20 15
Service Record
Date
Device ID
Gas
Pass
Sign

Installation & Operation Manual Parksafe
AGS Parksafe Panel - IOM Iss: 6 10-20 16
INSTALLATION DETAILS
Please pass this manual to the system owner/user.
Date of Installation:
Installation Location:
Organisation:
Stamp/ Signature of the installer:
American Gas Safety LLC
Head office:
4500 140th Ave North
Suite 101
Clearwater
FL 33762
Tel: (727) 608-4375
Fax: (727) 538-4237
info@americangassafety.com
American Gas Safety LLC is the owner of this document and reserves all rights of modification without prior notice.
Other manuals for Parksafe Control Panel
3
Table of contents
Other AGS Control Panel manuals
Popular Control Panel manuals by other brands

Elmes Electronic
Elmes Electronic CB32 Installation and operation manual

ESAB
ESAB A2 PEK instruction manual

Artforma
Artforma LCD panel user manual

RSI VIDEO TECHNOLOGIES
RSI VIDEO TECHNOLOGIES XT610 COMPLETE SETUP AND PROGRAMMING MANUAL

Pego
Pego ECP202 EXPERT Use and maintenance manual

Macurco
Macurco DVP-120B User instructions