AGS Merlin 2000S User manual

Merlin 2000SUser Guide
Rev: 06 05-19 1
Gas Safety Products
Merlin 2000S
Gas Proving & Interlock system
User Guide
Please read this guide carefully and retain for future use.

Merlin 2000SUser Guide
Rev: 06 05-19 2
Table of contents
1General Information............................................................................................3
1.1 Panel Mounting...............................................................................................................3
2Circuit Board Terminals.......................................................................................4
2.1 LINE VOLTAGE..................................................................................................................4
2.2 VALVE OUT .......................................................................................................................4
2.3 SUPPLY FAN & EXTRACT FAN PD SWITCHES...................................................................4
2.4 BMS OUT ...........................................................................................................................4
2.5 PRESSURE SENSOR ...........................................................................................................4
2.6 EM REMOTE ......................................................................................................................5
2.7 GAS DETECTOR................................................................................................................5
2.8 FS 1/2/3/4 .........................................................................................................................5
2.9 CO2 Monitor ....................................................................................................................5
2.10 12V DC .............................................................................................................................5
3Installation & Operation ......................................................................................6
3.1 System ON and OFF........................................................................................................6
3.2 Emergency Shut Off........................................................................................................6
3.3 BMS integration ...............................................................................................................6
3.4 Fan Switch Integration....................................................................................................6
3.5 Gas Fill and Prove Time ..................................................................................................7
3.6 Fire alarm integration .....................................................................................................7
3.7 CO2Mode (Select Models Only) ..................................................................................7
4Panel LED status...................................................................................................8
52000S Wiring Spec ............................................................................................10
6Manufacturer’s Warranty ..................................................................................12

Merlin 2000SUser Guide
Rev: 06 05-19 3
1General Information
The Merlin 2000S is a gas proving and ventilation interlock panel.
The system comprises of a control panel and a gas pressure sensor. The Merlin 2000S can receive
connections from remote air pressure differential switches or external current monitors, remote
emergency shut-off buttons, gas detectors and a CO2 monitor. It can also be integrated with a
BMS and fire alarm.
It is recommended that the user reads this guide before using the system. Please do NOT
attempt to operate the unit until the contents of this document have been read and are
thoroughly understood.
1.1 Panel Mounting.
The control panel is designed for surface mounting using 4 mounting screws. Removing the cover
on the panel gives access to the circuit board.
The PCB should be removed before drilling entry holes into the case. A flush mount kit is
available, comprising of a mounting bracket and decorative surround strip. Contact your
supplier for more information.
Important Warning Statements
Never ignore your device when in alarm.
This device requires a continual supply of electrical power –it will not work without power.
This device should not be used to substitute proper installation, use and/or maintenance of fuel burning
appliances including appropriate ventilation and exhaust systems.
Your product should reach you in perfect condition, if you suspect it is damaged, contact your supplier.
Information on waste disposal for consumers of electrical & electronic equipment. (EEE)
When this product has reached the end of its life it must be treated as Waste Electrical & Electronics Equipment
(WEEE). Any WEEE marked products must not be mixed with general household waste, but kept separate for the
treatment, recovery and recycling of the materials used.
Please contact your supplier or local authority for details of recycling schemes in your area.

Merlin 2000SUser Guide
Rev: 06 05-19 4
2Circuit Board Terminals
2.1 LINE VOLTAGE
A 110-120VAC electrical supply should be externally fused at
3A and connected to the terminals marked [LINE VOLTAGE
LNE].
2.2 VALVE OUT
The 110-120VAC gas solenoid valve should be powered using
the terminals on the Merlin 1000S detailed [VALVE OUT LNE].
2.3 SUPPLY FAN & EXTRACT FAN PD SWITCHES
These terminals are used to receive an input signal from external air pressure switches or external
current monitors. These are linked out as a factory setting as shown.
Wiring to switches & current monitors should be made using
two-core volt free connections.
If only one fan is being used the terminals not in use should be
left linked out.
2.4 BMS OUT
Terminal connections are available on the circuit board for connections to
Building Management systems.
This is a relay that changes state in alarm or when gas is on/off and can be
used in conjunction with the [12VDC] output and other external relays that
affect other devices and controls such as purge fans, audible alarms etc.
Detailed on the circuit board as [BMS OUT] normally closed (N/C),
common (COM) and normally open (N/O). These are volt free
connections.
2.5 PRESSURE SENSOR
The terminals marked pressure sensor [+ - IN].
These wire to the gas pressure sensor which is
screwed into the downstream port on the gas
solenoid valve.
Min Operating Pressure = 0.17psi
Max Operating Pressure = 1.45psi
ENSURE THIS IS SCREWED TO THE DOWNSTREAM PORT OF THE GAS SOLENOID VALVE

Merlin 2000SUser Guide
Rev: 06 05-19 5
2.6 EM REMOTE
The terminal for remote emergency shut-off buttons is detailed on the circuit
board as [EM REMOTE].
These connections are linked out as a factory setting.
Remote emergency shut-off buttons should be volt free and wired to the Merlin
2000S using a plenum security cable, white, 18/2 (18AWG 2 conductor),
stranded, CMP or similar.
2.7 GAS DETECTOR
These connections can be wired to a Merlin gas detector (LPG,
natural gas or carbon monoxide) as shown.
If no detector is being used leave the link in between the “ ”.
Refer to your detector guide for more information.
2.8 FS 1/2/3/4
This terminal switches when the key is turned on and off.
This can be linked to a fan switch (panel supplied separately) which can
provide power to the fans when the control panel is switched on.
2.9 CO2 Monitor
This terminal can be wired to CO2 monitor to shut off the system in the
event of CO2 being at alarm level.
If no CO2 monitor is connected, the panel will ‘beep’ and CO2 LED will
flash 3 times to indicate this terminal has been disabled.
2.10 12V DC
This is a permanent 12v DC output when there is power at the panel and can
be used to create a relay switch with the BMS relay output.
This is normally used to power a PM2 current monitor. (Supplied separately)
Contact your supplier for more information.

Merlin 2000SUser Guide
Rev: 06 05-19 6
3Installation & Operation
3.1 System ON and OFF
Turn off all appliances
Turn the Fans On.
Turn the key switch to ON position.
To turn the system off, turn the key switch to OFF position.
3.2 Emergency Shut Off
The emergency shut off button is located on the front of the panel.
There is also a facility for remote shut off buttons to be wired in series on the circuit board.
The emergency shut off button(s) will cut off the gas supply when activated.
To reinstate the system, the emergency shut off button(s) will need to be reset and the panel
restarted.
3.3 BMS integration
The Merlin 2000S can be integrated with a BMS to make or break a circuit on
gas on/gas off, (valve open or valve closed). This will tell the BMS whether or not
110-120VAC is being sent to the solenoid.
There is a dip-switch located on the inside facia of the Merlin 2000S labelled
[BMS SEL].
This is factory set in the OFF position which signals the BMS on gas on/gas off.
When switched to the ON position, the 2000S will only signal the BMS on a fault,
i.e. fan fault, CO2 high level detected, gas detected, EM Stop pressed, etc.
3.4 Fan Switch Integration
There is the facility to connect a Fan Switch (FS1 or FS2 sold separately).
The Fan Switch provides the facility to turn on the fan(s) when the key switch on the Merlin 2000S
is in the on position and turn the power off to the fan(s) when the key switch on the Merlin 2000S
is in the off position.
There is a dip-switch located on the circuit board labelled [EM SEL].
This is factory set in the OFF position which instructs the system to shut down
the fan(s) and gas supply on activation of the Emergency shut off button(s).

Merlin 2000SUser Guide
Rev: 06 05-19 7
3.5 Gas Fill and Prove Time
Gas fill and prove times are adjustable. There are two dip-switches located on the inside facia of
the Merlin 2000S labelled “Fill Time” and “Prove Time”. They are factory set in the ‘off’ position.
Fill and prove time can be changed by turning the relevant dip switch to on position.
FILL TIME is the amount of time the gas valve is open to fill the gas line.
Off –5 seconds
On –10 seconds
PROVE TIME is the amount of time the system tests the gas line for any leaks.
Off –30 seconds
On –50 seconds
Once the settings has been changed please remove power from the fuse spur for 10 seconds.
On installation, this can be switched to the ON position if required. This will instruct the system
to leave the fans on and only shut off the gas supply on activation of the Emergency shut off
button(s).
Note: This option is not available if Fan Switch is not installed.
3.6 Fire alarm integration
The Merlin 2000S can be integrated with a fire alarm to close the gas supply automatically in the
event of a fire.
The volt free fire alarm signal can be wired in series with any remote emergency shut off buttons.
3.7 CO2Mode (Select Models Only)
Under normal working conditions the Merlin 2000S monitors the ventilation and the concentration
level of CO2. In the event of ventilation failure or if the CO2level is at alarm level, the panel will
shut off the gas supply.
The Merlin 2000S features a ‘CO2Mode’ this allows the kitchen to have the access to the gas
supply in the event of a fan failure. There is a ‘CO2Mode’ button located on the front of the
panel. This button will only be available to use when ‘Fan fault’ LED illuminates Red. To enable
the CO2Mode, the ‘CO2button’ has to be pressed for 5 seconds. The Fan Fault LED will go off
and CO2Mode LED will come on. In this mode, the Merlin 2000S will monitor only the CO2levels
to ensure there is a safe working environment. This mode will allow the gas valve to open for 8
hours each time the system is energised, provided there are satisfactory levels of CO2.
At the end of 8 hours, the gas valve will close and CO2 Mode LED will be flashing.
To reinstate the system the panel has to be restarted. The ‘CO2 Mode’ will be permanently
disabled if a CO2 Sensor is not detected at power up.

Merlin 2000SUser Guide
Rev: 06 05-19 8
4Panel LED Status
When the system is connected to the mains supply, the Red LED of the AGS Logo located in the
bottom right corner of the panel will illuminate.
When no power is present, this LED will not light up.
Gas On
When the fans are running at the correct speed and the key switch is turned on, the Merlin 2000S
will open the gas valve and the green ‘Gas On’ LED will illuminate.
ON = Gas On
OFF = Gas Off
Testing
This LED will illuminate GREEN for approximately 30 seconds when the panel is checking the
integrity of the gas installation upon start up.
GREEN = proving the gas line, do NOT operate any appliances during the testing period.
Test Fail
Under normal working conditions this LED is off. When the panel detects a gas leak on start-
up, the LED will illuminate AMBER. Gas valve will remain closed.
OFF = OK
ON = gas proving test failed
Pressure Low
Under normal working conditions the LED is off. The LED will illuminate AMBER when the incoming
gas pressure drops below 0.17psi for 10 seconds. The gas valve will close.
OFF = OK
ON = gas supply pressure low.

Merlin 2000SUser Guide
Rev: 06 05-19 9
Supply Fans
Under normal working the LED will illuminate GREEN. If a supply fan fault is detected, the LED will
be flashing.
ON = OK
FLASHING = One of the supply fans is not running.
Extract Fans
Under normal working the LED will illuminate GREEN. If an extract fan fault is detected, the LED
will be flashing.
ON = OK
FLASHING = One of the extract fans is not running
IF SUPPLY AND/OR EXTRACT FANS LED FLASHES FOR MORE THAN 20 SECONDS, THE GAS WILL SHUT OFF.
Fan Fault
Under normal working conditions this LED is off. If a fan fault is present for more than 20 seconds,
the LED will illuminate RED.
OFF = OK
ON = the gas supply has been shut off due to a ventilation fault.
IF A FAULT IS FOUND YOU WILL NEED TO CONTACT YOUR SERVICE/MAINTENANCE COMPANY.
YOU SHOULD NOT ATTEMPT TO CARRY OUT A REPAIR UNLESS YOU ARE QUALIFIED TO DO SO.
EM Stop
If an emergency shut off button (either remote or on the panel) is pressed, the LED will illuminate
AMBER and the gas turned off. The EM Stop button must be re-set before restarting the system.
OFF = OK
ON = EM Stop button pressed
Gas Detected
Under normal working conditions this LED is off. If the external Merlin detector connected detects
gas this will show RED and the Gas valve will turn off.
OFF = OK
ON = Gas detected.
CO2High
Under normal working conditions this LED is off. If the concentration of CO2 in the air is at
alarm level (relevant detector required), the LED will show RED and the Gas valve will turn off.
OFF = OK
ON = the concentration of CO2 is at alarm level.

Merlin 2000SUser Guide
Rev: 06 05-19 10
52000S Wiring Spec
1. LINE VOLTAGE: Mains Input 110-120VAC. Single phase
2. VALVE OUT: Gas Solenoid Valve Power Output, 110-120VAC. Max 3A
3. SUPPLY FAN 1 and 2 external pressure differential switch or current switch. VOLT FREE INPUT
4. EXTRACT FAN 1 and 2 external pressure differential switch or current switch. VOLT FREE INPUT
5. BMS OUT contacts. Normally Closed, Common and Normally Open.
6. PRESSURE SENSOR: Gas pressure transducer, power supply and returned signal (supplied).
7. EM REMOTE: Remote EM Stop buttons and Fire Alarm input wired in series (purchased separately).
VOLT FREE INPUT
8. GAS DETECTOR: power supply and VOLT FREE INPUT (purchased separately).
9. FS1/2/3/4: Fan Switch output (purchased separately).
For wiring instruction see Fan Switch user manual.
10. CO2 MONITOR: (purchased separately). VOLT FREE INPUT
11. 12VDC: Permanent 12VDC output (Normally used to power a PM2 Current Monitor). 50A Max.

Merlin 2000SUser Guide
Rev: 06 05-19 11

Merlin 2000SUser Guide
Rev: 06 05-19 12
6Manufacturer’s Warranty
3 Year Limited Warranty
Warranty coverage: The manufacturer warrants to the original consumer purchaser, that this product will be free of
defects in material and workmanship for a period of three (3) years from date of purchase. The manufacturer’s liability
hereunder is limited to replacement of the product with repaired product at the discretion of the manufacture. This
warranty is void if the product has been damaged by accident, unreasonable use, neglect, tampering or other causes
not arising from defects in material or workmanship. This warranty extends to the original consumer purchaser of the
product only.
Warranty disclaimers: Any implied warranties arising out of this sale, including but not limited to the implied warranties of
description, merchantability and intended operational purpose, are limited in duration to the above warranty period. In
no event shall the manufacturer be liable for loss of use of this product or for any indirect, special, incidental or
consequential damages, or costs, or expenses incurred by the consumer or any other user of this product, whether due to
a breach of contract, negligence, strict liability in tort or otherwise. The manufacturer shall have no liability for any personal
injury, property damage or any special, incidental, contingent or consequential damage of any kind resulting from gas
leakage, fire or explosion. This warranty does not affect your statutory rights.
Warranty Performance: During the above warranty period, your product will be replaced with a comparable product if
the defective product is returned together with proof of purchase date. The replacement product will be in warranty for
the remainder of the original warranty period or for six months –whichever is the greatest.
CONTACT US:
AGS Head Office
Tel: (727) 608-4375
Fax: (727) 538-4237
info@americangassafety.com
American Gas Safety is the owner of this document and reserves all rights of modification without prior notice.
Other manuals for Merlin 2000S
1
Table of contents
Other AGS Security Sensor manuals
Popular Security Sensor manuals by other brands

Leuze electronic
Leuze electronic RSL 430 Original operating instructions

Takex
Takex PR-5B instruction manual

Bircher Reglomat
Bircher Reglomat ProLoop operating instructions

Optex
Optex sensor manual

System Sensor
System Sensor B110LPA Installation and maintenance instructions

Macurco
Macurco GD-6 User instructions