
TM5-250_B
7
LP0859X 10/10
WIRING THE METER
WIRING OVERVIEW
Electrical connections are made via screw-clamp terminals located on the back of the meter. All
conductors should conform to the meter's voltage and current ratings. All cabling should conform to
appropriate standards of good installation, local codes and regulations. It is recommended that the power
supplied to the meter (DC or AC) be protected b a fuse or circuit breaker.
When wiring the meter, compare the numbers embossed on the back of the meter case against those
shown in wiring drawings for proper wire position. Strip the wire, leaving approximatel 0.3” (7.5 mm)
bare lead exposed (stranded wires should be tinned with solder.) Insert the lead under the correct screw-
clamp terminal and tighten until the wire is secure. (Pull wire to verif tightness.)
EMC INSTALLATION GUIDELINES
Although this meter is designed with a high degree of immunit to ElectroMagnetic Interference (EMI),
proper installation and wiring methods must be followed to ensure compatibilit in each application. The
meter should be mounted in a metal enclosure, which is properl connected to protective earth. The t pe
of the electrical noise, source or coupling method into the meter ma be different for various installations.
The meter becomes more immune to EMI with fewer I/O connections. Cable length, routing, and shield
termination are ver important and can mean the difference between a successful or troublesome
installation. Listed below are some EMC guidelines for successful installation in an industrial environment:
1. The meter should be mounted in a metal enclosure, which is properl connected to protective earth.
2. Use shielded (screened) cables for all Signal and Control inputs. The shield (screen) pigtail connection
should be made as short as possible. The connection point for the shield depends somewhat upon the
application. Listed below are the recommended methods of connecting the shield, in order of their
effectiveness.
a. Connect the shield onl at the panel where the unit is mounted to earth ground (protective earth).
b. Connect the shield to earth ground at both ends of the cable, usuall when the noise source
frequenc is above 1 MHz.
c. Connect the shield to common of the meter and leave the other end of the shield unconnected and
insulated from earth ground.
3. Never run Signal or Control cables in the same conduit or racewa with AC power lines, conductors
feeding motors, solenoids, SCR controls, and heaters, etc. The cables should be run in metal conduit
that is properl grounded. This is especiall useful in applications where cable runs are long and
portable two-wa radios are used in close proximit or if the installation is near a commercial radio
transmitter.
4. Signal or Control cables within an enclosure should be routed as far as possible from contactors,
control rela s, transformers, and other nois components.
5. In extremel high EMI environments, the use of external EMI suppression devices, such as ferrite
suppression cores, is effective. Install them on Signal and Control cables as close to the unit as
possible. Loop the cable through the core several times or use multiple cores on each cable for
additional protection. Install line filters on the power input cable to the unit to suppress power line
interference. Install them near the power entr point of the enclosure. The following EMI suppression
devices (or equivalent) are recommended:
Ferrite Suppression Cores for signal and control cables:
Fair-Rite # 0443167251
TDK # ZCAT3035-1330A
Steward # 28B2029-OAO
Line Filters for input power cables:
Schaffner # FN610-1/07
Schaffner # FN670-1.8/07
Corcom # 1 VR3
Note: Reference manufacturer’s instructions when installing a line filter.
6. Long cable runs are more susceptible to EMI pickup than short cable runs. Therefore, keep cable runs
as short as possible.
7. Switching of inductive loads produces high EMI. Use of snubbers across inductive loads suppresses EMI.