Air Control TERMOSPLIT 35.14 KONDENS Manual

G20 ENGINEERING SRLLoc. Campogrande 13, 29013 CARPANETO PIACENTINO (PC), Italy
tel. + 39 0523 850513 - fax. +39 0523 850712 - www.aircontrol-pc.com - www.g20engineering.com
G20 ENGINEERING Brand
ITALIAN DESIGN
MADE IN ITALY
INSTALLATION, FIRST IGNITION, USE AND MAINTENANCE MANUAL
TermoSplit 35-70.14
KONDENS
09.2015 rev.3

APPLICATION FIELD OF “TERMOSPLIT”
TERMOSPLIT, the hot air generator device, can be used for heating large
environments where re risk activities are carried out or with relevant ow of
people.
The different models of TERMOSPLIT are composed of an external unit and an
internal unit that can be connected by a supplied kit.
The external unit provides the heat the internal unit will convey within the room
in total safety.
TERMOSPLIT doesn't need the Fire Department authorization even in case of
systems exceeding 100,000 kcal/h.

1
CONTENTS
General requirements 1
-Product presentation 1
-Statement of the manufacturer 1
-Danger symbols 1
-Disposal of packaging and waste uid 1
-General instructions 2
-Law and safety rules 2
-Law and reference standards 2
-Technical data 3
-Connection pipes diameter 3
-Dimensions and weights 3
-Hydraulic drawing 4
-Electric diagram 4
Installation 5
-Appliance positioning 5
-Installing the external unit 6
-Connecting the condensate line 6
-Flue ducts selection 7
-Exhaust fumes and air intake system
installation 7
-Installing the internal unit 8
-Connection of the two units 8
-Connection to the methane gas
network 9
-Connection to the LPG tank 9
-Carrier uid lling 9
-Carrier uid lling/topping up by self
relling kit 10
-TermoSplit 70.14 Kondens I.S.P.E.S.L.
Safeties 10
-Connection to the electrical system 11
-Single control connection 12
-One control connection 12
-Room sensor connection 12
-Connection 12
-Important notes 12
First start-up 13
-General inspection 13
-Review - Combustion check and
tuning 13
-Supply gas change 14
Use and operation 15
-Warning for the tenant 15
-Operational characteristics 15
-Remote control 15
-First start-up 15
-Password request 16
-Schematic layout 17
-Operation modes 17
-Manual mode set-up 18
-Set-up menu 18
-Clock (Time) 18
-Weekly time scheduling 18
-Info menu 20
-Technical menu 21
-Ventilation 21
-Malfunctioning and block 21
-Error codes 22
Maintenance 23
-Appliance check 23
-Warnings for maintenance technician 23
-Maintenance schedule 23
-Preventive checks 23
STATEMENT OF THE MANUFACTURER
The Air Control devices are EC certied (DM April 2nd 1998 Implementing regulation art. 32 Law 10/91) and
comply with the following Directives and subsequent amendments: Gas Directive 90/396; Electromagnetic
Compatibility Directive 89/336/EEC; Efciency Directive 92/42/EEC; Low Voltage Directive 73/23/EEC; satisfy
the minimum energy performance requirements at rated load.
PRODUCT PRESENTATION
TERMOSPLIT KONDENS .14 is a splitting hot air generator condensing device. Due to these characteristics,
it is suitable to industrial and commercial premises and workshops of different sizes and in particular to
heat spaces where re risk activities are carried out (joiner's workshops, printing works, workshops, weaving
factories, etc.).
DANGER SYMBOLS
DANGER: All warnings preceded by this symbol MUST be carefully observed to avoid any mechanical
or general injuries (e.g. wounds or contusions).
DANGER: All warnings preceded by this symbol MUST be carefully observed to avoid risk of personal
injuries due to electrical shock.
DANGER: All warnings preceded by this symbol MUST be carefully observed to avoid risk of heat-
related personal injuries.
Caution: All warnings preceded by this symbol MUST be carefully observed to avoid malfunctions
and/or damages to the appliance or other components.
PACKAGING AND WASTE FLUID DISPOSAL
The TERMOSPLIT KONDENS .14 packaging is made of recyclable material and must be disposed through
waste management companies.
The heat-carrying uid (mono ethylene glycol), at the end of its life-cycle, must be disposed through a
special waste disposal company.
GENERAL REQUIREMENTS

2
GENERAL WARNINGS
The instruction manual is an integral and essential part of the product and is supplied with every TERMOSPLIT Air Control.
Read carefully all the Warnings in the Manual as they provide important information on safe installation, operation
and maintenance.
Keep this manual for future reference.
- Installation must be carried out according to National and Local rules and laws by qualied personnel and following the
manufacturer's instructions.
- Qualied personnel refers to skilled technicians with specic expertise for the installation of heating systems for domestic use
and hot water production, as per Law No 46/90 of March 3rd 1990.
- The tasks the user can undertake are described ONLY in the chapter "USER INSTRUCTIONS".
The manufacturer does not accept any contractual or extra contractual liability for damage caused by wrong installation and
use and failure to comply with local and national applicable rules and the instructions provided.
- Always ensure the TERMOSPLIT packaging material (cardboard, nails, plastic bags, etc.) is out of reach of children as it is
potential source of danger.
- Before carrying out any cleaning or maintenance activity disconnect the appliance from the mains supply using the system
switch and/or the specic breakers.
- In case of failure and/or erratic behaviour, disconnect the appliance and avoid any repair attempt.
Only qualied personnel should perform service and maintenance on the TERMOSPLIT using genuine spare parts. Failure to
comply with such provisions may jeopardize the apparatus safety.
- In case you transfer the appliance to a new owner, please ensure to give him also the manual so he and/or the installer can
refer to it.
- The hot air generator TERMOSPLIT is only intended for the use it has been designed for. Any other use should be consider
incorrect and therefore dangerous.
LAW AND SAFETY RULES FOR PERSONNEL IN CHARGE OF INSTALLATION
Legislative Decree 19/09/94, No. 626
“Implementation of Directives 89/391/CEE; 89/655/CEE, 90/296/CEE, 90/934/CEE, 90/679/CEE, concerning the enhancement of
workers' safety and health in the workplace.
Legislative Decree 04/12/1992, No. 475
“Implementation of Council Directive 89/686/CEE of 21 December 1989, concerning the approximation of the laws of the
Member States relating to personal protective equipment".
During equipment handling, installation and maintenance, pay particular attention to the metal parts to avoid personal
injuries (cuts and/or abrasion). Always wear safety gloves.
LAW AND REFERENCE STANDARDS FOR THE INSTALLER
Law 05-03-90 No. 46
"Systems safety rules".
Presidential Decree 06-12-91 No. 447
“Implementing rule of Law No. 46 of March 5th 1990, concerning systems safety”.
Law 09-01-91 No. 10
"Rules for implementing the national energy plan concerning the rational energy use, the energy saving and the renewable
energy sources".
Presidential Decree 26-08-93 No. 412
"Regulation laying down the rules for the design, the installation and the maintenance of heating systems in buildings to limit
energy consumption, according to Law No. 10 art. 4, par. 4 of January 9th 1991.
D.P.R. ATTACHMENT G 26-08-93 No. 412
"Appliance booklet".
Presidential Decree 21-12-99 No. 551
“ Regulation amending DPR 26-08-93 No. 412, concerning design, installation, operation and maintenance for buildings heating
systems to limit energy consumption".
UNICIG 7129/92 installation rule
"Domestic gas appliances fuelled by gas distribution network".
UNICIG 7131/99 installation rule
"Domestic liquid petroleum gas (LPG) appliances not fuelled by gas distribution network".
CEI 64-8 electric systems rule
Ministerial Order 12-04-96 No. 74
"‘Approval of the re prevention thermal regulation for design, creation and operation of heating systems fuelled by gaseous fuels.

3
(*) The use of zinc plated pipes is no recommended.
Installing a 90/45° bend in the hydraulic circuit reduce the max allowable distance.
TERMOSPLIT 70 KONDENS
Hydraulic distance 0 - 12 m internal min. Ø = 26 mm Hydraulic distance 18 - 24 m internal min. Ø = 40 mm
Hydraulic distance 12 - 18 m internal min. Ø = 32 mm Hydraulic distance 24 - 30 m internal min. Ø = 40 mm
TERMOSPLIT 35 KONDENS
Hydraulic distance 3 - 12 m internal min. Ø = 20 mm Hydraulic distance 18 - 24 m internal min. Ø = 28 mm
Hydraulic distance 12 - 18 m internal min. Ø = 24 mm Hydraulic distance 24 - 30 m internal min. Ø = 30 mm
TECHNICAL DATA
LONG DISTANCES CONNECTION PIPES DIAMETER (*)
DIMENSIONS AND WEIGHTS
MODEL TERMOSPLIT 35 KONDENS TERMOSPLIT 70 KONDENS
CATEGORY II 2H 3P II 2H 3P
WORKING POWER max min max min
Heat output (referred to H
j
)kW 33 759.28 12.14
Thermal efciency (referred to H
j
)kW 32.3 6.8 58.0 12.7
Supply pressure G20 20 mbar 17 mbar 20 mbar 17 mbar
G31 37 mbar 25 mbar 37 mbar 25 mbar
Hourly gas consumption
(15°C - 1013 mbar)
G20 m
3
/h 3.54 1.46 6.4 1.29
G31 kg/h 2.7 0.55 5.0 1.15
Air ow m
3
/h 4100 1750 8300 3480
Air jet m19 825 13
Fluid max pressure bar 3 3
Sound pressure (free eld) dB(A) 50 32 55 36
Air room delta °C 25.8 24.6
Fluid content (standard) l10.00 18.00
Fluid composition 25% glycol - 75% water 25% glycol - 75% water
Voltage and frequency VAC/Hz 230/50 230/50
Power consumption W480 810
Index protection IP internal unit X4D / external unit X5D internal unit X4D / external unit X5D
Exhaust pipe max length m20 20
Ventilation speed No. 4 4
Int./ext. unit min. operation temp. °C -10/-15 -10/-15
Unit max distance m30 30
Unit connection cable max. length m30 30
Exhaust pipe Ø mm 80 80
Gas coupling Ø “ 3/4 3/4
Efciency Pn1 85 - 60 %98 97 98 98.3
Suggested installation heigh m2.5 2.5
TERMOSPLIT
35 KONDENS
TERMOSPLIT
70 KONDENS
Fig. 1

4
1
22
4
3
5
7
68
1. External unit exchanger
2. Automatic vent valve
3. Expansion tank
4. Heat exchanger
5. Unloading/loading valve
6. Pressure gauge
7. Safety valve
8. Circulator unit
NF
EA
SA SA
GND
B-
A+
CONDENSER
CONDENSER PWM
GND
L
X10 X3 X13 X8
X2
X7
X6
X12 X11 X5
SINGLE
BOOSTER
PUMP
ROOM
SENSOR 220Vdc
L N
LL
SV SV
WIND
SENSOR
MULTIPLE
CONTROL CONTROL
L
N
TRR
NEUTRAL
LIVE
LIVE
NEUTRAL
H2O PRESS. jumper
SAFETY THERM.
GAS THERM. jumper
RETURN SENSOR
DELIVERY SENSOR
GAS VALVE
NEUTRAL
LIVE
EARTH
X1
X9
X6
X10
X5
X16
X17X12X19
X3
X30
+24 Vdc
Feedback Hall Sensor
PWM + - 24 Vdc
0 Vdc
X5
GND
TPH2O INPUT
+5Vdc
PRESSURE
TRANSDUCER
FA1
PWM
FAN
PWM
FAN
FAN
IGNITER
LIVE
NEUTRAL
OPEN THERM.
FA4
N
FAN FAN
NN
LOADING
PUMP
GND
TPH2O INPUT
+5Vdc
PRESSURE
TRANSDUCER
NN
L L
CIRCULATOR UNIT
CIRCULATOR
UNIT PWM
ROOM SENSOR
ON/OFF SWITCH
MAX THERM.
MIN THERM.
SAFETY THERM.
LOCK THERM.
BBN L
INTERNAL UNIT CONNECTION CABLE
B B N L
CONNECTION CABLE EXTERNAL UNIT ONLY FOR KONDENS 70KW
FUNCTIONAL HYDRAULIC DRAWING
FUNCTIONAL ELECTRICAL DRAWING
Weight in kg Internal unit External unit
TERMOSPLIT 35 KONDENS 61 38
TERMOSPLIT 70 KONDENS 103 55
Fig. 2
Fig. 3

5
GAS
450
570
DRILLING TEMPLATE
FOR EXTERNAL UNIT
TSK70kW
FORO Ø85 PER
PASSAGGIO TUBI
870
281 210
79
90
132
EXHAUST GAS FLUE
285
285
FLOOR
CEILING
1000
min
1000 min
MINIMUM
RECOMMENDED
2500
1000
min
101
According to the installation design, prepare the
gas supply line and the electric system as per values
shown in the data sheet.
When you have chosen the exact TERMOSPLIT
KONDENS .14 installation position, follow the
instructions below:
- Set the cardboard template onto the wall, at the
desired height and perfectly levelled; the template
in Fig. 5 shows the layout of the holes to be drilled;
- Remove the external unit plastic cover by
unscrewing the two xing screws "A" on both sides.
Remove the front casing by loosening the four clips
xing it to the frame (Fig. 6).;
- Measure the wall thickness at the Ø 85 mm hole
and cut the plastic Ø 80 mm pipe (5 cm longer)
provided, place it in the hole as shown in Fig. 7
and seal it with cement or silicone ash with the
internal wall;
- Place the external unit using proper anchors
and connect the two hoses to the threaded pipe
ttings located on the bottom left side, matching
the colours (Red and Blue), installing the seals
provided. (Fig. 8)
N.B.: The part to be connected to the external unit
is the one with the union elbow.
POSITIONING OF THE APPLIANCE
Before installing the appliance, you have to take
note of the minimum clearances necessary for the
TERMOSPLIT KONDENS .14 installation.
In addition to what shown in Fig. 4, you should also
be borne in mind that:
- Installing the appliance far higher than the
minimum required height is not advisable as it
makes difficult carrying out maintenance and
would require special equipment to work in safe
condition (e.g. scaffold or basket), moreover the
hot air tends to stratify towards the top;
- If the installation minimum required clearances
(shown next) are not met, removing some of the
components could be difcult.
EXTERNAL UNIT INSTALLATION
We suggest to install a destratication fan “MIXER”
to improve thermal comfort and reduce energy
consumption in high premises.
INSTALLATION
GAS
350
132
784
470
246
75
DRILLING TEMPLATE
FOR EXTERNAL UNIT
TSK35
FORO Ø85 PER
PASSAGGIO TUBI
80
145
EXHAUST GAS FLUE
191 280
"Clip"
"Clip"
"Clip"
"Clip"
"A"
"A"
Fig. 4
Fig. 5
Fig. 6

6
Pre-cut
slot
Condensate outlet
Condensate trap
Grey-water drainage
Boiler
condensate
trap
If a standard installation is not feasible as it is not
possible to drill a connection hole between internal
and external unit as per the cardboard template,
you can guide the two connection pipes and the
electrical cable through the bottom removing the
pre-cut slot (see Fig. 9).
You will have to use more ttings (not provided) and
a pipes and cable conduit for protection against
UV and weathering.
N.B.: Pay attention to the ow direction (delivery
and return).
TERMOSPLIT KONDENS .14 is already tted with a
condensate trap to avoid the combustion products
entering the environment it is installed in.
The boiler's connection to the condensate line must
be inspectable and must drain into the household
waste-water drainage system with a minimum fall
specied by applicable regulations. There must be
no points where standing water can form and no
narrowing which could impede the ow.
An open type connection must be used to ensure
that any formation of ice in the drainage system
does not impede the condensate ow. Fig. 10
shows how to connect the trap to the household
drainage system.
Reference standard UNI 11071.
The installer shall be responsible for installing a
condensate neutralisation system if necessary.
CONNECTING THE CONDENSATE LINE
Fig. 10
50 mm
Seal with cement
or silicon
"B" RED
"A" BLUE
Connection
cable
Fig. 7 Fig. 8
Fig. 9

7
EXHAUST FUMES AND AIR INTAKE SYSTEM INSTALLATION
The external unit TERMOSPLIT KONDENS .14 comes
with exhaust fumes and air intake system on the
top (wall-mounted exhaust) (A).
If it is not possible a wall-mount exhaust or you
prefer a roof-mount exhaust (for exhaust pipes
max. length see Table on page 4) you need to do
the following:
- Remove the cover "D" from the external unit by
unscrewing the two xing screws located on the
side (D1);
- Drill, in the position shown in Figure 11, a hole with
a diameter suitable for a Ø 80 pipe;
- Remove the metal sheet "C" releasing it from
exhaust "A";
- Remove the plug "B" from the exhaust "A"
loosening the two side screws (Fig. 12);
- Reinstall the exhaust "A" by xing it with the metal
sheet "C" and replace the cover "D";
- Install a rubber rosette "E" onto the Ø 80 pipe;
- Insert the Ø 80 pipe in the exhaust "A" until it
reaches the stop. The standard front outlet will
close and the fumes will go out through the inserted
vertical pipe;
- Check the pipes for proper installation to prevent
rainwater inltration in the appliance;
- Reinstall the two side screws.
Fig. 12
Fig. 11
FLUE DUCT SELECTION
Similarly to all condensing appliances, TERMOSPLIT
KONDENS .14 needs approved ttings made of acid
aggressive resistance materials for fumes exhaust.
We suggest you to buy only genuine Air Control
parts.
"D"
"B"
"A"
"E"
"C"
"D1"
"D1"

8
Installation of TERMOSPLIT KONDENS .14 is complete
when the two units are connected by means of
the electric cord and the delivery and return pipes.
Proceed as follows:
- connect the two pipes shown in Figure 15 to the
two valves "A" and valve "B", making sure to match
the relevant colours; open the two shut-off valves.
N.B.: In order to obtain a leak proof joint insert
the relevant TEFLON gaskets (included). Even
the slightest leak could prevent operation of the
TERMOSPLIT KONDENS .14 in a short time.
- You must now connect the two units using the
power cord built-in in the external unit.
N.B.: The two units can installed be as much as 30
metres max apart from each other (over 20 metres
a booster pump is required). The pipes size shall be
adapted accordingly and the uid relled (see the
technical data table on Page 4). The connection
cable can be ordered according to the required
length (max. 30 m.).
CONNECTION OF THE TWO UNITS
INTERNAL UNIT INSTALLATION
When you have chosen the installation position
of the TERMOSPLIT KONDENS .14 internal unit and
veried the corrected clearances as shown in Fig.
5 on page 6, you'll have to do the following:
- Remove the appliance from the packaging;
- Remove the two plastic sides;
- Following the guidelines on the cardboard
template, define the holes needed to fix the
TERMOSPLIT KONDENS .14;
- Position the cardboard template (see page 6);
- Drill the holes according to the anchors diameter
used;
- Screw a counter-locknut between the wall and
the mount bracket, then hang up the internal unit
and lock with a self-locking nut.
CAUTION: To avoid damaging the mount bracket,
do not over tighten the locknut if you don't have
inserted the counter-locknut.
N.B.: We suggest to use anchors with threaded bar
(max M8) as shown in Figure 14.
ANCHOR WITH
THREADED BAR
(M8 max.)
*: 45 mm
COUNTER-LOCKNUT
"B" RED
"A" BLUE Connection
cable
Fig. 13 Fig. 14
Fig. 15

9
CONNECTION TO THE TANK
In addition to the standards for the connection to
the methane gas network, you have to conform
to the following:
- Use only Teon or suitable sealant for ttings (do
not use hemp);
- Install a pressure reducer at the LPG tank
outlet calibrated to 1.5 bar and, before using
the appliance, install a second stage reducer
calibrated to a 30 mbar pressure for commercial
butane. When the installation is complete, always
check the seal as per UNI-CIG 7131 standard.
CONNECTION TO THE METHANE GAS NETWORK (G 20)
- According to the installation design, prepare the
gas supply line as per values shown in the data
sheet (see page 4).
- Connect the methane distribution network using an
appropriate pipe for the TERMOSPLIT KONDENS .14
consumption (see Figure 6 on page 7).
- Always install a shut off ball valve upstream of
the appliance.
- Check the inside of the pipe for contaminants
and, when the installation is complete, the tightness
as per UNI-CIG 7129 standard.
CARRIER FLUID FILLING
This activity must be carried out by the installer
during the appliance installation according to the
following instructions:
- Connect a loading pump to the valve;
- Open the valve;
- Ensure the automatic air vent valve plugs on both
units are open; Leave them open so the air in the
circuit comes out automatically. In the top part of
the unit there is also a manual bleed valve;
Fig. 16 Fig. 17
Once the installation is complete, and before
mounting the side panels of the internal unit, check
the circuit for uid leaks and that its pressure ranges
between 1.8 and 2.0 bars.
- Load the uid provided (pre-mixed 75% water +
25% glycol) until you reach about a 2 bar pressure;
- Close the valve and disconnect the pump.
Filling loop
cock SK35.13 Filling loop
cock SK70.13

10
Fuel shut-off
valve
Cock with
pressure gauge
Bithermostat
Thermometer
Minimum
pressure switch
Maximum
pressure switch
V.I.C. capillary
ISPESL
safety valve
Fig. 20
TERMOSPLIT KONDENS 70 - I.S.P.E.S.L. SAFETIES
TERMOSPLIT KONDENS .14 70 is supplied complete
with all I.S.P.E.S.L. safety-related components, pre-
installed and certied, but the (mandatory) On/
Off valve.
The choice of this valve is at the discretion of the
installer, who shall provide the external mounting
of the device as shown in Figure A.
Each TERMOSPLIT KONDENS .14 70 comes with
the specic pit for installing the fuel On/Off valve
capillary (suitable to the CALEFFI valve mod.
541050).
N.B.: Certificates for the approved I.S.P.E.S.L.
components are included in the appliances
technical documentation.
CARRIER FLUID FILLING/TOPPING UP BY SELF REFILLING KIT
Relling the carrier uid is performed automatically
during the rst start-up of the appliance. In order to
do this, once the internal unit is installed, open the two
connection valves between the units (making sure no
leaks are present), pour the content of the included
uid can in the machine relling tank and power the
appliance On.
In case the pressure of the uid is lower than 0.9 bar,
the loading pump will start automatically, increasing
the pressure up to 1.8 bars within 5 minutes maximum.
In case the required pressure is not reached within 5
minutes, the pump will stop.
You must now verify the circuit for leaks and the relling
tank for full, then cycle power to the system for reset;
now the system should restart the automatic relling.
The automatic refilling process is set to start
automatically any time the internal circuit pressure
drops below 0.9 bars.
In case of failure of the loading pump or if you need
emptying the system, use the manual unloading/
loading valve provided.
Once the installation is complete, and before
mounting the side panels of the internal unit, check
the circuit for uid leaks and that its pressure ranges
between 1.8 and 2.0 bars.
Fig. 18 -
TERMOSPLIT KONDENS 35.14
Fig. 19 -
TERMOSPLIT KONDENS 70.14

11
Fig. 21
Fuel shut-off
valve
Cock with
pressure gauge
Bithermostat
Thermometer
Minimum
pressure switch
Maximum
pressure switch
V.I.C. capillary
ISPESL
safety valve
Upon request, Air Control can supply the fuel
shut-off valve CALEFFI mod. 541050 (already
installed in the external unit) as highlighted in
Figure 21.
PLUG
3
.15 A FUSES
CABLE SOCKE
T
Socket
CONNECTION TO THE 230 V 50 HZ MAINS
Connect the appliance to a suitable ground system.
This operation must be performed only by qualified
personnel, with specic expertise in domestic and/or
industrial components, meeting the CEI Standard.
Fig. 22
TERMOSPLIT KONDENS .14 requires only a connection
to 230 V/50 Hz mono-phase power (Fig. 13). A correct
connection requires linking the earth, line and neutral
cables to the cable socket (Fig. 23) matching the
polarities shown in the socket. The connection cable must
have a section of 3x1,5 mm2.
Fig. 23

12
"CRONO" CABLE
CONNECTOR
SINGLE CONTROL CONNECTION AND INSTALLATION
- Locate the position in which you plan to install
the single control;
- Drill 2 holes Ø 5 mm. spanning 97 mm between
centres and insert anchors and screws, tightening
the screws as to leave a 3-4 mm gap from the wall
(Fig. 24).
- Remove the control's back panel, connect the
cable to the connector (Fig. 25) and secure the
cable with the appropriate cable clamp. Close
the control and hang it by the screws. Connect
the other cable end to the terminal board internal
unit, R-R position (see Figure 26), driving it through
cable clamps "A" and "B".
Fig. 24
Fig. 25
Fig. 26
L N A+ B- SA SA LN
BOOSTER
PUMP
ROOM
SENSOR 230 Vdc
GND
RR
SV SV
WIND
SENSOR
SINGLE
CONTROL
MULTIPLE
CONTROL
"A"
"B"
Never leave the control panel hanging without
fastenings. Always verify that the control panel
cable is isolated from non low-voltage power
cables.
Fig. 27
Multi-boilers connection - Example chart
IMPORTANT NOTES
- TERMOSPLIT KONDENS .14 must be connected to the
ground.
- The plug in the bottom part of the internal unit includes
also the 3.15 A fuses.
- Never modify the TERMOSPLIT KONDENS .14 electrical
wiring.
Never connect to the TERMOSPLIT KONDENS .14 any kind
of electric/electronic device other than those provided by
the manufacturer.
When required, a CR011 remote device allows to control
multiple fans (up to 8) with one single control.
This single control allows full management of all main boiler
functions, for multiple boilers from remote locations.
In addition, the CR011 allows to schedule ambient
temperatures on a daily/weekly basis and manage
decreased activity periods such as holidays, maintenance
etc.
Please refer to the specic manual for more information on
the control's operation.
In case a booster pump is required, to be installed
on the connection pipes between the external and
internal units, it shall be connected to the terminals
L - N POMPA RIL. - of the internal unit terminal board
(see Fig. 25).
The booster pump and the fan unit pump operation
will be enabled simultaneously,
- The connection cable for the TERMOSPLIT KONDENS .14
control panel must always be isolated from non low-voltage
electric cables.
- Never modify or cut the connection cable between the
two units.
N.B.: The installer is required to inform the customer
about the use of the equipment and to provide the
complete technical documentation.
MULTIPLE CONTROL CONNECTION
CONNECTING THE BOOSTER PUMP
UNIT 1 UNIT 2 UNIT 3
SV SV A+ B- SA SA LN
230 Vdc
GND
RR
CR011 REMOTE CONTROL
485 network 4 poles twisted cable (400 mtrs. max)
L NSV SV A+ B- SA SA LN
WIND
SENSOR
ROOM
SENSOR 230 Vdc
GND
RR
L N
BOOSTER
PUMP
MULTIPLE
CONTROL
SV SV A+ B- SA SA LN
230 Vdc
GND
RR
L N
GND
12V cc
12 VCC Power supply
A+ B- GND A+ B- GND
AIR HEATER
UNIT
1
AIR HEATER
UNIT
2
A+ B- GND
AIR HEATER
UNIT
2
MAX 8
A+
B-
GND
SINGLE
CONTROL
WIND
SENSOR
ROOM
SENSOR
BOOSTER
PUMP
MULTIPLE
CONTROL
SINGLE
CONTROL
WIND
SENSOR
ROOM
SENSOR
BOOSTER
PUMP
MULTIPLE
CONTROL
SINGLE
CONTROL
CR011 REMOTE CONTROL
To connect the CR011 sole remote control, all the equipments
must be connected sequentially; a maximum length of the
connections not exceeding 400 meters and the use of a
TWISTED 4 POLES CABLE for 485 NETWORK are recommended.

13
FIRST IGNITION
GENERAL INSPECTION
Before performing the rst ignition (also known as
"rst ignition test") the local T.A.C. shall check the
appliance for correct installation. This check is
specically aimed at those conditions that could
endanger the safety and functionality of the
appliance. Therefore, it's quintessential that the
installation meets the minimum required height and
obstacles clearance, as shown in Figure 1 on page
6 and dened by UNI-CIG standards 7129/7131, Law
46/90 and CEI 648 standard.
Furthermore, you must check that the installation
has been performed as described in the AIR
CONTROL manual. In case the T.A.C. detects
any potential problem that may affect the
safety or functionality of the appliance, the
commissioning shall not be performed and the lack
of compliance communicated to the installer and
the manufacturer.
IMPORTANT: the first ignition MUST be solely
performed by an AIR CONTROL Authorized
Technical Assistance Centre.
ANALYSIS - CHECKING AND REGULATING COMBUSTION
The boiler comes already calibrated and tested for the
requested type of gas, however it is advisable to check
that the type of gas supplied in the mains and the supply
pressure are correct. If this should not be the case, follow
the procedures described in this section.
Using a pressure gauge connected to the gas valve"P"
pressure port (Fig. 31), check that the measured pressure
matches the values shown in the technical data table.
MAXIMUM POWER:
• Cut power to the equipment using the power switch
and open the instrument board by loosening the
cover 4 "A" screws (See Fig. 28).
• Set the A and B JUMPERS to ON (see Fig. 29) so that
the boiler ramps automatically to max. power at
restart.
• Close the instrument board, apply power, switch the
boiler On and set the fan in manual mode at max.
speed. Wait a few seconds for the ignition phase
to nish and the boiler to reach automatically the
max. power.
• Insert the combustion analyser probe in the
inspection outlet provided in the ue (Fig. 30). After
the boiler has been running for 2-3 minutes, run the
analysis and check that the CO2 measured by the
analyser corresponds to the value indicated in the
table for maximum power.
• If the CO2does not correspond, regulate with screw
"N" (Fig. 31) of the ratio adjuster until the specied
CO2 value is obtained. Turn clockwise to decrease
the CO2, value, anticlockwise to increase it.
MINIMUM POWER:
• Cut power to the equipment using the power switch
and open the instrument board by loosening the
cover 4 "A" screws (See Fig. 28).
• Set the A and B JUMPERS to OFF (see Fig. 29) so
that the boiler ramps automatically to min. power
at restart.
• Close the instrument board, apply power, switch the
boiler On and set the fan in manual mode at max.
speed. Wait a few seconds for the ignition phase
to nish and the boiler to reach automatically the
min. power.
• After the boiler has been running for 2-3 minutes, run
the analysis and check that the CO2 level measured
by the analyser corresponds to the level shown in
the table at minimum power.
J U MP E R
AB
A B
C
C
MIN
MAX
Unscrew the dowel
A
A
A
A
Fig. 28
Fig. 29
Fig. 30

14
A B C
J U MP E R
A B C
METHANE
LPG
CHANGING THE SUPPLY GAS
• If the CO2 level does not match, adjust it using
the screw "M" (Fig. 31) of the ratio adjuster, after
removing the protective cover "L" until the specied
CO2 level is reached. Turn clockwise to increase the
CO2, value, anticlockwise to decrease it.
Once the adjustments are complete it's advisable to
move the "A" and "B" JUMPERS to Off position (open);
screw in place the "L" protection cover; check if the
pressure outlet screw is tightened and the ue line is
perfectly leak proof. Restore the desired condition for
the fan.
It may be necessary to repeat the maximum and
minimum adjustment twice to obtain correct regulation.
TERMOSPLIT 35 KONDENS CO2 TABLE TERMOSPLIT 70 KONDENS CO2 TABLE
P
L
M
N
+ -
- +
Fig. 31
Fig. 32
Fig. 33
U.M. G20
(Methane)
G31
(LPG)
CO2 max power % 9.5 +1 -0 10.6 + 0.1 -0
CO2 min power % 8.8 +1 -0 9.8 + 0.1 -0
Min. network pressure mbar 17 29
Max. network pressure mbar 25 37
U.M. G20
(Methane)
G31
(LPG)
CO2 max power % 9.3 +1 -0 10.6 + 0.1 -0
CO2 min power % 8.7 +1 -0 10.7 + 0.1 -0
Min. network pressure mbar 17 29
Max. network pressure mbar 25 37
CHANGING FROM METHANE TO LPG
• Remove the boiler casing (external unit).
• Cut power to the equipment using the power switch
and open the instrument board by loosening the 4
cover screws (See Fig. 28).
• Move the C JUMPERS to On position (see Fig. 32) so
that the boiler will automatically change to LPG at
restart.
• Close the instrument board and apply power.
• On TERMOSPLIT KONDENS .14 70 only, you are
required to replace the adjustment diaphragm
located in the Mixer (Fig. 33) changing from Ø31 for
methane (G20) to Ø29 for LPG (G30/G31).
• Check that the supply pressure coming into the boiler
is correct and that there are no gas leaks.
• Repeat the adjustment for Max. and Min. power.
• Once the change and any adjustment have been
performed, seal the valve and update with the
correct data the data plate on the boiler.
CHANGING FROM LPG TO METHANE
• Cut power to the equipment using the power switch
and open the instrument board by loosening the 4
cover screws (See Fig. 28).
• Move the C JUMPERS to On position (see Fig. 32) so
that the boiler will automatically change to METHANE
at restart.
• Close the instrument board and apply power.
• For TERMOSPLIT KONDENS .14 70 only you are required
to replace the adjustment diaphragm located in the
Mixer (Fig. 33) changing from Ø29 for LPG (G30/G31)
to Ø31 for Methane (G20).
• Check that the supply pressure coming into the boiler
is correct and that there are no gas leaks.
• Repeat the adjustment for Max. and Min. power.
• Once the change and any adjustment have been
performed, seal the valve and update with the
correct data the data plate on the boiler.

15
Fig. 34
WARNING FOR THE TENANT
- Before any use of the equipment, and within 30 days from the installation, you are required to have the
local T.A.C. perform the free First Ignition test. (The list of the authorised Technical Assistance Centres is
attached to the documentation of each appliance).
- In order not to cut out the electronically managed safeties, the equipment shall always be powered even
when not in use.
- Furthermore, with regard to your and other peoples' safety, you are required not to perform any direct
intervention on the appliance and especially on gas and/or electric components.
FUNCTIONAL CHARACTERISTICS
SINGLE CONTROL
TERMOSPLIT KONDENS .14 can be used for heating
large environments where re risk activities are
performed. The built-in control panel enables to
set manually summer and winter operation on 4
power levels with the relevant fan speeds.
USE AND OPERATION
These are used to view and change the air ow rate level from 0 (automatic) to 4 (maximum manual
power). They are also used to set the time and scroll the menus.
These are used to view and change the room temperature set points that can be set.
MODE: used to select the boiler operating MODE.
Boiler ON/ OFF. Conrmation.
Programming and menu info (in the submenus this is also used to return to the main page)
Enables the timed functions (PARTY and VACATION)
FIRST IGNITION
The rst time the remote programming unit is turned on, the
warning CLOW will appear on the display (the backup ca-
pacity is not sufciently charged). To access the info menu,
wait a few minutes, which is the time required for the backup
capacity to accumulate the minimum charge needed for
operation.
0 3 6 9 12 15 18 21 24h
SET
DAY
123457
°F
°C
00:000

16
Password change
After being allowed to access, you can modify
the two passwords by pressing simultaneously the
keys
PROG
and .
The blinking symbol of a spanner will display,
followed by the messages “IPS” or “IPS2” for
entering password_1 or password_2 respectively,
according to the method previously explained.
Exiting the pages for entering/changing the
password takes place automatically after a 5
seconds inactivity or pressing any other key.
The initial conguration has both passwords null
(00000).
After each password change you must wait at least
10 seconds for storage in a non-volatile memory.
Power failures before 10 seconds are elapsed may
cause missed data storage.
The following chart shows the menus with password.
In the initial screen, press one of the following
buttons
PROG
,
AUTO
, , , to enter the access
password screen. Entering the correct password
will enable all the keys for 5 minutes after the last
pressure on any key. After the time-out the keys
shown above are disabled. When pressed again,
you will have to re-enter the password.
When pressing the above keys you are prompted a
"PS" message and a 5 digit password is requested.
The rst digit will blink and, using the and
keys, you will be able to change it. After setting the
relevant value you must press the OK key to move
to the next digit, that will start blinking.
After entering all the 5 digits and pressing the
OK
key for the last time, if the password you entered
is correct, you will move to your requested screen.
In case a wrong password was entered, you will
return to the rst blinking digit.
After 5 failed attempts the Errore 96 message will
appear. It will disappear only by pressing the OK
key, but it will re-appear after 1 minute without
pressing any key.
After this lock, having exceeded the maximum
number of allowed attempts, you will be prompted
to enter a Level 2 password (message "PS2" on the
display) whose task is to reset the number of trials
with password_1.
After entering password_2 you will have to re-enter
also password_1.
The number of failed access attempts, or any lock,
is stored also in the ash memory (at 10 seconds
intervals) and remains stored also after cycling the
power (Off/On).
The maximum number of attempts allowed with
password_1 is reset after unlocking with password_2
or at the clock's midnight, unless the maximum
is not exceeded; otherwise, the unlock request
through password_2 will remain.
Fig. 35
Fig. 36
Fig. 35
PASSWORD REQUEST

17
0 3 6 9 12 15 18 21 24h
1. By selecting AUTOMATIC mode, the symbols and
appear on the display. The boiler satises the heat request for
heating based on the programmed time intervals.
The elapsed time interval is shown blinking (on the program's
phase cursor). It also species whether the level is COMFORT
or ECONOMY .
During the time interval when the boiler remains OFF (in
STANDBY), the cursor does not ash and the control switches
to antifreeze.
OPERATING MODES
Pressing the MODE
AUTO
key repeatedly makes it possible
to set one of the following boiler operating modes:
ILLUSTRATIVE GRAPH
PROG
PROG
OK
AUTO
AUTO
>> COMFR (Comfort)
>> ECONM (Economy)
>> TIME (Clock)
>> PROG (Time progr.)
>> EXT T
>> CH 0
>> CH SP
>> HW PR
>> HW SP
>> PWR
>> SDR
>> NO FRX
>> T FRX
>> CH SL
>> T MX
>> T MN
>> CH MX
>> CH MN
>> MAX P
>> OFF (STANDBY)
>> AUTOMATIC
>> MANUAL COMFORT
>> MANUAL REDUCED
>> OFF (OFF) >> VENT 0
>> VENT 1
>> VENT 2
>> VENT 3
>> VENT 4
>> T AMB >> PARTY
>> OFF (Vacation)
+
key pressed
for 3 secs
key pressed
for 3 secs
MAIN
SCREEN
MODE SYMBOLS ACTIVATED
AUTOMATIC
MANUAL COMFORT
MANUAL REDUCED
SUMMER - - -

18
During automatic operation, the and keys can be
used to manually change the level set by the program or to
switch off the heating.
This temporary change is indicated by the ashing symbol
and lasts until the next time interval.
The selected level is indicated by the respective symbol:
COMFORT
ECONOMY
OFF OK
SETTINGS MENU
CLOCK (TIME)
WEEKLY TIME PROGRAMMING
Pressing the
PROG
key accesses the INFO – settings menu.
Use the
PROG
key to scroll the menu, to enter and make
changes, press
OK
.
•COMFR (Comfort) - Sets the set point for the comfort level
(the set point will be stored).
•ECONM (Economy) - Sets the set point for the economy
level (the set point will be stored).
•TIME (Time) - Clock setting.
•PROG (Time programming) - Sets the weekly time
programming.
•EXIT
At the end of the menu, there is the automatic exit from the
INFO – settings menu.
To set the clock, enter the settings menu by pressing
PROG
.
Scroll the menu to TIME and press
OK
to access the submenu.
The time can be changed using the and keys. To
change the minutes, press the
PROG
key, and press it also to
change the day.
To conrm the changes, press the OK key (the display will
return automatically to the main page).
To change the heating mode weekly time programming,
press the
PROG
key to access the settings menu and then select
the programming menu by repeatedly pressing the
PROG
key.
Press the OK key to access the time programming menu.
Time programming makes it possible to set the automatic
operation of the boiler in heating mode during certain time
intervals and on certain days of the week, selecting the
temperature level for each interval.
The boiler operating settings can be set for single days or for
groups of consecutive days.
Single days
There are 4 time intervals available for every selected day (4
periods of switching the boiler on and off in heating mode,
also with different times for each day), as shown in the
following table:
SETTINGS IN MANUAL MODE
The settings that can be made in MANUAL mode (fan speed,
room temperature) must be stored so that after turning off
the system, the unit will return to the previous conditions after
turning back on.
Pressing the OK key turns off all the functions except for anti-
freeze, if turned on. Only the symbol will be on. Pressing the
OK
key again returns to the mode set prior to switching off.
2. By selecting MANUAL COMFORT, the symbols , and
appear on the display.
The boiler satises the heat request for heating based on the
set comfort temperature.
3. By selecting MANUAL ECONOMY, the symbols , and
appear on the display.
The boiler satises the heat request for heating based on the
set economy temperature.
4. In SUM mode (summer), the summer cooling function will
be activated via the fans; the fan symbol will appear
on the display.
This manual suits for next models
1
Table of contents
Popular Heater manuals by other brands

Flamerite Fires
Flamerite Fires Tyrus Inset Instructions

SchwankAir
SchwankAir 524EH manual

Conrad
Conrad 56 10 79 operating instructions

Pinnacle
Pinnacle REMINGTON REM-45-KFA-O User's manual & operating instructions

Raider
Raider RD-DSH20 user manual

Pinnacle
Pinnacle ProTemp PT-80-OFR User's manual & operating instructions