12
Condensation drain connection
During the cold period, condensation forms in the unit and must be drained out of the unit. If a heat
recovery heat exchanger (ERV) is used, no condensate
will form under normal conditions, but it is still
recommended to connect it.
•To connect the condensate, screw the
condensate lock onto the bushing on the bottom
of the appliance. Make sure the connection is
correct and tight.
Condensate drain is included with each unit as standard.
A 32 mm pipe can be used to continue the condensate
drain. The appliance must be level to allow normal
condensation to drain out. Once a year, the condensate drain should be removed from the unit and
cleaned of accumulated dirt. Only use the condensate drain specified by the manufacturer. The
condensate drain valve is equipped with a vacuum valve, which ensures airtightness during the dry
period.
Installing and connecting the buttoned remote control (VB-
2)
The control panel shall be installed in a room where the following conditions are met:
●The ambient temperature is between 5 ° C and 30 ° C and the humidity is up to 80%.
●The control panel does not come into contact with steam or liquids.
The control panel is connected to the ventilation unit with a 4-core (max. 0.75 mm 2 ) low-voltage
cable to the connection socket on the side or top of the
unit. The remote control comes with a 5 meter cable that
you can use to connect the remote control.
•Connect the control panel cable from the device
to the control panel terminals marked 5V -
brown, A - yellow, B - white, GND - green. Make
sure that the control unit and the ventilation unit
are connected correctly as marked
●There are 2 holes on the back for attaching the
remote control to the wall. Tighten the screws on
the wall, and then place the remote control on
the wall with the holes shown in the illustration.
It is recommended to plan a suitable location in the room
for the control panel during the design phase so that the cable can be routed through the wall to the
desired location. To connect a cable that is routed separately through a wall, open the electrical
cabinet of the ventilation unit and connect the wires to the LCD terminals as marked.