
OPERATING AND INSTALLATION MANUAL HEAT PUMP COMBI UNIT PKOM4 PAGE 9
SPECIALIST PERSONNEL GENERAL
USER
Electrical connection work and
work on the system's electrical
components may be carried out
by authorised electricians only, in compli-
ance with national and local regulations.
Before opening the unit and
when carrying out work on the
unit e.g. maintenance work and
repairs, the unit must be isolated from the
mains (all poles disconnected) and secured
against being switched back on for the
duration of the work. The heat pump combi
unit is designed for a voltage supply of 230
V/50 Hz.
Work practices that could
potentially damage the unit are
prohibited. To ensure safe opera-
tion, safety devices must not be removed or
bypassed.
Electrical equipment and the
unit's warning and protective de-
vices must be inspected regularly
to ensure that they are in perfect working
order. In the event of faults in the electrical
power supply or identification of defects
e.g. loose connections or burnt or defective
cables, the unit must be switched o imme-
diately. The unit may not be operated until
safe operational conditions are restored.
Fault finding and immediate remediation
of electrical defects and mal-
functions shall be carried out by
authorised electricians only. All
protective measures must be inspected
(e.g. earth resistance, etc.) after completion
of electrical work on the unit. For details,
see Section 13: “Electrical Connection”.
All national and local regulations
must be heeded when assem-
bling, installing and setting up
the unit. Installation shall be carried out in
accordance with the general local building,
safety and installation regulations of the
relevant community or the water and elec-
tricity department and other bodies.
Observe all locally-applicable construction
and fire protection guidelines, regulations
and standards. If necessary, appropriate
suitable measures should be taken when
installing the unit e.g. installation of fire
dampers in air ducts, etc.
The unit may only be installed in frost-free
and dry rooms. The room temperature at
the place of installation must be consist-
ently between +5°C min. and +35 °C max.
The unit is designed for upright installa-
tion and may only be set up on a suitable,
load-bearing construction. The unit must
not be exposed to vibration of any kind.
Suitable drainage of condensate aris-
ing during operation of the unit will be
required, including eective odour blocking
traps (siphon). Installations for water,
heating and condensate connections may
be performed by a specialist only. The unit
must be installed and executed appropri-
ately so as to ensure seal-tightness and
eective condensate drainage in order to
exclude the possibility of building damage.
Eective condensate drainage must be
verified on-site prior to initial start-up and
after servicing the unit.
The maximum permissible load must be
observed when transporting the unit.
Components of the heat pump combi unit,
e.g. air ducts which may need to be in-
stalled in unheated areas, must be suitably
insulated to prevent heat loss or conden-
sate formation (for temperatures under
dewpoint).
5.3 DEVICE INSTALLATION
5.4 ELECTRICAL
CONNECTION WORK