Airzone Easyzone AZCE6CB1IAQ User manual

Installation Manual
Easyzone

Contents
ENVIRONMENTAL POLICY_________________________________________________________________________ 3
BEFORE STARTING__________________________________________________________________________________ 4
ELEMENTS AND INSTALLATION__________________________________________________________________ 5
>Main control board (AZCE6CB1IAQ)___________________________________________________ 5
>Assembly_____________________________________________________________________________ 5
>Connection ___________________________________________________________________________ 5
>Temperature probe (AZX6SONDPROTEC) __________________________________________ 8
>Control Module of Radiant Elements (AZCE6OUTPUT8)_________________________ 9
>Assembly_____________________________________________________________________________ 9
>Connection __________________________________________________________________________ 9
>Wired Thermostat _______________________________________________________________________ 11
>Elements _____________________________________________________________________________ 11
>Assembly_____________________________________________________________________________ 11
>Connection ___________________________________________________________________________ 11
>Wireless thermostats ___________________________________________________________________ 12
>Elements _____________________________________________________________________________ 12
>Assembly_____________________________________________________________________________ 12
>Airzone Control Gateway-3 Speed Fancoil (AZX6FANCOILZ) ___________________ 13
>Elements _____________________________________________________________________________ 13
>Assembly_____________________________________________________________________________ 13
>Connection ___________________________________________________________________________ 14
>Airzone Control Gateway-0-10V Fancoil (AZX6010VOLTSZ) ___________________ 15
>Elements _____________________________________________________________________________ 15
>Assembly_____________________________________________________________________________ 15
>Connection ___________________________________________________________________________ 16
>Airzone Control Gateway-Electromechanical Unit (AZX6ELECTROMEC) _____ 17
>Elements _____________________________________________________________________________ 17
>Assembly_____________________________________________________________________________ 17
>Connection ___________________________________________________________________________ 18
>Webserver Airzone Cloud ______________________________________________________________ 20
>Elements _____________________________________________________________________________ 20
>Assembly_____________________________________________________________________________ 21
>Connection __________________________________________________________________________ 22
>Supermaster Controller (AZX6CSMASTER [S/E] [B/G])___________________________ 24
>Assembly_____________________________________________________________________________ 24
>Connection ___________________________________________________________________________ 24
>Production control board _______________________________________________________________ 25
EN

>Elements _____________________________________________________________________________ 25
>Assembly_____________________________________________________________________________ 25
>Connection ___________________________________________________________________________ 26
>Airzone-KNX Integration Gateway (AZX6KNXGTWAY) __________________________ 30
>Elements _____________________________________________________________________________ 30
>Assembly_____________________________________________________________________________ 30
>Connection ___________________________________________________________________________ 30
>Airzone-BACnet Integration Gateway (AZX6BACNET) ___________________________ 31
>Elements _____________________________________________________________________________ 31
>Assembly_____________________________________________________________________________ 31
>Settings_______________________________________________________________________________ 31
>Airzone-Lutron Integration Gateway (AZX6GTILUT)______________________________ 32
>Elements _____________________________________________________________________________ 32
>Assembly_____________________________________________________________________________ 32
>Settings_______________________________________________________________________________ 32
>Airzone Consumption Meter (AZX6ACCCON)_______________________________________ 33
>Assembly_____________________________________________________________________________ 33
>Connection __________________________________________________________________________ 33
>Reset __________________________________________________________________________________ 33
SYSTEM INSTALLATION____________________________________________________________________________ 34
>Easyzone plenum assembly ___________________________________________________________ 34
>Assembly in the indoor unit ______________________________________________________ 34
>Fresh air intake (CMV) assembly ________________________________________________ 35
>Additional Easyzone information_____________________________________________________ 36
>Bypass damper assembly ________________________________________________________ 36
>Damper override ____________________________________________________________________ 36
>Motorized plenum with blind cover _____________________________________________ 37
>Thermostat installation _________________________________________________________________ 38
>Connection to the indoor unit__________________________________________________________ 38
>Other peripherals_________________________________________________________________________ 38
>Power supply to the system ___________________________________________________________ 39
CHECKING THE INSTALLATION ___________________________________________________________________ 40
INITIAL CONFIGURATION __________________________________________________________________________ 41
>Airzone Blueface _________________________________________________________________________ 41
>Airzone Think _____________________________________________________________________________ 42
>Airzone Lite________________________________________________________________________________ 44
>Checking the initial conguration_____________________________________________________ 45
>System reset ______________________________________________________________________________ 45
>Zone reset _________________________________________________________________________________ 45
AIRFLOW REGULATION ____________________________________________________________________________ 46
>Airow adjustment (REG)_______________________________________________________________ 46
EN

>Minimum air adjustment (A-M)________________________________________________________ 46
SYSTEM ADVANCED SETTINGS __________________________________________________________________ 47
>Airzone Blueface _________________________________________________________________________ 47
>Airzone Think _____________________________________________________________________________ 47
>System parameters______________________________________________________________________ 48
>Zone parameters _________________________________________________________________________ 50
INCIDENTS ____________________________________________________________________________________________ 51
>Warnings___________________________________________________________________________________ 51
>Errors _______________________________________________________________________________________ 51
NAVIGATION TREES ________________________________________________________________________________ 62
>Airzone Blueface _________________________________________________________________________ 62
>Screensaver__________________________________________________________________________ 62
>Main screen__________________________________________________________________________ 62
>Advanced settings__________________________________________________________________ 63
>Screensaver__________________________________________________________________________ 63
>Main screen__________________________________________________________________________ 63
>Airzone Think _____________________________________________________________________________ 64
>Screensaver__________________________________________________________________________ 64
>Main screen__________________________________________________________________________ 64
>Advanced settings__________________________________________________________________ 65
>Screensaver__________________________________________________________________________ 65
>Main screen__________________________________________________________________________ 65
EN

AZCE6BLUEFACEC AZCE6THINKC AZCE6LITEC AZCE6THINKR AZCE6LITER
AZX6CABLEBUS
D3
R1 R2 R3 R4 R5 R6 R7 R8
AZCE6OUTPUT8

(ES) Easyzone CAI
(ES) Ionizador Airzone (ES) Central del sistema(ES) Sensor de partículas (ES) Pasarela de control
(ES) Unidad interior
(EN) Easyzone IAQ
(EN) Airzone ionizer (EN) Particulate matter
sensor
(EN) Main control board (EN) Control gateway
(EN) Indoor unit
(FR) QAI Easyzone
(FR) Ioniseur Airzone
(FR) Sonde de matières
particulaires
(FR) Platine centrale du
système
(FR) Passerelle de contrôle
(FR) Unité intérieure
(IT) IAQ Easyzone
(IT) Ionizzatore Airzone
(IT) Sensore di particolato
(IT) Scheda centrale del
sistema
(IT) Interfaccia di controllo
(IT) Unità interna
(PT) QAI Easyzone
(PT) Ionizador Airzone
(PT) Sensor do material
particulado
(PT) Central do sistema
(PT) Gateway de controlo
(PT) Unidade interior
(DE) Easyzone RLQ
(DE) Airzone-Ionisator
(DE)Feinstaubsensor
(DE) Hauptsteuerplatine
(DE) Steuerungs-Gateway
(DE) Innengerät

3
EN
Environmental Policy
• Never dispose of this equipment with household waste. Electrical and electronic
products contain substances that can be harmful to the environment if not
properly handled. The crossed-out waste bin symbol indicates separate collection
of electrical devices, which must be separated from other urban waste. For correct
environmental management, at the end of its useful life the equipment should be
taken to the collection centers provided for this purpose.
• The parts that make it up can be recycled. Therefore, please respect the regulations
in force regarding environmental protection.
• If you replace the equipment, the original equipment must be returned to your
dealer or deposited at a specialized collection center.
• Violations are subject to the penalties and measures stipulated in environmental
protection law.

4
EN
• The system must be installed by a qualified technician.
• This product must not be modified or disassembled under any circumstances.
• Do not handle the system with wet or damp hands.
• In the case of any malfunction of this appliance, do not repair it yourself. Contact the
sales distributor or service dealer for repair or disposal of the product.
• Check that the HVAC installation has been installed according to the manufacturer's
requirements, complies with local regulations in force and is working correctly
before you install the Airzone system.
• Place and connect the elements in your installation in accordance with current
regulations covering electrical installations.
• All connections must be made with the power supply completely turned off.
• Take care not to short circuit any of the system's connections.
• Please refer carefully to the wiring diagram and these instructions when wiring.
• Connect all wiring securely. Loose wiring may cause overheating at the connection
points and is a possible fire hazard.
• Do not locate the Airzone communication bus close to power lines, fluorescent
lights, actuators, etc. as this may cause interference in communications.
• The connection to the external power supply must include a main switch or other
method of disconnection that includes a constant separation for all polarities,
in accordance with appropriate local and national regulations. The system will
Before Starting
automatically restart if the power supply is turned off. Use separate circuits for the
unit that is to be controlled and the power supply to the system.
• Check the polarity of each device's connectors. A wrong connection can seriously
damage the product.
• To connect to the system, use Airzone cable: four-wire cable (2x0.22 mm2twisted
shielded wires for data communications and 2x0.5mm2wires for power supply).
• A Blueface thermostat must be used to enable all the Airzone system functionalities.
• Recommendations for the placing of the thermostats:
• For equipment using R32 refrigerant, verify the compliance with the local
refrigerant regulation.
• The room size installation requirements mentioned in the manual of the ducted
indoor unit, to which the Easyzone is connected, remain applicable to each and
every separate room served by the Airzone unit.
• Ducts connected to Easyzone shall not contain a potential ignition source.

5
EN
Elements and Installation
MAIN CONTROL BOARD (AZCE6CB1IAQ)
Assembly
Connection
The system's main control board is already installed in the plenum.
AI1
DI1
O1
O2
AZ1 AZ2 AZ3
N L
IAQ SW1
IU DM1
IO1
IO2
IO3
IO4
IO5
IO6
IO7
IO8
ON/OFF MODULE
P3
For further information, see the technical fact sheet.
To connect the Airzone connection bus, there are three 5-pin terminals. This system allows star
and bus connection. Use 2x0.5+ 2x0.22mm2Airzone cable. Fix the cables with the screws on
the terminal, following the color code.
Important: For elements with external power supply at 110/230 VAC, it is only necessary to
connect poles "A" and "B" of the bus for communications.
For increased safety, fix the cables to the main control
board using the turrets:
AZ1 - AZ2 - AZ3
The Airzone connection bus is used to connect all the internal elements independent of the
main control board and can control up to 8 zones.
Important: If you have a Flexa 4.0
system, you have the option of
incorporating a zone On/Off control
module (AZCE6ACCOFF) on the
main control board.
For further information on the On/
Off module, see the technical fact
sheet.

6
EN
SW1
The system main control board has wireless
communication for connecting wireless Airzone
elements. These devices are associated by opening
the association channel on the main control board.
To do this, press SW1 until LED D19 turns red.
For 15 minutes, the system will keep the wireless
association channel open.
Reset system: If you need to reset the system to
factory defaults, press and hold SW1 until LED D19
stops blinking.
D18
D19
D10
SW1
DM1
The automation bus allows several systems to be interconnected in order to manage all of
them, using the control peripherals offered by Airzone or their integration into a higher-level
control network.
To connect the automation bus, there is one 5-pin terminal.
This system only uses bus connections. Fix the cables with the
screws on the terminal, following the color code.
Important: For elements with external power supply at 110/230
VAC, it is only necessary to connect poles "A", "B" and "Shield" of
the communications bus. Only use the shield on the connector
on the main control board side.
IU
The communication gateway/controller gateway will already be connected to the system's
main control board at the port. For more information, refer to your gateway's data sheet.
IO1...IO8
Connection outputs to ionizers and actuators. Factory connected.
DI1
This input sets the Stop mode on the AC unit, closing all system dampers when an alarm
warning is received and blocking the operation mode. This input is configured as normally
closed. For proper system operation, this contact is shipped with a bridge from the factory.
AI1
Allows the return temperature of an AC unit to be measured by means of an external probe.
The use of this probe is recommended when working with electromechanical or NON Inverter
units, where the return temperature of the AC unit must be controlled.
P3
Antenna connection for wireless elements.

7
EN
O2
This output can be configured for the control of controlled mechanical ventilation units (CMV)
or for the management of a boiler (see Advanced settings section on the Blueface thermostat -
System parameters).
O1
This output is designed for the Stop-Start of AC units, in the event that only this type of control
is required. The operation logic of this output is as follows:
• CMV configuration
Status Stop Ventilation Cooling Air heating Radiant heating
Demand ON OFF ON ON ON ON
Demand OFF OFF ON ON ON ON
Status Stop Ventilation Cooling Air heating Radiant heating
Demand ON OFF ON ON ON OFF
Demand OFF OFF OFF OFF OFF OFF
• Boiler configuration
Status Stop Ventilation Cooling Air heating Radiant heating
Demand ON OFF OFF OFF OFF ON
Demand OFF OFF OFF OFF OFF OFF
The technical characteristics of the CMV/Boiler relays are Imax 1 A at 24-48 V voltage free.
To control higher power elements, the use of contactors of the power to be controlled is
recommended.
The technical characteristics of the Stop-Start relays are Imax 1 A at 24-48 V voltage free.
To control higher power elements, the use of contactors of the power to be controlled is
recommended.
N L
This connector supplies power to the system main control board and consequently to the
elements connected to it. External power supply at 110/230VAC.
To supply power to the system's main control board, loosen the cable gland if necessary and
insert the cable through the hole (Ø5-10 mm). Then attach the cables to the terminal following
the polarity indicated. Connect the terminal to the power supply input and tighten the cable
gland to attach the power supply cable.

8
EN
The connection to the external power supply must include a main switch or other
method of disconnection that includes a constant separation for all polarities,
in accordance with appropriate local and national regulations. The system will
automatically restart if the power supply is turned off. Use separate circuits for the
unit that is to be controlled and the power supply to the system.
Once all the connections have been made,
make sure the cover of the main control
board is correctly replaced.
TEMPERATURE PROBE (AZX6SONDPROTEC)
For further information, see the technical fact sheet.
Connects to the temperature probe (AI1) connector. Protects the AC unit from the water
returning to the boiler.

9
EN
CONTROL MODULE OF RADIANT ELEMENTS (AZCE6OUT-
PUT8)
Assembly
Connection
This device is DIN rail mounted. This module is externally powered at 110/230 VAC. The location
and assembly of this module must comply with current electronic regulations.
The control module of radiant elements is a device that is connected to the Airzone connection
bus on the main control board.
The operation of the relays is
indicated as follows:
OX = demand of the radiant
element in zone X.
Note: To remove the module, pull the tab
downwards to release it.
For further information, see the technical fact sheet.
The characteristics of the control relays are Imax 10 A at 110/230 VAC voltage free.
To control higher power elements, the use of contactors of the power to be controlled is
recommended. Remember to connect the neutral directly from the circuit to the element to
be controlled.
For connection to the Airzone connection bus on the
main control board , there is one 5-pin terminal.
Fix the cables with the screws on the terminal,
following the color code.
Relay status
LEDs

10
EN
The power connection to the module is via a 3-pin terminal
. Fix the cables with the screws on the terminal, following the
polarity.
Once powered, the control module of radiant elements
performs a sequential opening and closing of all relay outputs.
This operation is repeated once a week to ensure correct
operation of the valves.
The connection to the external power supply must include a main switch or other
method of disconnection that includes a constant separation for all polarities,
in accordance with appropriate local and national regulations. The system will
automatically restart if the power supply is turned off. Use separate circuits for
the unit that is to be controlled and the power supply to the system.

11
EN
WIRED THERMOSTAT
Assembly
Elements
Connection
Airzone wired thermostats are surface mounted on a
support. Remember that the maximum recommended
distance for this device is 40 meters. For wall mounting,
follow these steps:
• Separate the back of the thermostat and make the
relevant connections.
• Fix the back of the thermostat to the wall.
• Place the display over the fixed support.
• Place the anti-vandalism rods to better hold the
thermostat in place (optional).
Airzone thermostats are elements that are
connected to the Airzone connection bus on
the main control board. Fix the cables with
the screws on the terminal, following the color
code.
Important: Use the tool provided to press on
the fastening tabs.
Main control board connection
Thermostat connection
AZCE6BLUEFACEC
For further information, see the technical fact sheet.
AZCE6THINKC
For further information, see the technical fact sheet.
AZCE6LITEC
For further information, see the technical fact sheet.
Press

12
EN
WIRELESS THERMOSTATS
Assembly
Airzone wireless thermostats are surface mounted on a
support. Remember that the maximum recommended
distance for this device is 40 meters.
• Remove the back of the thermostat and insert the
CR2450 button battery.
• Fix the back of the thermostat to the wall.
• Place the display over the fixed support.
• Place the anti-vandalism rods to better hold the
thermostat in place (optional).
Note: If you wish to change the battery, please see the user’s manual.
Elements
AZCE6THINKR
For further information, see the technical fact sheet.
AZCE6LITER
For further information, see the technical fact sheet.

13
EN
AIRZONE CONTROL GATEWAY-3 SPEED FANCOIL (AZX6FANCOILZ)
Elements
Assembly
No. Description
Cooling air demand
Speed 1
Speed 2
Speed 3
Heating air demand
Power supply
AC unit bus
This device is DIN rail or wall mounted. This module is externally powered at 110/230 VAC. The
location and assembly of this module must comply with current electronic regulations.
Mounted on wallMounted using DIN rail
Note: To remove the module on DIN rail, pull the tab downwards to release it.
For further information, see the technical fact sheet.

14
EN
4-pipe installation
F-Coil
N
L
V1
V2
Y
V3
W
WV3Y OV1 V2
O O O O
2-pipe installation
Connection
F-Coil
V1
WV3Y OV1 V2
O O O O
V2
V3
W-Y
N
L
For connection to the main control board AC unit bus there is one
4-pin terminal. Fix the cables with the screws on the terminal, following
the color code. Only use the shield on the connector on the main control
board side.
The power connection to the module is via a 3-pin terminal. Fix the
cables with the screws on the terminal, following the polarity.
The connection to the external power supply must include a main switch or other
method of disconnection that includes a constant separation for all polarities,
in accordance with appropriate local and national regulations. The system will
automatically restart if the power supply is turned off. Use separate circuits for
the unit that is to be controlled and the power supply to the system.
The characteristics of the control relays are Imax 10 A at 110/230VAC voltage
free. To control higher power elements, the use of contactors of the power to be controlled is
recommended.

15
EN
AIRZONE CONTROL GATEWAY-0-10V FANCOIL (AZX-
6010VOLTSZ)
Elements
Assembly
No. Description
Cooling air demand
Heating air demand
Ventilation demand
Control of fan
Power supply
AC unit bus
This device is DIN rail or wall mounted. This module is externally powered at 110/230 VAC. The
location and assembly of this module must comply with current electronic regulations.
Mounted on wallMounted using DIN rail
Note: To remove the module on DIN rail, pull the tab downwards to release it.
For further information, see the technical fact sheet.

16
EN
4-pipe installation
+
-
W
Y
LF-Coil
N
0 Y 0 W 0 ON/OFF
2-pipe installation
Connection
+
-
W-Y
LF-Coil
N
0 Y 0 W 0 ON/OFF
The characteristics of the control relays are Imax 10 A at 110/230VAC voltage free.
To control higher power elements, the use of contactors of the power to be controlled is
recommended.
For connection to the main control board AC unit bus there is one
4-pin terminal. Fix the cables with the screws on the terminal, following
the color code. Only use the shield on the connector on the main control
board side.
The power connection to the module is via a 3-pin terminal. Fix the
cables with the screws on the terminal, following the polarity.
The connection to the external power supply must include a main switch or other
method of disconnection that includes a constant separation for all polarities,
in accordance with appropriate local and national regulations. The system will
automatically restart if the power supply is turned off. Use separate circuits for
the unit that is to be controlled and the power supply to the system.
This manual suits for next models
16
Table of contents
Other Airzone Fan manuals
Popular Fan manuals by other brands

Ebmpapst
Ebmpapst W2G107-AD03-02 operating instructions

Ebmpapst
Ebmpapst S4E350-ZD02-01 operating instructions

Gulf Coast Fans
Gulf Coast Fans 4YU26 owner's manual

Ebmpapst
Ebmpapst A4E350-AF20-05 operating instructions

Ebmpapst
Ebmpapst D4E225-CC07-37 operating instructions

AAF
AAF AstroFan EC FFU Installation, operation and maintenance manual