manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Akse
  6. •
  7. Measuring Instrument
  8. •
  9. Akse Electrex D6 RS485 User manual

Akse Electrex D6 RS485 User manual

INSTALLATION GUIDE
Further documentation may be downloaded from our web site www.electrex.it.
This document is owned by company AKSE that reserves all rights.
DECLARATION OF CONFORMITY
Akse hereby declares that its range of products complies with the following directives EMC
2014/30/EU, 2014/35/EU and complies with the following product’s standard CEI EN
61326 - Ed. 2.0 (2012) – IEC 61326 - Ed. 2.0 (2012) CEI EN 61010 Ed. 3 (2010) – IEC
61010 Ed. 3 (2010). The product has been tested in the typical wiring confi guration and
with peripherals conforming to the EMC directive and the LV directive.
COPYRIGHT
Electrex is a trademark of Akse S.r.l. All rights reserved.
It is forbidden to duplicate, adapt, transcript this document without Akse written
authorization, except when regulated accordingly by the Copyright Laws.
WARRANTY
This product is covered by a warranty against material and manufacturing defects for a 24
months period from the manufacturing date.
The warranty does not cover the defects that are due to:
• Negligent and improper use
• Failures caused by atmospheric hazards
• Acts of vandalism
• Wear out of materials
• Firmware upgrades
Akse reserves the right, at its discretion, to repair or substitute the faulty products
The warranty is not applicable to the products that will result defective in consequence of
a negligent and improper use or an operating procedure not contemplated in this manual.
RETURN AND REPAIR FORMALITIES
Akse accepts the return of instruments for repair only when authorized in advance. The
transport costs are at customer charge.
RE-SHIPPING OF REPAIRED PRODUCT
The terms for re-shipment of repaired products are ex-works, i.e. the transport costs are
at customer charge.
Products returned as detective but found to be perfectly working by our laboratories, will
be charged a fl at fee to account for checking and testing time irrespective of the warranty
terms.
SAFETY
This instrument was manufactured and tested in compliance with IEC 61010-1 CAT III -
300V class 2 standards for operating voltages up to 300 VAC rms phase to neutral.
In order to maintain this condition and to ensure safe operation, the user must comply with
the indications and markings contained in the following instructions:
• When the instrument is received, before starting its installation, check that it is
intact and no damage occurred during transport.
• Before mounting, ensure that the instrument operating voltages and the mains
voltage are compatible then proceed with the installation.
• The instrument power supply needs no earth connection.
• The instrument is not equipped with a power supply fuse; a suitable external
protection fuse must be foreseen by the contractor.
• Maintenance and/or repair must be carried out only by qualifi ed, authorized
personnel
• If there is ever the suspicion that safe operation is no longer possible, the instrument
must be taken out of service and precautions taken against its accidental use.
Operation is no longer safe when:
• There is clearly visible damaged.
• The instrument no longer functions.
• After lengthy storage in unfavorable conditions.
• After serious damage occurred during transport
The instruments must be installed in respect of all the local regulations.
OPERATOR SAFETY
Warning: Failure to observe the following instructions may lead to a serious danger of
death.
• During normal operation dangerous voltages can occur on instrument terminals and
on voltage and current transformers. Energized voltage and current transformers
may generate lethal voltages. Follow carefully the standard safety precautions while
carrying out any installation or service operation.
• The terminals of the instrument must not be accessible by the user after the installation.
The user should only be allowed to access the instrument front panel where the
display is located.
• Do not use the digital outputs for protection functions nor for power limitation functions.
The instrument is suitable only for secondary protection functions.
• The instrument must be protected by a breaking device capable of interrupting both
the power supply and the measurement terminals. It must be easily reachable by the
operator and well identifi ed as instrument cut-off device.
• The instrument and its connections must be carefully protected against short-circuit.
Precautions: Failure to respect the following instructions may irreversibly damage to the
instrument.
• The outputs and the options operate at low voltage level; they cannot be powered by
any unspecifi ed external voltage.
• The application of currents not compatible with the current inputs levels will damage
to the instrument.
Keep pressed for 2
seconds to display:
- Type of instrument
- Firmware version
- Serial number
- RS485 address
MEASURE LIST TABLE
(The parameters available vary according to instrument confi guration)
Long keypress
U I P Ea + MAIN t LIFE
U Min I Max P ∑ Ea - MAIN t MAIN
U Max I AVG P Avg Imp Ea Phase t P1
P Avg Exp Ea + Phase t P2
P MD Imp Ea - Phase t P3
P MD Exp Ea + P1
Ea - P1
Ea + P2
Ea - P2
Ea + P3
Ea - P3
LEGEND OF PARAMETERS AND SYMBOLS
UVoltage L-N Phase - Neutral reference
ICurrent L-L Phase - Phase reference
PActive Power THD Total Harmonic Distortion
QReactive Power Min Minimum values (10 cycles time base)
SApparent Power Max Maximum values (10 cycles time base)
PF Power Factor Avg Average value
Ea Active Energy MD Maximum Demand
Er Reactive Energy ∑ / MAIN Value (total)
Es Apparent Energy PValue (partial)
LInductive tTime counting
CCapacitive LIFE Operating time
Imp / + Imported value
Exp / - Exported value
READINGS
MODELS
PFN66-H0509-110, PFN66-H0509-A10, PFN66-H0W09-110, PFN66-H0709-0M0
MECHANICAL CHARACTERISTICS
Case Self-extinguishing plastic material class V0
Protection degree IP40 on front panel, IP20 terminals side
Size 105 x 90 x 58 mm (6 DIN modules)
VOLTAGE INPUT
Direct insertion Up to 300 V
max. 360 V
Aux. power supply 85÷265Vac +/- 10% 50/60Hz
Self consumption: < 2,5VA
SETUP SEQUENCE
PAGE PARAMETERS VALUES AVAILABLE DEFAULT
PASSWORD
PASSWORD 0000 ... 9999 0000
MEAS-A Note n.1
NET 3PH-4W, 2PH-2W, 1PH-2W,
3PH-3W-2C 3PH-4W
EXPORT IMP / EXP EXP
CT 10000 / 500 500/500
VT 400000/300 1/1
MEAS-B Note n.2
I AVG 1...60 (minutes) 8
P AVG 1...60 (minutes) 15
RS485-A Note n.3
MODE SLAVE, MASTER SLAVE
TOUT 100...10000 (ms) 3000
RETR 0...9 3
RS485-B
ADDR (485 address) 1 ... 247 247
COM1 (Baud rate) 2400, 4800, 9600, 19200,
38400 38400
COM1 (Data Bit) 7 or 8 8
COM2 (Parity) N = no parity, E = even parity,
O = odd parity N
COM (Stop bit) 1 or 2 2
S.T. (Silent Time) 0 ... 1000 mS (Step of 10) 100
ETH Note n.4
DHCP N, Y N
IP xxx.xxx.xxx.xxx 192.168.027.001
NETM xxx.xxx.xxx.xxx 255.255.255.000
GWAY xxx.xxx.xxx.xxx 127.000.000.001
WIFI Note n.4
DHCP N, Y N
IP xxx.xxx.xxx.xxx 192.168.026.001
NETM xxx.xxx.xxx.xxx 255.255.255.000
GWAY xxx.xxx.xxx.xxx 127.000.000.001
NET Note n.5
DEF ETH, WIFI ETH
ETH N, Y Y
WIFI N, Y Y
LCD Note n.6
DIM DISABLE, ENABLE DISABLE
TIME 1...90 (sec) 3
LIGHT 300...1000 500
PULSE DISABLE, ENABLE ENABLE
ALARM 1 / A Note n.7
MODE NORMAL, 1-OF-3, 3-OF-3,
UNBAL%, DERIV, UNBAL NORMAL
TYPE MIN, MAX MAX
MEAS (note n.5) Controlled measure. See table
n.1 for register selection 000
THRE (note n.5) Threshold value +000.000
ALARM 1 / B Note n.8
HYST 0...99 (%) 05
DEL 0...99 / S,M / 0...99 / S,M 01 / S / 01 / S
AVG 0...99 (sec) 05
OUT NORMAL, PULSE-S, PULSE-L,
HOLD NORMAL
ALARM 2 / A (see ALARM 1/A)
ALARM 2 / B (see ALARM 1/B)
ALARM 3 / A (see ALARM 1/A)
STAT
The “STAT” page shows the assigned IP address of the LAN and WI-FI port (if present)
ALARM 3 / B (see ALARM 1/B)
ALARM 4 / A (see ALARM 1/A)
ALARM 4 / B (see ALARM 1/B)
CHANGE PWD
PWD 0000...9999 0000
DEVICE SETUP
ENTER THE SETUP EXIT THE SETUP
Push for
2 seconds
Push for
2 seconds
Using the keys
or
select SET
from the menu
Push the key
DESCRIPTION OF KEYS
Short keypress Long keypress Short keypress Long keypress
Confi rm parameter Setup confi rmation Go to previous value Go to previous page
Modify parameter Go to next value Go to next page
Modify parameter Exit without saving
the confi guration
NOTE n.1
NET 3PH-3W-2CT 2 phases 3 wires, Triangle
3PH-4W 3 phases 4 wires, Star
2PH-2W 2 phases 2 wires, Bi-phase
1PH-2W 1 phase, 2 wires, Single phase
3I 3 phases
CT Primary / Secondary of the current transformer (CT)
VT Primary / Secondary of the voltage transformer (VT)
NOTE n.2
P AVG Integration time for Power of the average value (AVG) and peak value (MD)
I AVG Integration time for Current of the average value (AVG) and peak value (MD)
NOTE n.3
MODE SLAVE RS485 port set as Slave of the network.
MASTER RS485 port set as Master of the network.
TOUT Predetermined time in which a given operation must be
terminated
RETR Number of communication attempts on the RS485 port
NOTE n.4
DHCP Enable / Disable the search for a DHCP server in the network
IP IP address of the network interface
NETM Subnet mask: defi nes the belonging range of a host within an IP
subnetwork
GWAY IP address of the gateway
NOTE n.5
DEF Selects the default network interface to be used for the communication
ETH Enable / Disable the Ethernet (LAN) port
WIFI Enable / Disable the WIFI port
NOTE n.6
DIM Enable / Disable dimming of the display
TIME Time in seconds after which the display luminosity is reduced. (With DIM
enabled)
LIGHT Luminosity level of the display
PULSE Enable / Disable the fl ashing of the sine wave symbol light near the
Electrex logo.
NOTE n.7
MODE NORMALE Classic Alarm with reference to a fi xed threshold or to
maximum and minimum delay and applicable hysteresis.
“AVG” parameter is not used.
1-OF-3 Considers also the 2 following registers of the selected one
in “MEAS”. It operates on a fi xed max or min threshold with
delay and applicable hysteresis. If one of the three registers
exceeds the threshold the alarm goes ON. “AVG” parameter
is not used.
3-OF-3 Considers also the 2 following registers of the selected one
in “MEAS”. It operates on a fi xed max or min threshold with
delay and applicable hysteresis. When all the three registers
exceed the threshold the alarm goes ON. “AVG” parameter
is not used.
DERIV “THRE” parameter becomes a % value, “AVG” parameter
is used. The instant value applied to the alarm on “MEAS”
is compared with its value mediated obtained on the basis
of the time set on “AVG”. When the instantaneous value
combined alarm diff ers in more (setting “Max”) or less (setting
“MIN”) from the average value (“ AVG “) of the percentage
set on “THRE” the alarm goes on. With delay and applicable
hysteresis.
UNBAL Considers also the 2 following registers of the selected one
in “MEAS”. “THRE” parameter becomes a % value. Alarm
goes on when one of the three register is diff erent from the
percentage set on “THRE” comply with the higher value of the
three read register if “MAX” is set on “TYPE”, or comply with
the lower value of the three register if “MIN” is set on “TYPE”
With delay and applicable hysteresis.
TYPE MAX Alarm setting in excess or in decrease compared with the
predefi ned conditions.
With the exception of “UNBAL and UNBAL%”.
MIN
MEAS Indicates which register (measure) the alarm is related to.
See table N.1 Input Register.
THRE Alarm threshold in absolute value, with the exception made
for “DERIV” and “UNBAL” in which the value inserted be-
comes a percentage.
NOTE n.8
HYST Hysteresis, ie the cycle between alarm value and alarm
return value. It is a particularly useful function to avoid
unwanted oscillations and / or alarms. Example: Alarm on
current set at 100 A Max with 5% hysteresis. The alarm is
activated at 100 A and is deactivated at 95 A
DEL Delay time (between 1 sec and 99 min) for activation.
Delay time (between 1 sec and 99 min) for deactivation.
AVG Parameter to be used in “DERIV” mode only. Moving window
width (in secs) used to create a reference value with which
to compare the instantaneous data
OUT NORMAL Alarm remains active during the duration of the event. It
restores automatically.
HOLD Alarm remains active until the manual reset via Modbus.
PULSE-L Generates a 500ms impulse when the alarm goes on.
PULSE-S Generates a 100ms impulse when the alarm goes on.
DIP FUNCTION SLAVE MASTER *
1 Line termination resistance (120 Ohm) OFF ON
2 Fail safe resistance B (-) OFF ON
3 Fail safe resistance A (+) OFF ON
4 Not used OFF OFF
* with RS-485 Master PUK activated
LAN 10/100 ETHERNET PORT
DIP-SWITCH CONFIGURATION
EXPBUS PORT
The instrument is equipped with a Ethernet Lan 10/100 Auto-MDI/MDIX
port.
For the connection can be used a data cable straight or crossover.
Note: the port is not a PoE (Power over Ethernet = device power supply
via the Lan port) type. The connection of the device to a PoE port is
anyway accepted. The power supply anyway must be always provided
by an external power supplier.
The ExpBus port, confi gurable via Ethernet port on web pages:
- uses a multicast communication rated at 250kb/sec with collision
management
- max cable length : 10 meters
- manages up to 16 modules (but technically can manage up to 126)
- uses the UTP cable, 4 wires used:
2 for the power supply at 9 Vdc
2 for the bidirectional communication
The modules will also power supply the ExpBus port
The cable must be connected in in-out modality (multidrop) as per the
RS485 Bus.
Use cables with max cross-section of 2,5 mm2 if stranded, 4 mm2 if rigid and connect them
to the terminals marked VOLTAGE INPUT on the instrument according to the applicable
diagrams that follow.
VOLTAGE CONNECTION CURRENT CONNECTION
Use only the CTs supplied with the instrument. Connect the CTs to the terminals marked
with I1, I2, I3, I4 (current input) according to the diagrams.
N.B. Failure to comply with the connection diagrams results in measurement errors. Do
not extend the CT cables.
The instrument is equipped with a separate power supply. The power supply terminals
are numbered (17) and (18). Use cables with max cross-section of 2,5 mm2 if stranded,
4 mm2 if rigid.
POWER SUPPLY
SERIAL LINE CONNECTION
POWER SUPPLY
1 85/265Vac +/- 10% 50/60Hz
2 F: 500 mA T
Max cable length: 1000 meters.
RS485
Address 27
Baud rate 38400
Parity None
Bit of Stop 2
MESSAGE “CFG ERROR”
During the set up operation a “CFG ERROR” message could appear. This means that
some wrong parameters are typed.
Subject to modifi cation without notice.
Edition 2019 01 28 ENG0147

This manual suits for next models

6

Other Akse Measuring Instrument manuals

Akse Electrex FEMTO D4 70A PFA6431-02 User manual

Akse

Akse Electrex FEMTO D4 70A PFA6431-02 User manual

Akse X3M Instruction Manual

Akse

Akse X3M Instruction Manual

Akse Electrex 96 RS485 User manual

Akse

Akse Electrex 96 RS485 User manual

Popular Measuring Instrument manuals by other brands

Hioki FT3432 instruction manual

Hioki

Hioki FT3432 instruction manual

ColorVision Spyder2 Plus quick start guide

ColorVision

ColorVision Spyder2 Plus quick start guide

Xylem YSI Alyza IQ NH4 Operation manual

Xylem

Xylem YSI Alyza IQ NH4 Operation manual

Bushnell 1K owner's guide

Bushnell

Bushnell 1K owner's guide

Pulsar MDot instruction manual

Pulsar

Pulsar MDot instruction manual

3nh YG Series Operation manual

3nh

3nh YG Series Operation manual

SRM ORIGIN PowerMeter user guide

SRM

SRM ORIGIN PowerMeter user guide

Endress+Hauser Liquicap M FMI52 PFM operating instructions

Endress+Hauser

Endress+Hauser Liquicap M FMI52 PFM operating instructions

Jolly logic ALTIMETERTWO quick start

Jolly logic

Jolly logic ALTIMETERTWO quick start

Amprobe VPC-10 instruction manual

Amprobe

Amprobe VPC-10 instruction manual

Endress+Hauser Proline Promass E TB2 HART operating instructions

Endress+Hauser

Endress+Hauser Proline Promass E TB2 HART operating instructions

LINOVISION IOT-S300AP product manual

LINOVISION

LINOVISION IOT-S300AP product manual

Bosch GLM 50 Professional Original instructions

Bosch

Bosch GLM 50 Professional Original instructions

Apogee 2349 DLTM4 instructions

Apogee

Apogee 2349 DLTM4 instructions

Palstar PM2000AM Technical manual

Palstar

Palstar PM2000AM Technical manual

TSI Incorporated velocicalc 9545 Operation and service manual

TSI Incorporated

TSI Incorporated velocicalc 9545 Operation and service manual

Dent ELITEpro XC Operator's guide

Dent

Dent ELITEpro XC Operator's guide

Megger MPQ1000 Getting started

Megger

Megger MPQ1000 Getting started

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.