Aktek AFLO User manual

USER’S GUIDE
Installation & Operation
Instructions
Electromagnetic Flow Meter
Model ALIT-BT

AFLO-Electromagnetic Flow Meter
1

AFLO-Electromagnetic Flow Meter
2
INDEX
1.Introduction…………………………………………………………………………………………….3
1.1. Sensor……………………………………………………………………………………………………………………....3
1.2. Transmitter………………………………………………………………………………………………………………..4
2. Technical Specifications………………………………………………………………………….4
3. Technical Drawings ……………………………………………………………………………… 5
4. Wiring ……………………………………………………………………………………………………7
4.1. Compact type Terminal …………………………………………………………………………………………….……7
4.2. Remote type Terminal ……………………………………………………………………………………………………9
5. Digital outputs……………………………………………………………………………………..12
6. Operating…………………………………………………………………………………………….13
6.1.Compact Transmitter Display …………………………………………………………………………………….…13
6.2.Remote Transmitter Display ……………………………………………………………….…………………..……13
6.3. Keys Functions…………………………………………………………………………………………………….….….14
6.4. Functions select menu………………………………………………………………………………………….……..14
6.5. Parameters Configuration ………………………………………………………………………………………..….14
6.5.1.Passwords………………………………………………………………………………………………….…….…16
6.5.2. Details Parameters ……………………………………………………………………………………………16
6.6. Alarm information ……………………………………………………………………………………………………….21
7. Troubleshooting .………………………………………………….……………………………..21
7.1. No display…………………………………………………………………………………………………………………...21
7.2. Exciting alarm ……………………………………………………………………………………………………………..21
7.3.Empty pipe alarm………………………………………………………………………………………………………….22
8. MOUNTING CONDITIONS.......................................................................22
9. SHIPPING AND STORAGE CONDITIONS…………………………………………………23

AFLO-Electromagnetic Flow Meter
3
1. Introduction
AFLO electromagnetic flowmeters offer reliable, precise and inexpensive flow measurement on all
electrically conductive liquids. Typical applications are found in all industries. E.g.:
Water sector: Potable water, treatmentof chemicals,waste waterand sludge.
Food sector:Dairyproducts,beer, wine,soft-drinks andfruit juices.
Chemicalsector:Detergents,pharmaceuticals,acids andalkalies.
Other sectors:Districtheating,paperpulpandminingslurries.
The flow measuring principle is based on Faraday’s law of electromagnetic induction.
Figure (1)
Ui = Whenan electricalconductoroflengthL is moved atvelocity v, perpendiculartothelines of
flux through a magneticfieldof strengthB, the voltage Ui is inducedatthe ends of the conductor
Ui = L x B x v
Ui = Induced voltage
L = Conductorlength= Inner pipediameter= k1
B = Magnetic fieldstrength= k2
v = Velocity of conductor(media)
k = k1 x k2
Ui = k x v, the electrode signal is directly proportional to the fluid velocity
1.1.SENSOR
The sensorconverts theflow into anelectricalvoltage (Ui) proportionaltothe velocity ofthe flow.
The sensoris builtupof a stainlesssteelpipe,2coils,electrodes,anisolatingliner,housing and
where applicable,connectingflanges.

AFLO-Electromagnetic Flow Meter
4
1.2.TRANSMITTER
The transmitter consists ofanumberof function blocks whichconvert the sensorvoltageintoflow
readings.
Figure (2)
2. Technical Specifications
Transmitter
Fluid conductivity
≥5 μS / cm
Accuracy
±0.5%
Keypad
4 controlbuttons
Ambient Temperature
-20…+60 ˚C
Output
0-10mA, 4-20mA, Frequency, Pulse
Communication
RS485 MODBUS
Display
3 Lines LCD
PowerSupply
85…250 VAC 45…63Hz 20W,
20…36 VDC or battery powered
Protection
IP67
Totalizer
Forward, reverse andnet totalizer
Sensor
Nominal Size mm
DN10…DN3000
Nominal Pressure
PN6,10,16,25,40
Liner
Neoprene,PTFE, FEP, HardRubber,Polyurethane
Electrodes
AISI 316LSt. St., Hastelloy,Titanium,Tantalum,Platinum-Iridium
Operating temperature
-20...+80 °C (hard rubber) -20...+120 °C (with Teflon and awayfrom the
transmitterinstallation)
Measuring Tube
Stainless steel
Body Material
CarbonSteel
Protection
IP 67/ IP 68(for remoteversion)

AFLO-Electromagnetic Flow Meter
5
3. Technical Drawings
Figure (3)
Figure (4)

AFLO-Electromagnetic Flow Meter
6
Dimensions according to Nominal Pressure Value for Remote and Compact Type
Figure (5)
DN
Dimensions(Pressure 1.6MPa)
Dimensions(Pressure 4.0MPa)
L
H
Weight
Kg
D
d1
d0
n
b
D
d1
d0
n
b
15
95
65
14
4
16
95
65
14
4
16
200
160
13
20
105
75
14
4
18
105
75
14
4
18
200
167
13
25
115
85
14
4
18
115
85
14
4
18
200
169
13
32
140
100
18
4
18
140
100
18
4
18
200
185
13
40
150
110
18
4
20
150
110
18
4
20
200
193
15
50
165
125
18
4
20
165
125
18
4
20
200
206
16
65
185
145
18
4
20
185
145
18
4
22
250
224
20
80
200
160
18
8
22
200
160
18
8
22
250
241
22
100
220
180
18
8
22
235
190
22
8
26
250
263
25
125
250
210
18
8
22
270
220
26
8
26
250
295
33
150
285
240
22
8
24
300
250
26
8
28
300
325
36
DN
Pressure 1.6 Mpa
Pressure 1.0MPa
200
340
295
22
12
26
340
295
22
8
24
350
383
46
250
405
355
26
12
28
395
350
22
12
26
450
440
65
300
460
410
26
12
32
445
400
22
12
28
500
498
75
350
520
470
26
16
35
505
460
22
16
30
500
553
100
400
580
525
30
16
38
565
515
26
16
32
500
608
160
450
640
585
30
20
42
615
565
26
20
35
550
665
170
500
715
650
33
20
46
670
620
26
20
38
550
727
210
600
840
770
36
20
52
780
725
30
20
42
600
840
240
DN
Pressure 1.0 MPa
Pressure 0.6MPa
700
895
840
30
24
30
860
810
26
24
26
700
895
270
800
1015
950
33
24
32
975
920
30
24
26
800
1002
900
1115
1050
33
28
34
1075
1020
30
24
26
900
1107
1000
1230
1160
36
28
34
1175
1120
30
28
26
1000
1222
1200
1405
1340
33
32
28
1200
1437
1400
1630
1560
36
36
32
1400
1663
1600
1830
1760
36
40
34
1600
1863
1800
2045
1970
39
44
36
1800
2072
2000
2265
2180
42
48
38
2000
2282
2200
2475
2390
42
52
42
2200
2487
2400
2685
2600
42
56
44
2400
2636
2600
2905
2810
48
60
46
2600
2836
2800
3115
3020
48
64
48
2800
3036
3000
3315
3220
48
68
50
3000
3236

AFLO-Electromagnetic Flow Meter
7
4. Wiring
4.1.Compact type Terminal
Figure (6)
I+: Output Current for Flow Measurement G: RS232 Communication Ground
COM:Output Current (Ground) for Flow Measurement L1:220V(24V)Power Supply
P+:Frequency(Pulse) Output for Bi-directional Flow L2:220V(24V)Power Supply
COM:Frequency (Pulse) Output (Ground)
AL:Alarm Output for Low Limit
AH:Alarm Output for Upper Limit
COM:Alarm Output (Ground)
FUSE:Fuse for Power Supply
T+: +Communication Input Signal(RS485-A)
T-: -Communication Input Signal(RS485-B)

AFLO-Electromagnetic Flow Meter
8
Signal lines labels in compact type
Figure (7)
White twisted-pair cable (for exciting current)
12 Conductors (Red)
12 Conductors (Black)
Grey shielded twisted-pair cable
10 Conductors (Red) connected to “Signals 1”
13 Conductors (White) connected to “Signals 2”
Shielded Conductor connected to “Signal Ground”

AFLO-Electromagnetic Flow Meter
9
4.2.Remote type Terminal
Figure (8)
SIG 1 Signal 1
SGND Signal Ground
SIG 2 Signal 2
DS1 Shielded Exciting 1
DS2 Shielded Exciting 2
EXT+ Exciting Current+
EXT- Exciting Current-
VDIN Current two lines 24V Spots
ICOUT Analog Current Output
ICCOM Analog Current Output Ground
POUT Flow Frequency (Pulse) Output
PCOM Frequency (Pulse) Output Ground
ALMH Upper Limit Alarm Output
ALML Low Limit Alarm Output
ALCOM Alarm Output Ground
TRX+ Communication Input (RS485-A)
TRX- Communication Input (RS485-B)
TCOM 232 Communication Ground
To Separate Model Sensor
Analog Current Output
Frequency (Pulse) Output
Communication Input
Two Alarm Outputs

AFLO-Electromagnetic Flow Meter
10
Output connection
I out I com
Figure (9) output current circuit
When DIP switch set to ON, AFLO Transmitter can provide +28V as a power supply and up-pull 10kΩ
resistance to output Frequencies (PUL) to isolated OC gate, Alarm Output (ALMH.ALML), and Status Control
(INSW). Frequency output obtained from POUT and PCOM terminals when DIP switch set as ON
When inductive load is connected to converter, a diode should be used as shown in figure (10)
Figure (10) Connection of electro magnet counter
Electronic counter connection as shown in figure (11)
Figure (11)

AFLO-Electromagnetic Flow Meter
11
Alarm output connection as shown in figure (12)
Figure (12)
OC gate connection as shown in figure (14)
Figure (14)
ON/OFF Switch Diagram
Key 1 ON: Supplyuppower(24V) for ALML output.
OFF: Noconnection.
Key 2 ON: Pulseoutputto OC gate when flow verification was taken.Connectpull -up resistor.
OFF: Noconnection.
Key 3 ON: Supplyuppower(24V) for ALMH output.
OFF: No connection.
Key 4 ON: ConnectedtoRS485 terminalresistorforcommunication
OFF: Noconnection.
Note Terminalusedforfar communicationonly.
Figure (15)

AFLO-Electromagnetic Flow Meter
12
5. Digital outputs
Digitaloutput means frequency output and pulse output, and both of them use the same output point, so
user can choose only one type of them not both
Digital voltage output connection as shown in figure (15)
Figure (15)
Photoelectricity coupling (PLC etc.) connection as shown in figure (16)
Figure (16)
Relay connection as shown in figure (17), mostly relays has a diode inside. If not, user should connect one
externally.
Figure (17)

AFLO-Electromagnetic Flow Meter
13
6. Operating
6.1.Compact Transmitter Display
Flow volume
Unit
Flow velocity(FLS)
Percentage (FQP)
Ratio of emptiness (MTP)
Forward and reverse intergated volumes
Deference of forward and reverse
Alarm
Enter
Down ; minusl1, page down
Up ; plus1, page up
Compound
Alarm
indicator
+ 282.92
FQH m 3/ h
+ 00000013.
5 m3
×1
∑
Figure (18)
6.2.Remote Transmitter Display
Flow volume
Unit
Flow velocity(FLS)
Percentage (FQP)
Ratio of emptiness (MTP)
Forward and reverse intergated volumes
Deference of forward and reverse
Alarm
Enter
Down ; minusl1, page down
Up ; plus1, page up
Compound
Alarm
indicator
+ 282.92
FQH m 3/ h
+ 00000013.
5 m3
×1
∑
Figure (19)

AFLO-Electromagnetic Flow Meter
14
6.3.Keys function
“Down” key: Selecting displayed data on lower line in turn
“Up” key: Selecting displayed data on higher line in turn
“Compound” key + “Enter” key: Come into parameter setting
“Enter” key: Press it to come into selected function
Adjust LCD contract using “Compound” key + “Up” key or “Compound” key + “Down” key for several
seconds
“Compound” key + “Down” key: Cursor turns left
“Compound” key + “Up” key: Cursor turns right
“Enter” key: Press for two seconds under any state and will return to measuring, after 3 minutes It will
return to the measuring automatically
6.4.Functions select menu
Push “Compound ”+“Enter” keys for functions select, push “Up” or “Down” keys to select one of the
following parameters.
Code
Functions
Notes
1
ParametersSet
Enter a password , and then adjust parameterssettings.
2
Clr Total Rec
reset totalizer
3
Fact Modif Rec
Select this function, it can be check the factor‘s modify
Record
6.5.Parameters Configuration
Code
Parameter words
Setting Way
Grades
Range
1
Language
Select
2
English
2
Comm Addres
Set count
2
0~99
3
Baud Rate
Select
2
300~38400
4
Snsr Size
Select
2
3~3000
5
Flow Unit
Select
2
L/h, L/m, L/s, m3/h, m3/m, m3/s
6
Flow Range
Set count
2
0~99999
7
Flow Rspns
Select
2
1~50
8
Flow Direct
Select
2
Plus/ Reverse
9
Flow Zero
Set count
2
0~±9999
10
Flow Cutoff
Set count
2
0~599.99%
11
Cutoff Ena
Select
2
Enable/Disable
12
Total Unit
Select
2
0.001m3~1m3 、0.001L~1L
13
SegmaN Ena
Select
2
Enable/Disable
14
Analog Type
Select
2
0~10mA /4~20mA
15
Pulse Type
Select
2
Freque / Pulse

AFLO-Electromagnetic Flow Meter
15
16
Pulse Fact
Select
2
0.001m3~1m3, 0.001L~1L
17
Freque Max
Select
2
1~5999 HZ
18
Mtsnsr Ena
Select
2
Enable/Disable
19
Mtsnsr Trip
Set count
2
59999 %
20
Alm Hi Ena
Select
2
Enable/Disable
21
Alm Hi Val
Set count
2
000.0~599.99 %
22
Alm Lo Ena
Select
2
Enable/Disable
23
Alm Lo Val
Set count
2
000.0~599.99 %
24
Sys Alm Ena
Select
2
Enable/Disable
25
Clr Sum Key
Set count
3
0~99999
26
Snsr Code1
User set
4
Finished Y M
27
Snsr Code2
User set
4
Product number
28
Field Type
Select
4
Type1,2,3
29
Sensor Fact
Set count
4
0.0000~5.9999
30
Line CRC Ena
Select
2
Enable/Disable
31
Lineary CRC1
User set
4
Set Velocity
32
Lineary Fact 1
User set
4
0.0000~1.9999
33
Lineary CRC2
User set
4
Set Velocity
34
Lineary Fact 2
User set
4
0.0000~1.9999
35
Lineary CRC3
User set
4
Set Velocity
36
Lineary Fact 3
User set
4
0.0000~1.9999
37
Lineary CRC4
User set
4
Set Velocity
38
Lineary Fact4
User set
4
0.0000~1.9999
39
FwdTotal Lo
Correctable
5
00000~99999
40
FwdTotal Hi
Correctable
5
00000~9999
41
RevTotal Lo
Correctable
5
00000~99999
42
RevTotal Hi
Correctable
5
00000~9999
43
PlsntLmtEna
Select
3
Enable/Disable
44
PlsntLmtVal
Select
3
0.010~0.800m/s
45
Plsnt Delay
Select
3
400~2500ms
46
Pass Word 1
User re-set
5
00000~99999
47
Pass Word 2
User re-set
5
00000~99999
48
Pass Word 3
User re-set
5
00000~99999
49
Pass Word 4
User re-set
5
00000~99999
50
Analog Zero
Set count
5
0.0000~1.9999
51
Anlg Range
Set count
5
0.0000~3.9999
52
Meter Fact
Set count
5
0.0000~5.9999
53
MeterCode 1
Factory set
6
Finished Y /M
54
MeterCode 2
Factory set
6
Product Serial No

AFLO-Electromagnetic Flow Meter
16
6.5.1.Passwords
Grade 1 of password (set by manufacturer as 00521): users can only read parameter.
Grade 2 of password (set by manufacturer as 03210): users can change 1~24 parameters.
Grade 3 of password (set by manufacturer as 06108): users can change 1~25parameters.
Grade 4 of password (set by manufacturer as 07206): users can change 1~38parameters.
Grade 5 of password (Fixed): users can change 1~52 parameters.
Password Grade 5 can be set by skilled users. Grade 4 is mainly used for resetting total volume in password.
Grades 1~3 can be set by anyone who can be chosen by users.
6.5.2.Details Parameters
1- Language
There are 2 languages for AFLO transmitter. They can be set by users.
2- Comm Addres
It means this instrument’s address when communicates with many, and has 01~99, holding the 0.
3- Baud Rate
300, 1200, 2400, 4800, 9600, 38400, baud rate.
4- Snsr Size
AFLO transmitters can be equipped with some different sensors that have deferent diameter of measuring
pipes. The pipes in different diameters from 10mm to 3000mm can be chosen in relative table.
5- Flow unit
The flow unit can choose form the parameters (L/s, L/m, L/h, m3/s, m3/m, m3/h), user can choose the proper
unit according to the technological requirement and using habit.
6- Flow Range
Flow range means upper limit value, and lower limit value is set “0” automatically. So, it makes the range,
and makes the relation of percent display, frequency output and current output with flow:
Percent display = (flow measure / measure range) x 100 %;
Frequency output = (flow measure / measure range) x frequency full;
Current output = (flow measure / measure range) x current full + base point;
Pulse output will not affect.
7- Flow Rspns
It means time of filter measure value. The long one can enhance the stability of flow display and output
digital, and fits for gross add up of pulse flow; the short one means fast respond rate, and fits for production
control. It is set by select.

AFLO-Electromagnetic Flow Meter
17
FS = ○○○○○
±○○○○○
8- Flow Direct
If users think the direct and design are different, just change the direct parameter is OK, but not change
exciting or signal.
9- Flow zero
Make sure the sensor is full of fluid, and the fluid is stable. Flow zero is shown as velocity of flow, mm/s.
Figure (20)
Converter’s zero-flow correction displays like this:
Upper small words: FS means measure value of zero;
Lower large words: correction value of zero.
When FS is not “0”, make FS = 0. Note: if change the value on next line and FS increases, please change the
“+, -” to correct FS to zero.
Flow zero is the compound value of the sensor, and should be recorded in sensor list and band. The unit will
be mm/s, and the sign will be opposite with correction value.
10-Flow cutoff
Flow cutoff is set in percentage of Upper Limit Range of flow, and users can delete all Negligible Small Signals
of flow volume, velocity and percentage out of displaying and outputting them. Sometimes user can delete
output of current output signal and frequency (pulse) output signal only to have flow, velocity and
percentage being displayed.
11-Total Unit
Converter display is counter with 9 bits, and the max is 999999999.
Integrator units are L, m3 (liter, stere,).
Flow integrator value: 0.001L, 0.010L, 0.100L, 1.000L, 0.001m3, 0.010m3, 0.100m3, 1.000m3;
12-SegmaN Ena
When “SegmaN Ena” is “enable”, if the flow flows, the sensor will export pulse and current。When it is
“disable”, the sensor will export pulse as “0” and current as “0” (4mA or 0mA) for the flow flows reversals.

AFLO-Electromagnetic Flow Meter
18
13-Output currents
Output current types can be chosen by users as 1~10mA or 4~20mA practically.
14-Pulse Type
Two kinds of Pulse Outputs can be chosen: Frequency Output and Pulse Output. Frequency Output is
continuous square waveform and Pulse output is a serial wave of square wave. Frequency output is mainly
used for instant flow and total integrated flow in short time measurement. Frequency output can be chosen
in equivalent frequency unit and volume of integrated flow can be displayed. Frequency Output can be used
in long time measurement for total integrated flow with volume units.
Frequency output and pulse output are usually from OC gates so that DC power supplies and load resistors
have to be required.
Equivalent pulse Unit is referred to one pulse for value of flow. The range of pulse equivalent can be chosen:
Pulse Equivalent
Flow
Pulse Equivalent
Flow
1
0.001L/cp
5
0.001m3/cp
2
0.01L/cp
6
0.01m3/cp
3
0.1L/cp
7
0.1m3/cp
4
1.0L/cp
8
1.0m3/cp
Under the same flow, the smaller pulse, the higher frequency output, and the smaller error will be. The
highest pulse output is 100cp/s.
15-Freque Max
Frequency output range is as the upper limit of flow measure, just the percent flow 100%. Frequency output
upper limit can be selected between 1~5000Hz.
16-Mtsnsr Ena
The state of empty pipe can be detected with the function of converter. In the case of Empty Pipe Alarm, if
the pipe was empty, the signals of analog output and digital output would be zero and displayed flow would
be zero, too.
17-Mtsnsr Trip
When the pipe is full of liquid (whether flowing or not), the parameter of “Mtsnsr”could be modified
more easily. The parameter displayed upper line is real MTP, and the parameter displayed bellow is the
“Mtsnsr trip”that should be set. When setting “Mtsnsr trip”, you could be according to the real MTP, the
value that should be set is usually three to five times of real MTP.

AFLO-Electromagnetic Flow Meter
19
18-Alm Hi Ena
Users can choose “Enable” or “Disable”.
19-Alm Hi Val
The parameter of upper limit alarm is percentage of flow range and can be set in the way of setting one
numerical value between 0%~199.9%.When the value of flow percentage is larger than the value of setting
value, transmitter outputs the alarm signal.
20-Alm Lo Val
The same as upper limit alarm.
21-Sys Alm Ena
Selecting Enable will have the function, and selecting Disable will cancel the function.
22-Clr Sum Key
User use more than 3 byte code to enter ,Then set this password in Clr TotalRec.
23-Snsr Code
It is referred to the produced date of sensor and the serial number of product that can keep the sensors
coefficient right and accurate.
24-Sensor Fact
“Sensor Coefficient” is printed on the Label of the sensor when it is made in factory. The “sensor coefficient”
has to be set into Sensor Coefficient Parameter when it runs with converter.
25-Field Type
AFLO affords three exciting frequency types: 1/16 frequency (type 1), 1/20frequency (type 2), 1/25
frequency (type 3). The small-bore one should use 1/16 frequency, and large-bore one should use 1/20 or
1/25 frequency. When using, please select type 1 first, if the zero of velocity is too high, select the type 2 or
type 3.
Note: Demarcate on which exciting type, working on it only.
26-FwdTotal Lo、hi
Positive total volume high byte and low byte can change forth coming and reverse total value, and be used
to maintenance and instead.
User use 5 byte code to enter, and can modify the positive accumulating volume (∑+). Usually, it is unsuitable
to exceed the maximum the counter set(999999999).
Table of contents
Other Aktek Measuring Instrument manuals
Popular Measuring Instrument manuals by other brands

MC Crypt
MC Crypt GLP03LJ operating instructions

enertexbayern
enertexbayern Enertex KNX Smartmeter 85A (RT) Manual and Configuration

Check-line
Check-line TI-007 operating instructions

S.E. International
S.E. International USB Inspector Operation manual

B meters
B meters HYDROCLIMA 2 user manual

Aqualytic
Aqualytic CHECKIT Comparator instruction manual