Alba Fiber Systems AFS8202M Series Installation instructions

Series AFS8202M
Alba Fiber Systems Inc. Specifications are subject to change without notice. Page 16/20/14
www.albafiber.net [email protected]
Industrial Redundant Managed Ethernet Media Converter with 2 Ports
1 x 10/100/1000BaseT(X) Port, 1 x 1000M SFP Port
Installation/Operation Instructions
Fiber Optic 10/100/1000Mbps Ethernet Transmission System
Part Number: AFS 8202M
10/100/1000Mbps Industrial Managed Ethernet Fiber Switch
Alba Fiber System, Inc.
265 E. Merrick Rd., Valley Stream, NY 11580
Tel: 1-516-837-9449 Fax: 1-516-837-9450
E-mail: [email protected]
Web: www.albafiber.net
Document Version 1.0

Series AFS8202M
Alba Fiber Systems Inc. Specifications are subject to change without notice. Page 26/20/14
www.albafiber.net [email protected]
Industrial Redundant Managed Ethernet Media Converter with 2 Ports
1 x 10/100/1000BaseT(X) Port, 1 x 1000M SFP Port
Table of Contents
1.0 Safety Instructions.........................................................................................................................................................4
2.0 Fiber Installation Hints................................................................................................................................................ 5
3.0 Product Description....................................................................................................................................................... 6
4.0 Product Features..............................................................................................................................................................7
5.0 Hardware.............................................................................................................................................................................. 8
5.1 Hardware Installation.......................................................................................................................................... 8
5.1.1 Din-Rail Installation.................................................................................................................................. 8
5.1.2 Wall Mount Installation...........................................................................................................................8
5.2 Panels Layout and Pinout Assignment Diagrams................................................................................9
5.2.1 Top Panel..........................................................................................................................................................9
5.2.2 Front Panel....................................................................................................................................................11
5.2.3 RJ45 Port Pinout 1000BaseT Ethernet Port Connection...................................................11
5.2.4 SFP Slots.........................................................................................................................................................12
5.2.5 Console Port................................................................................................................................................. 13
5.3 Front Panel LED Indicators............................................................................................................................. 14
5.4 Product Signal Format & Specifications..................................................................................................16
5.5 PoE Specifications.................................................................................................................................................17
5.6 Dimension Figure.................................................................................................................................................. 17
6.0 Web-Based Management.......................................................................................................................................... 19
6.1 Systems....................................................................................................................................................................... 21
6.1.1 System Information Configuration................................................................................................ 21
6.1.2 IP Configuration........................................................................................................................................ 22
6.1.3 SNTP Configuration..................................................................................................................................24
6.1.4 System Password......................................................................................................................................26
6.2 PoE..................................................................................................................................................................................26
6.2.1 Command Usage of PoE........................................................................................................................ 27
6.2.2 Displaying PoE Status............................................................................................................................ 29
6.3 LLDP...............................................................................................................................................................................30
6.3.1 Configuring Link Layer Discovery Protocol...............................................................................31
6.3.2 Displaying LLDP Information............................................................................................................ 33
6.4 Ports.............................................................................................................................................................................. 35
6.4.1 Port Configuration.................................................................................................................................... 36
6.4.2 Loop Protection.......................................................................................................................................... 40
6.5 Aggregation.............................................................................................................................................................. 41
6.5.1 Aggregation Mode Configuration.................................................................................................... 42
6.5.2 Aggregation Group Configuration...................................................................................................43
6.5.3 LACP Port Configuration....................................................................................................................... 44
6.6 Redundancy.............................................................................................................................................................. 47
6.6.1 Spanning Tree Algorithm (STA) Configuration...................................................................... 47
6.6.2 STP/RSTP/CIST Interface Configuration.................................................................................. 50

Series AFS8202M
Alba Fiber Systems Inc. Specifications are subject to change without notice. Page 36/20/14
www.albafiber.net [email protected]
Industrial Redundant Managed Ethernet Media Converter with 2 Ports
1 x 10/100/1000BaseT(X) Port, 1 x 1000M SFP Port
6.7 SNMP System Configuration...........................................................................................................................54
6.8 Port Status.................................................................................................................................................................55
6.9 MAC Table List......................................................................................................................................................... 56
6.10 IEEE 802.1Q VLANS...........................................................................................................................................59
6.11 PROTOCOL VLANS.............................................................................................................................................. 60
6.11.1 ASSIGNING PORTS TO VLANS........................................................................................................60
6.11.2 CONFIGURING VLAN ATTRIBUTES FOR PORT MEMBERS.............................................. 61
6.12 System Log Information................................................................................................................................ 63
6.13 Profile Configuration........................................................................................................................................ 65
6.13.1 Configuration Save................................................................................................................................65
6.13.2 Configuration Upload........................................................................................................................... 66
6.14 Firmware Update................................................................................................................................................ 67
6.15 Factory Defaults.................................................................................................................................................. 68
6.16 Restart Device...................................................................................................................................................... 69
7.0 Product Part Number Variations..........................................................................................................................71
8.0 Warranty............................................................................................................................................................................. 72

Series AFS8202M
Alba Fiber Systems Inc. Specifications are subject to change without notice. Page 46/20/14
www.albafiber.net [email protected]
Industrial Redundant Managed Ethernet Media Converter with 2 Ports
1 x 10/100/1000BaseT(X) Port, 1 x 1000M SFP Port
1.0 Safety Instructions
The optical devices used in this equipment are Hazard Level 1M. As required by IEC60825-1, the
installer is responsible for insuring that the label depicted below is present in the restricted locations
where this equipment is installed.
This assembly contains parts sensitive to damage by electrostatic discharge (ESD).
Use ESD precaution procedures when touching, removing or inserting parts or
assemblies.
Units are not waterproof; please install in an appropriate NEMA Enclosure.
When units are installed in extremely hot environments, the metal enclosures
may become hot to the touch. Please install is restricted areas where properly
trained personnel have access.
The safety information contained in this section, and on other pages of this manual,
must be observed whenever this unit is operated, serviced, or repaired. Failure to
comply with any precaution, warning, or instruction noted in the manual is in violation
of the standards of manufacture, warranty and intended use of the unit. ALBA assumes
no liability for the customer’s failure to comply with any of these safety requirements.
LASER RADIATION CAUTION:
DISCONNECTED OPTICAL CONNECTORS MAY EMIT OPTICAL ENERGY.
DO NOT VIEW BEAM WITH OPTICAL INSTRUMENTS (MAGNIFIERS).
This product contains Class 1M lasers
•Class 1M laser product according to IEC60825-1:1993+A1+A2
•CAUTION: Use of controls or adjustments or procedures other than those specified
herein may result in hazardous radiation exposure.
•Precautions should be taken to prevent exposure to optical radiation if the internal PCB removed
from its enclosure or when the fiber is disconnected from the unit.
•Laser radiation may be present on a fiber connection to this unit even when the power has been
removed from the unit.
•This unit is intended for installation in locations where only trained service personnel have
access to the fiber connections.
•The optical connectors are listed in the Connection Diagrams and Function section of this manual.
•Optical outputs and wavelengths are listed in the Specifications section of this manual.

Series AFS8202M
Alba Fiber Systems Inc. Specifications are subject to change without notice. Page 56/20/14
www.albafiber.net [email protected]
Industrial Redundant Managed Ethernet Media Converter with 2 Ports
1 x 10/100/1000BaseT(X) Port, 1 x 1000M SFP Port
2.0 Fiber Installation Hints
Fiber Information
Alba Fiber Transmission Systems are manufactured with optical connector covers to keep them
from accumulating dirt. In addition to safety precautions, our manual also provides the following
guidelines when working with optical fibers.
Please maintain optical fiber connectors as clean as possible to reduce loss of optical
transmission output. Cleanliness is extremely important to proper operations.
1. Protect optical connectors by leaving the connector covers in place on unused fiber
connections and on the fiber tips themselves.
a. Personnel who remove and replace fiber connectors or fiber pigtails should be equipped
with a fiber cleaning kit. These are available as off-the-shelf items from a supplier of fiber
optic accessories.
b. Propyl Alcohol and lint-free tissue or cloth may be used to clean fiber connector tips.
c. Do not use rubbing alcohol mixed with water. This can cause additional spots.
d. Clean the fiber by pulling the connector tip across the tissue, then turn the connector 90
degrees and repeat it in a different spot on the tissue.
e. Don’t pull the fiber across and then push it back. This will put the dirt that was cleaned off
back on again.
f. Repeat the process on a dry, folded tissue.
2. When removing fiber cables from fiber system ports, it is good practice to clean them again.
3. Installer must pay attention to the bend radius of the fibers. A general rule is to have a 3-
inch (8cm) bend radius. A bend radius less than 3 inches may cause attenuation also known
as optical signal loss.
4. Installers of fiber equipment should be equipped with an Optical Light Source an Optical
Power Meter to measure the optical inputs and outputs in a system. These instruments are
available from Alba at great savings, especially to our customers. The use of these tools will
save much time and effort in getting optical communications links up and running. Properly
equipped and trained installers can quickly determine the source of any problems that occur.

Series AFS8202M
Alba Fiber Systems Inc. Specifications are subject to change without notice. Page 66/20/14
www.albafiber.net [email protected]
Industrial Redundant Managed Ethernet Media Converter with 2 Ports
1 x 10/100/1000BaseT(X) Port, 1 x 1000M SFP Port
3.0 Product Description
The ALBA FIBER SYSTEMS Series AFS8202M, is a Layer 2, network managed Industrial Ethernet
Fiber Switch with one(1) 10/100/1000Base-T/TX 802.3af (PoE) or 802.3at (PoE+) compliant
Ethernet ports and designed to transmit and receive 1000Mbps data over two user selectable
SFP options. AFS8202M Ethernet switches provide up to 30 watts of power per PoE+ port in
standard mode. Units feature MDI/MDIX Full/Half Duplex Auto-Negotiation, 10/100/1000Base
Auto-sensing and compatibility with major Network Protocols. The optical interfaces operate at a
1000Mbps Ethernet rate. Redundant ring, plug-and-play performance, ensures ease of
installation; no user electrical or optical adjustments are required. Features included are
advanced network management functions as QoS, VLAN, IGMP snooping/GMRP, Port Trunking,
SNMP V1/V2c/V3, STP/RSTP 802.1w/d/s, LLDP; bandwidth management, and port mirroring.
Low power consumption, LED indicators for monitoring equipment link, operating status activity
and auto resettable voltage transient fuses. Additionally, they are designed with DIN-Rail or Wall
mount, fan-less, IP40 rated Aluminum enclosures in industrial extended temperature version.
With dual (2) redundant inputs 12- 55VDC voltage, the Series AFS8202M are outstanding
products in transmission of 10/100/1000Mbps Ethernet signals for industrial Layer 2 Managed
Network Installation.

Series AFS8202M
Alba Fiber Systems Inc. Specifications are subject to change without notice. Page 76/20/14
www.albafiber.net [email protected]
Industrial Redundant Managed Ethernet Media Converter with 2 Ports
1 x 10/100/1000BaseT(X) Port, 1 x 1000M SFP Port
4.0 Product Features
■IEEE802.1x compatible
■One (1) 10/100/1000BASE-T/TX Copper Port
■One (1) 1000Mbps SFP Port
■Backbone Bandwidth ≥20 Gbps
■Redundant Ring with <20ms Link Switchover
■Network Standards: IEEE802.3 10BaseT,
IEEE802.3u 100BaseT/TX and 1000BaseFX,
IEEE802.3x Flow Control, IEEE1588PTP,
IEEE1000Base-x, 1000Base-x
■Network Protocols: IGMP V1/V2/V3, GMRP,
GVRP, SNMP V1/V2C/V3, DHCP, TFTP, SNTP,
SMTP, RMON, HTTP, HTTPS, TELNET, SSH,
SYSLOG
■Supports RSTP/STP 802.1w/d/s, IEEE802.1D
■Enhanced mechanisms through QoS, TOS /
DiffServ
■Supports VLAN, QVLAN IEEE 802.1q,
IEEE802.1AD for Network Management
■Employs 802.3ad, LACP for Bandwidth
Optimization
■Supports ACL and Hardware Filtration
■Supports LLDP for Network Topology Discovery,
IEEE802.1AB
■LED Indicators for Link, Activity, Data Rate
■Configuring, Debugging via Web, Telnet, ssh,
Serial Port
■Port Loopback for Broadcast Storm Protection
■Port Locking for Authorized MAC Address
Access
■Relay Alarm Output for Power Failure
■Din-rail or Wall Mount Enclosure
■Industrial Temperature version, IP40
protection
■12-55VDC voltage
■Compliance with CE, FCC, ROHS
■PoE or PoE+ or PoE++ selectable

Series AFS8202M
Alba Fiber Systems Inc. Specifications are subject to change without notice. Page 86/20/14
www.albafiber.net [email protected]
Industrial Redundant Managed Ethernet Media Converter with 2 Ports
1 x 10/100/1000BaseT(X) Port, 1 x 1000M SFP Port
5.0 Hardware
5.1 Hardware Installation
5.1.1 Din-Rail Installation
AFS8202M series are din-rail mountable structure. This series of equipment’s back panel have
fixed well in DIN rail-way connection seat.
Insert DIN-Rail into DIN-Rail slot, and see Fig.1 below:
Fig.1 DIN-Rail Installation
5.1.2 Wall Mount Installation
AFS8202M series are wall mount structure. Loose the screws to remove the DIN-Rail.
Wall mount installation as shown Fig.2 below:

Series AFS8202M
Alba Fiber Systems Inc. Specifications are subject to change without notice. Page 96/20/14
www.albafiber.net [email protected]
Industrial Redundant Managed Ethernet Media Converter with 2 Ports
1 x 10/100/1000BaseT(X) Port, 1 x 1000M SFP Port
Fig.2 Wall Mount Installation
Specifications of Screw below Fig. 3 meet the standard of the AFS8202M series wall mount
installation:
Fig.3 Specification of the Screw
5.2 Panels Layout and Pinout Assignment Diagrams
5.2.1 Top Panel
Top Panel Fig.4 Is Shown as below:

Series AFS8202M
Alba Fiber Systems Inc. Specifications are subject to change without notice. Page 10 6/20/14
www.albafiber.net [email protected]
Industrial Redundant Managed Ethernet Media Converter with 2 Ports
1 x 10/100/1000BaseT(X) Port, 1 x 1000M SFP Port
Fig.4 Top panel
Power Input Terminal:
Redundancy dual power input by the terminal block as below. The standard power specs is
DC12V--55V, 12V DC (3A), 24V DC (1.5A) for non-PoE switch only, PoE switch should choose
48V DC (1A).
Alarm Relay
Normally, Ethernet switch alarm relay is closed. When the switch works, the relay power supply
is open; when the system power off, the relay power supply is closed. Recommended load
capacity of the relay switch is 1.5A (24VDC).

Series AFS8202M
Alba Fiber Systems Inc. Specifications are subject to change without notice. Page 11 6/20/14
www.albafiber.net [email protected]
Industrial Redundant Managed Ethernet Media Converter with 2 Ports
1 x 10/100/1000BaseT(X) Port, 1 x 1000M SFP Port
5.2.2 Front Panel
Front Panel Fig.5 Is Shown as Below:
Fig.5 Front Panel
5.2.3 RJ45 Port Pinout 1000BaseT Ethernet Port Connection
1000BaseT data is transmitted on differential TRD+/- signal pairs over copper wires.
Fig.6

Series AFS8202M
Alba Fiber Systems Inc. Specifications are subject to change without notice. Page 12 6/20/14
www.albafiber.net [email protected]
Industrial Redundant Managed Ethernet Media Converter with 2 Ports
1 x 10/100/1000BaseT(X) Port, 1 x 1000M SFP Port
5.2.4 SFP Slots
Insert 1000M SFP modules into each port, the SFP can be either 1 fiber or 2 fibers.
A. SFP of LC Double fiber, details seen Fig. 7 below:
Fig. 7 Double Fiber LC SFP
SFP of LC Double fiber Connection Method, details seen Fig. 8 below:
Fig. 8 LC Double fiber Connection Method
B. SFP of SC Single fiber, details seen Fig. 9 below:
Fig. 9 SC Single fiber

Series AFS8202M
Alba Fiber Systems Inc. Specifications are subject to change without notice. Page 13 6/20/14
www.albafiber.net [email protected]
Industrial Redundant Managed Ethernet Media Converter with 2 Ports
1 x 10/100/1000BaseT(X) Port, 1 x 1000M SFP Port
SFP of SC Single fiber Connection Method, details seen Fig. 10 below:
Fig. 10 SC Single fiber Connection Method
C. Copper SFP, details seen following Fig. 11:
Fig. 11 Copper SFP
5.2.5 Console Port
Network management port is a RJ45 port. It is a standard 3 wire RS-232 signal. Please use the
cable to connect with PC serial port. Serial communication parameters are as follows:
Baud Rate: 115200, Data bits: 8 Parity: None, Stop bit: 1 Flow Control: None
Console port pinout seen Fig. 12, Fig. 13 below:

Series AFS8202M
Alba Fiber Systems Inc. Specifications are subject to change without notice. Page 14 6/20/14
www.albafiber.net [email protected]
Industrial Redundant Managed Ethernet Media Converter with 2 Ports
1 x 10/100/1000BaseT(X) Port, 1 x 1000M SFP Port
Fig. 12 RJ45 Console Ports Pinout
Fig. 13 RJ45 (8-Pin) to DB9 (F) Cable Wiring
5.3 Front Panel LED Indicators
All the media converters have front panel mounted indicators to provide visual operational status
of the card and each of the channels. Functions of the various LED indicators are listed and
described as Fig. 14.

Series AFS8202M
Alba Fiber Systems Inc. Specifications are subject to change without notice. Page 15 6/20/14
www.albafiber.net [email protected]
Industrial Redundant Managed Ethernet Media Converter with 2 Ports
1 x 10/100/1000BaseT(X) Port, 1 x 1000M SFP Port
Fig. 14: LED Indicators of
Front Panel
AFS8202M
LED STATUS INDICATORS
LED
indicator
lamp
Status Explanation
PWR 1
Green
On Power 1 Up
Red On When power supply is no more than 10V
SYS On Switch works properly
PWR 2
Green
On Power 2 Up
Red On When power supply is no more than 10V
M/S
Green
On
When RSTP enable and switch in root mode,
Green
Green
Blink In Slave mode
Link/Act
On Active Optic Signal
Off Data signal absent
Blink Active data connection
1-2 Green
On
Power supply of PD Cameras normally on 1 to 2
copper ports

Series AFS8202M
Alba Fiber Systems Inc. Specifications are subject to change without notice. Page 16 6/20/14
www.albafiber.net [email protected]
Industrial Redundant Managed Ethernet Media Converter with 2 Ports
1 x 10/100/1000BaseT(X) Port, 1 x 1000M SFP Port
5.4 Product Signal Format & Specifications
The tables below identify the specifications for the various signals that these fiber units transmit
/ receive.
CONNECTORS
Optical SFP Dependent
Power Terminal Block
Electrical 1 x RJ-45
Management Console RS-232, RJ-45
OPTICAL PARAMETERS
Fiber Depend on SFP modules
Wavelength Multimode Depend on SFP modules
Wavelength Singlemode Depend on SFP modules
DATA
Data Interface 1 x 10/100/1000Base-T/TX, RJ-45 ports
Data Rate
10/100 /1000Mbps

Series AFS8202M
Alba Fiber Systems Inc. Specifications are subject to change without notice. Page 17 6/20/14
www.albafiber.net [email protected]
Industrial Redundant Managed Ethernet Media Converter with 2 Ports
1 x 10/100/1000BaseT(X) Port, 1 x 1000M SFP Port
5.5 PoE Specifications
Max. Output Power: 15.4W in 802.3af, 30W in 802.3at,
Output Voltage: 46 to 57 VDC (depends on external power supply)
Max. Output Current: 350 mA in 802.3af, 600 mA in 802.3at,
Max. Overload Protection: 850 mA
Wire or AFS8202M’s RJ45 Port seen as following Fig. 15
Fig. 15
5.6 Dimension Figure
Details of Top Views and Whole Views of Fiber Switch Seen as following Fig. 16, Fig. 17

Series AFS8202M
Alba Fiber Systems Inc. Specifications are subject to change without notice. Page 18 6/20/14
www.albafiber.net [email protected]
Industrial Redundant Managed Ethernet Media Converter with 2 Ports
1 x 10/100/1000BaseT(X) Port, 1 x 1000M SFP Port
Fig. 16 Top View
Fig. 17 Whole View

Series AFS8202M
Alba Fiber Systems Inc. Specifications are subject to change without notice. Page 19 6/20/14
www.albafiber.net [email protected]
Industrial Redundant Managed Ethernet Media Converter with 2 Ports
1 x 10/100/1000BaseT(X) Port, 1 x 1000M SFP Port
6.0 Web-Based Management
Input the IP address that appears on the label of AFS8202M into browser and the login screen
will pop up as Fig. 18.
Fig. 18 Login Screen
Default User Name: admin
Default Password: (no password)
Then click “OK”, you will enter the first page of the system.

Series AFS8202M
Alba Fiber Systems Inc. Specifications are subject to change without notice. Page 20 6/20/14
www.albafiber.net [email protected]
Industrial Redundant Managed Ethernet Media Converter with 2 Ports
1 x 10/100/1000BaseT(X) Port, 1 x 1000M SFP Port
First page when entering the system: seen as Fig. 19
Fig. 19
Table of contents