manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. ALCO
  6. •
  7. Smoke Alarm
  8. •
  9. ALCO CFS-SD300 Series User manual

ALCO CFS-SD300 Series User manual




NOTE:All wiring must conform to applicable local codes, ordinances, and regulations.
NOTE: Verify that all detector bases are installed, that the initiating-device circuits have
been tested, and that the wiring is correct.
- Wire the sensor base per the wiring diagram.
- Notify the proper authorities that the system is in operation.
- After all sensors have been installed, apply power to the control unit.
- Test the sensor(s) as described in the TESTING section of this manual.
- Install the sensor into the sensor base. Push the sensor into the base
while turning it clockwise to secure it in place.
NOTICE: This manual should be left with the owner/user of this equipment.
IMPORTANT: The detector must be tested and maintained regularly following NFPA 72
requirements. The detector should be cleaned at least once a year.
Weight:
Diameter:
Height:
5.5 oz. (155 g)
4.0˝(103 mm)
2.2˝(55 mm) installed in Base
Operating Voltage Range:
Standby Current:
Maximum Alarm Current (LED on)
Operating Humidity Range:
Operating Temperature Range:
Adjustable Sensitivity:
9 to 28VDC Volts Non-polarized
≤60µA @ 24 VDC
≤30mA @ 24 VDC
10% to 93% Relative Humidity,
14°F to 122°F (-10°C to50°C)
0.15~0.3dB/m

intelligent solutions
intelligent solutions




Remove power from initiating-device circuits before installing detectors




- The device is photo electronic detector uses a state of-the-art optical sensing chamber.
- The alarm can be reset only by a momentary power interruption.
- Two LEDs on each detector provide local 360° visible alarm indication.
- They flash every 5 seconds indicating that power is applied and the detector is working properly.
- The LEDs latch on in alarm. LEDs will be off when a trouble condition exists indicating that the
detector sensitivity is outside the listed limit.
- This detector is designed to provide open area protection and to be used with most conventional
fire alarm control panel
- Before testing, notify the proper authorities that the smoke detector system is undergoing
maintenance and will temporarily be out of service.
- Disable the zone or system undergoing maintenance to prevent unwanted alarms.
- Detectors must be tested after installation and as part of periodic maintenance.
NOTE:Before testing the detector, check to ensure the LEDs blink.
- If they do not, the detector has lost power (check the wiring), it is defective (return it for repair),
or the detector sensitivity is outside the listed limits.
The sensor can be tested in the following ways:
- Smoke Entry test: Aerosol Generator (Gemini 501)
- The GEMINI model 501 aerosol generator can be used for smoke entry testing. Set the generator
to represent.
- 4%/ft to 5%/ft obscuration as described in the GEMINI 501 manual. Using the bowl shaped
applicator apply aerosol until the panel alarms.
- A sensor that fails any of these tests should be cleaned as described under CLEANING, and
retested. If the sensor fails after cleaning, it must be replaced.
The detector include a tamper-resistant capability that prevents their removal from the bracket
without the use of a tool.
Before removing the detector, notify the proper authorities that the smoke detector system is
undergoing maintenance and will be temporarily out of service. Disable the zone or system
undergoing maintenance to prevent unwanted alarms.
- Remove the sensor to be cleaned from the system.
- Vacuum the screen carefully without removing it. If further cleaning is required.
- Remove the chamber cover/screen assembly by pulling it straight out.
- Use a vacuum cleaner or compressed air to remove dust and debris from the sensing chamber.
- Turn until it is firmly in place.
- Remove the sensor cover by pressing firmly on each of the four removal tabs that hold the cover
in place.

intelligent solutions
intelligent solutions
intelligent solutions

Popular Smoke Alarm manuals by other brands

Kidde 1275E Start guide

Kidde

Kidde 1275E Start guide

Bentel Security RF 501t manual

Bentel Security

Bentel Security RF 501t manual

Gentex 700 SERIES Installation instructions - owner's information

Gentex

Gentex 700 SERIES Installation instructions - owner's information

Nittan CKLD-KPT2 instruction manual

Nittan

Nittan CKLD-KPT2 instruction manual

Gamewell BD-SS quick guide

Gamewell

Gamewell BD-SS quick guide

System Sensor 2151 Installation and maintenance instructions

System Sensor

System Sensor 2151 Installation and maintenance instructions

System Sensor 2151 Installation and maintenance instructions

System Sensor

System Sensor 2151 Installation and maintenance instructions

ELRO Sensus 7M instruction manual

ELRO

ELRO Sensus 7M instruction manual

Lexing LX-SO-215 instruction manual

Lexing

Lexing LX-SO-215 instruction manual

VESDA lasercompact VLC-500 product manual

VESDA

VESDA lasercompact VLC-500 product manual

FCI 7100 SERIES Installation & operating manual

FCI

FCI 7100 SERIES Installation & operating manual

Haibrain PGSD834 user manual

Haibrain

Haibrain PGSD834 user manual

Xtralis VESDA VLS Product guide

Xtralis

Xtralis VESDA VLS Product guide

Visonic MCT-425 installation instructions

Visonic

Visonic MCT-425 installation instructions

Abus RWM50 user manual

Abus

Abus RWM50 user manual

Ceasefire INTELLI-SENSE TI-002212 installation manual

Ceasefire

Ceasefire INTELLI-SENSE TI-002212 installation manual

nedis WIFIDS10 Serries quick start guide

nedis

nedis WIFIDS10 Serries quick start guide

2gig Technologies 2GIG-SMKT2-345 installation instructions

2gig Technologies

2gig Technologies 2GIG-SMKT2-345 installation instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.