02 ULADA Application Guide - 5 -
Output Programming Selection Table:
Outputs must be programmed independently (OUT1 - OUT4)
Function Switch Positions Descriptions
ON OFF
Input to Output
Follower Mode 12, 3
Output follows signal it receives from the corresponding
input (i.e. FACP Sync module - maintains synchronization
of notification appliance circuit).
Temporal Code 3 Mode 31, 2 Enables Temporal Code 3 signal generation output.
This mode will accept a steady or a pulsing input.
Steady Mode 1, 2, 3 A steady output signal will be generated.
This mode will accept steady or pulsing input.
For the above modes DIP Switch 4 determines which Input controls the
corresponding output:
Switch 4 in the ON position causes output(s) to be controlled by Input 1.
Switch 4 in the OFF position causes output(s) to be controlled by Input 2.
Sync Mode Selection Table:
Function Switch Positions Descriptions
ON OFF
Amseco
Sync Mode*
1, 3,
42
This mode is designed to work with the Amseco series of horns,
strobes, and horn/strobes to provide a means of synchronizing
the Temporal-coded horns, synchronizing the flash timing of the
strobe, and silencing the horns of the horn/strobe combination over
a two-wire circuit while leaving strobes active.
Faraday
Sync Mode* 2, 4 1, 3
This mode is designed to work with the Faraday series of horns,
strobes, and horn/strobes to provide a means of synchronizing the
Temporal-coded horns, synchronizing the flash timing of the strobe,
and silencing the horns of the horn/strobe combination over a two-
wire circuit while leaving strobes active.
Gentex®
Sync Mode*
Gentex is a registered
trademark of
Gentex Corporation.
1, 2,
3, 4
This mode is designed to work with the Gentex®series of horns,
strobes, and horn/strobes to provide a means of synchronizing
the Temporal-coded horns, synchronizing the flash timing of the
strobe, and silencing the horns of the horn/strobe combination
over a two-wire circuit while leaving strobes active.
System Sensor®
Sync Mode*
System Sensor is a
registered trademark of
Honeywell.
1, 2, 4 3
This mode is designed to work with the System Sensor®series of
horns, strobes, and horn/strobes to provide a means of synchroniz-
ing the Temporal-coded horns, synchronizing the one-second flash
timing of the strobe, and silencing the horns of the horn/strobe
combination over a two-wire circuit while leaving strobes active.
CooperWheelock®
Sync Mode*
CooperWheelock is a
registered trademark of
Cooper Wheelock.
2, 3, 4 1
This mode is designed to work with the CooperWheelock series of
horns, strobes, and horn/strobes to provide a means of synchronizing
the Temporal-coded horns, synchronizing the one-second flash tim-
ing of the strobe, and silencing the horns of the horn/strobe combina-
tion over a two-wire circuit while leaving strobes active.
*Note: The AL602ULADA, AL602ULADAJ, AL802ULADA, AL802ULADAJ, AL1002ULADA and
AL1002ULADAJ will only synchronize horns, horn/strobes and strobes that contain synchronization capability.
Contact signal manufacturer for more detailed info.
The same synchronization mode must be selected for all outputs.
AL800LGK9E Board
Output DIP Switches
INPUT SELECT
TEMPORAL
STROBE SYNC
IN>OUT SYNC