(AL800LGK Board)
Output Dip Switches
System Sensor is a registered
trademark of Honeywell.
Gentex is a registered
trademark of Gentex Corporation.
Output Programming Selection Table:
Outputs must be programmed independently (OUT1 - OUT4)
Function Switch Positions Descriptions
ON OFF
Input to Output 1 2, 3 Output follows signal it receives from the corresponding input (i.e. FACP
Follower Mode Sync module - maintains synchronization of notification appliance circuit.
Temporal Code 3 3 1, 2 Enables Temporal Code 3 signal generation output.
Mode This mode is activated by a steady or a pulsing input.
Steady Mode 1, 2, 3 A steady output signal will be generated. This mode is activated by
a steady or pulsing input.
March Time Mode 2, 3 1 Enables a March Time output which will sound 60 beats
(60 beats per minute) per minute. This mode is activated by a steady or pulsing input.
For the above modes Dip Switch 4 determines which Input controls
the corresponding output:
Switch 4 in the ON position causes output(s) to be controlled by input 1.
Switch 4 in the OFF position causes output(s) to be controlled by input 2.
Sync Mode Selection Table:
Function Switch Positions Descriptions
ON OFF
Amseco 1, 3, 4 2 This mode is designed to work with the Amseco series of horns, strobes,
Sync Mode* and horn/strobes to provide a means of synchronizing the Temporal-coded
horns, synchronizing the flash timing of the strobe, and silencing the horns
of the horn/strobe combination over a two-wire circuit while leaving
strobes active.
Faraday 2, 4 1, 3 This mode is designed to work with the Faraday series of horns, strobes,
Sync Mode* and horn/strobes to provide a means of synchronizing the Temporal-coded
horns, synchronizing the flash timing of the strobe, and silencing the horns
of the horn/strobe combination over a two-wire circuit while leaving
strobes active.
Gentex 1, 2, This mode is designed to work with the Gentex®Commander GOS
Sync Mode* 3, 4 and ST/HS series of horns, strobes, and horn/strobes to provide a
means of synchronizing the Temporal-coded horns, synchronizing the
flash timing of the strobe, and silencing the horns of the horn/strobe
combination over a two (2)-wire circuit while leaving strobes active.
System Sensor 1, 2, 4 3 This mode is designed to work with the SpectrAlertTM series of horns,
Sync Mode* strobes, and horn/strobes to provide a means of synchronizing the
Temporal-coded horns, synchronizing the one-second flash timing
of the strobe, and silencing the horns of the horn/strobe combination
over a two-wire circuit while leaving strobes active.
Note: The AL602ULADA, AL802ULADA, and AL1002ULADA will only synchronize horns, horn strobes
and strobes that contain synchronization capability. Contact signal manufacturer for more detailed info.
The same synchronization mode must be selected for all outputs.
*It is required to control visual notification appliances (strobes) via input 1 (IN1) and audible notification
appliances (horns) via input 2 (IN2). This allows audible notification appliances (horns) to be silenced while
visual notification appliances (strobes) continue to operate.
- 6 -
INPUT SELECT
TEMPORAL
STROBE SYNC
IN>OUT SYNC