manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Altronix
  6. •
  7. Extender
  8. •
  9. Altronix AL800ULADA User manual

Altronix AL800ULADA User manual

Rev. 122000
AL800ULADA
NAC Power Extender
Installation Guide
Overview:
The Altronix AL800ULADA is an extremely cost effective 8 amp voltage regulated remote power supply/battery charger.
The AL800ULADA may be connected to any 12 or 24 volt Fire Alarm Control Panel (FACP). Primary applications include
Notification Appliance Circuit (NAC) expansion (supports ADA requirements) and will provide auxiliary power to support
system accessories. The unit delivers regulated and filtered 24 or 12 volt power via four (4) Class B, two (2) Class A or two
(2) Class B and one (1) Class A Notification Appliance Circuits. Additionally, a separate 1 amp auxiliary output with reset
for four (4)-wire smoke detectors. The 8 amp rated supply current can be divided between the four (4) outputs for power-
ing notification appliances. Each output is rated at 2 amp max., and can be independently programmed for Steady,
Temporal Code 3 or *Strobe Synchronization. All outputs may be programmed for Input to Output Follower Mode (output
will follow input. i.e. March Time Input, March Time Output). An individual output of 4 amp is achieved by paralleling 2
outputs. The AL800ULADA in non-alarm condition provides independent loop supervision for Class A and/or Class B
FACP NAC circuits. In the event of a loop trouble the FACP will be notified via the AL800ULADA’s steered input (input
1 or input 2). In addition, there are common trouble output terminals (NC, C, NO) which are used to indicate general
loop/system trouble. A common trouble input is provided for optional NC (normally closed) devices to report trouble to
the FACP. Two (2) FACP signaling outputs can be connected to AL800ULADA’s inputs. These inputs can then be directed
to control supervision and power delivery to any combination of the four (4) outputs.
Specifications:
AL800ULADA - NAC Power Extender
Agency Listings:
• UL Listed for Control Units and Accessories for Fire
Alarm Systems (UL 864) and UL Listed Standard for
Safety for Fire Protective Signaling Systems (UL 1481).
• MEA - NYC Department of Buildings Approved.
• CSFM - California State Fire Marshal Approved.
• FM - Factory Mutual Approved.
•NFPA 72 Compliant.
Input:
• Power input 115VAC/60 Hz, 3.2 amp.
• Two (2) Class A or two (2) Class B FACP inputs.
• Two (2) NC dry contact trigger inputs.
Output:
• Class 2 Rated power limited outputs
• Field selectable 24VDC or 12VDC voltage regulated
power limited outputs.
• 24VDC or 12VDC rated @ 8 amp max.
• Typical 8.6 mV output voltage ripple.
•Separate 1 amp auxiliary output with built-in and
remote reset capability.
• Two (2) outputs may be paralleled for more power on
an indicating circuit.
•Programmable supervised indicating circuit outputs:
Four (4) Class B or Two (2) Class A or One (1) Class
and Two (2) Class B.
Battery Backup:
• Built-in charger for sealed lead acid or gel
type batteries.
• Automatic switchover to stand-by battery when
AC Fails.
• Zero voltage drop when switching over to
battery backup.
• Circuit breaker battery protection.
Supervision:
• AC fail supervision (form "C" contact, 1 amp / 28VDC).
Factory set for 1 minute with optional 6 hour delay
setting (field selectable).
• Battery presence and low battery supervision
(form "C"contact, 1 amp / 28VDC).
Visual Indicators:
• Input and output status LED indicators.
Special Features:
• Temporal Code 3, *Strobe Sync Mode, Steady Mode,
Input to Output Follower Mode (maintains
synchronization of notification appliances circuit).
•March Time.
• Compatible with 12 or 24VDC fire panels.
• Filtered and electronically regulated output.
• Output loop supervision steered to input 1 or input 2.
• Common trouble input and output.
• Ground fault detection.
Additional Features:
• Unit includes power supply, red enclosure, cam lock,
open frame transformer and battery leads.
• Thermal and short circuit protection with auto reset.
Enclosure Dimensions:
15.5"H x 12"W x 4.5"D
Product Weight:
17 lbs.
- 2 -
Power Supply Specifications:
AC Input: 115VAC / 3.2 amp @ 60Hz
Output: 12 - 24VDC. Maximum 2.0 amp per output.
Total of 8 amp in Alarm Condition.
Battery: For 12VDC operation use a 12VDC / 12AH battery
For 24VDC operation use two (2) 12VDC / 12AH or two (2)
12VDC / 7AH batteries connected in series.
Stand-by Current: 75mA
EOL Resistor: 2.2K (2200 ohm)
(end of line)
Stand-by Specifications:
Stand-by Batteries Stand-by Time Alarm Output Aux Output
Total Amp/Minutes Current
24VDC/12AH 24 Hours 8 Amp/15 Minutes 50mA
(use two (2) 12VDC batteries in series) 60 Hours 8 Amp/5 Minutes -
24VDC/7AH 24 Hours 8 Amp/5 Minutes -
12VDC/12AH 24 Hours 8 Amp/15 Minutes 50mA
60 Hours 8 Amp/5 Minutes -
Installation Instructions:
The AL800ULADA should be installed in accordance with article 760 of The National Electrical Code as well as
NFPA 72 and all applicable Local Codes.
1. Mount the AL800ULADA in a desired location. It is recommended to first review the following tables for screw
terminals, switch selection and LED status indications. This will greatly facilitate installation hook-up.
Carefully review:
Power Supply Specifications (pg. 3)
Stand-by Specifications (pg. 3)
Output Programming Selection Table (pg. 4)
LED Status Indication Table (pg. 4)
Terminal Identification Table (pg. 5)
Typical Application Diagrams (pg. 7)
2. Connect the black and white transformer leads of AL800ULADA to a separate unswitched
AC circuit (115VAC, 60Hz) dedicated to the Fire Alarm System (Fig. 1, pg.3).
Connect green lead to earth ground.
3. Set switch SW1 on Power Supply Board for desired output voltage. Open for 24VDC (factory set), Close for 12VDC.
4. Measure output voltage before connecting devices. This helps avoid potential damage.
5. Connect battery to terminals marked [+ BAT --] on the Power Supply Board (battery leads included).
Use two (2) 12VDC batteries connected in series for 24VDC operation.
6. Set output selection switches marked (OUT1 through OUT4) to follow corresponding input (IN1 & IN2) and desired
output signal type (Temporal Code 3, Strobe synchronization, Steady output or input to output synchronization)
(Output Programming Selection Table pg. 4).
7. Connect FACP output to desired AL800LGK logic board inputs and notification appliances to desired AL800LGK
logic board outputs (Typical Application Diagrams pg. 7).
8. For connection of smoke detectors, digital dialer (Optional Hookup Diagram pg. 8).
9. To enable ground fault detection remove insulating washer located between standoff and the Power Supply Board
(Fig. 4B, pg. 8) and replace between mounting screw and the Power Supply Board (Fig. 4C, pg. 8).
General Information:
• For all Class B hookups SW1 & SW2 on the AL800LGK logic board must be open.
For all Class A hookups SW1 & SW2 on the AL800LGK logic board must be closed.
• AC Fail condition will report approximately one (1) minute after loss of AC. To delay report for 6 hours cut jumper J1
on the Power Supply Board (AC trouble output delay option).
Green
Lead
(ground)
115VAC input
50/60 Hz,
3.2 amp
Black
Lead
White
Lead
XFMR
Fig. 1
- 3 -
If this mode is selected the Power Supply Board must be reset by removing all power to it for 30 seconds.
• Low battery condition will report at approximately 21VDC (24VDC output setting) or approximately 10.5VDC
(12VDC output setting).
•Battery presence detection will report approximately 5 minutes after battery remains undetected (missing or removed).
• It is recommended (not required) to control visual notification appliances (strobes) via input 1 (IN1) and audible
notification appliances (horns) via input 2 ( IN2). This allows audible notification appliances (horns) to be silenced
while visual notification appliances (strobes) continue to operate.
Output Programming Selection Table:
For all of the following modes Dip Switch 4 determines which Input controls
the corresponding output:
Switch 4 in the ON position causes output(s) to be controlled by input 1.
Switch 4 in the OFF position causes output(s) to be controlled by input 2.
Outputs must be programmed independently (OUT1 - OUT4)
Function Switch Positions Descriptions
ON OFF
Input to Output 1 2, 3 Output follows signal it receives from the corresponding input (i.e. FACP
Follower Mode Sync module - maintains synchronization of notification appliance circuit.
Temporal Code 3 3 1, 2 Enables Temporal Code 3 signal generation output.
Mode This mode will accept a steady or a pulsing input.
Steady Mode 1, 2, 3 A steady output signal will be generated. This mode
will accept steady or pulsing input.
March Time Mode 2, 3 1 Enables a March Time output which will sound 60 beats
(60 beats per minute) per minute. This mode will accept a steady or pulsing input.
Strobe Sync 1, 2 Enables Strobe synchronization mode 1 (30 ms pulse every .9 second).
Mode 1 3 Will accept a steady or pulsing input. (Gentex®).
Strobe Sync 1, 2 3 Enables Strobe synchronization mode 2 (40 ms pulse every 1 second).
Mode 2 Will accept a steady or pulsing input. (System Sensor®).
Strobe Sync 2 1, 3 Enables Strobe synchronization mode 3 (50 ms pulse every .95 second).
Mode 3 Will accept a steady or pulsing input. (Faraday).
Strobe Sync 1, 3 2 Enables Strobe synchronization mode 4 (60 ms pulse every 1 second).
Mode 4 Will accept a steady or pulsing input. (Amseco).
Note: The AL800ULADA will only synchronize strobes that contain synchronization capability. Contact signal
manufacturer for more detailed info. The same synchronization mode must be selected for all outputs. When using 2-wire
horn/strobes, horns will be silenced.
*Strobe Sync Mode Information
Sychronization is defined as the simultaneous flash of all visual signals in a given field of view.
LED Status Indication Table:
LED OFF ON BLINK (LONG)* BLINK (SHORT)**
Out 1 Normal Alarm Condition Trouble Condition Trouble Condition Memory
Out 2 Normal Alarm Condition Trouble Condition Trouble Condition Memory
Out 3 Normal Alarm Condition Trouble Condition Trouble Condition Memory
Out 4 Normal Alarm Condition Trouble Condition Trouble Condition Memory
Input 1 Normal Alarm Condition Trouble Condition ---
Input 2 Normal Alarm Condition Trouble Condition ---
Fault Normal System Trouble --- ---
AC AC Loss AC present --- ---
DC No DC Output DC present --- ---
*Indicates trouble condition. When trouble (open, short or ground) occurs on a specific output, the corresponding
red output LED, (OUT1-OUT4) will blink. The corresponding green input LED will blink as well.
- 4 -
Output Dip Switches
INPUT SELECT
TEMPORAL
STROBE SYNC
IN>OUT SYNC
1234
O N
(AL800LGK Board)
** Indicates trouble condition memory. When a trouble condition restores, the units red output LED, (OUT1-
OUT4) will blink with a shorter and distinctly different duration. The green input LED(s) will be off (normal
condition). To reset the memory remove and restore AC and battery power to the unit. The LED(s) will extiguish.
Note: If indicating circuits have been restored, memory reset is not required for normal operation of the unit.
Terminal Identification Table:
AL800LGK Logic Board
Terminal Function/Description
Legend
IN1+, IN1- These terminals connect to the 12 or 24VDC FACP notification appliance circuit outputs. (Class A
IN2+, IN2- or Class B) Input trigger voltage is 9-30VDC @ 5mA min. Terminal polarity is shown in alarm
condition. During an alarm condition these inputs will cause the selected outputs chosen to drive
notification appliances. The designated outputs are set by output switches OUT1 through OUT4
(Output Programming Selection Table pg. 4). A trouble condition on an output loop will cause the
corresponding input to trip the FACP by opening the FACP loop. An alarm condition will always
override trouble to drive notification appliances.
RET1+, RET1- For Class A hookups these terminal pairs return to FACP NAC1 and/or NAC2. For Class B hookups
RET2+, RET2- the FACP EOL resistor from the NAC1 and/or NAC2 outputs are terminated at these terminals.
Optionally, other notification appliances or additional signaling circuit power supplies may be
connected to these terminals. If this option is chosen the EOL resistor must be terminated at the
last device.
C “DRY1” N.C. An open across these terminal pairs will cause the selected outputs chosen to drive
C “DRY2” N.C. notification appliances. The designated outputs are set by output switches OUT1 through
(Dry input OUT4 (Output Programming Selection Table pg. 4). Note these inputs are
trigger) unidirectional and will not report a trouble condition to the FACP.
+ OUT1 -- Notification appliances are connected to these outputs (Typical Application Diagrams
+ OUT2 -- pg. 7). Each power limited output will supply 2 amp. Two (2) outputs may
+ OUT3 -- be connected in parallel for a maximum NAC output capability of 4 amp. Total supply
+ OUT4 -- current is 8 amp. Outputs are controlled by designated input 1 (IN1) or input 2 (IN2)
(Output Programming Selection Table pg. 4).
C “FAULT” N.C. An open circuit across this pair of terminals will cause IN1 and IN2 to simultaneously
(Common signal a trouble condition back to the FACP (Typically used to report AC or BAT Fail).
trouble input)
N.C., C, N.O. These are dry contact trouble outputs that follow any general loop/system trouble conditions.
(Common (Typically used to trigger a digital communicator or other reporting device).
trouble output)
-- AUX+ This separate 1 amp auxiliary output is typically used to power 4-wire smoke detectors.
It can be reset (voltage drops out) by pressing the momentary aux reset switch on
the AL800LGK logic board or via the N.O. “REMOTE” C terminals. (Fig. 4, pg. 8)
N.O. C A momentary dry contact closure across these terminals interrupts the -- AUX+
“REMOTE” power output to reset 4-wire smoke detectors.
- 5 -
- 6 -
Power Supply Board
Terminal Function/Description
Legend
AC/AC Low voltage AC input.
-- DC + 12VDC or 24VDC @ 8 amp continuous non-power limited output.
AC FAIL Form “C” dry contacts used to signal the loss of AC, with AC present terminals N.O. and C are
C, N.C., N.O. open, N.C. and C are closed. When loss of AC occurs terminals N.O. and C close, N.C. and C are open.
BAT FAIL Form “C” dry contacts used to signal low battery voltage or loss of battery voltage.
N.O., N.C., C Under normal conditions terminals N.O. and C are open, N.C. and C are closed.
During a trouble condition terminals N.O. and C are closed, and N.C. and C are open.
BAT+, BAT- Stand-by battery input (leads provided). Use two (2) 12VDC batteries wired in series for 24VDC operation.
Maintenance:
Unit should be tested at least once a year for the proper operation as follows:
Output Voltage Test: Under normal load conditions, the DC output voltage should be checked for proper voltage level
(Power Supply Output Specifications Chart).
Battery Test: Under normal load conditions check that the battery is fully charged. Check specified voltage
both at battery terminal and at the board terminals marked [+ BAT --] to insure there is no break in the battery
connection wires.
Note: Maximum charging current is 700mA.
Note: Expected battery life is 5 years, however it is recommended changing batteries in 4 years or less if needed.
- 7 -
Typical Application Diagrams:
2.2K
EOL
2.2K
EOL 2.2K
EOL
2.2K
EOL
Optional paralleled
Class B output
SW1SW2
+OUT1 --
OUT1 OUT2 OUT3 OUT4
INP1 INP2
FAULT
NO "REMOTE " C
2 3 4
N
1 2 3 4
O N
2 3 4
N
1 2 3 4
O N
NO C NC C "FAULT" NC
AUX
RESET
O
OUT2 OUT4
INPUT SELECT
TEMPORAL
STROBE SYNC
IN > OUT SYNC
IN1+ IN1-- IN2--
IN2+ C"DRY1" NC
RET1+ RET1-- RET2--
RET2+ C"DRY2" NC
+OUT2 -- +OUT3 -- +OUT4 --
INPUT SELECT
TEMPORAL
STROBE SYNC
IN > OUT SYNC
UPPER TERMINALS
LOWER TERMINALS
From FACP
NAC2
From
FACP
NAC1
To FACP NAC1
EOL or next signaling
device or AL800UL-ADA
To FACP
NAC2 EOL 
or next signaling
device or AL800UL-ADA
AL800LGK
Class B hookup:
• Switches SW1 & SW2 on AL800LGK logic board must be
in the open position.
• It is recommended (not required) to control visual notification
appliances (strobes) via Input 1 (IN1) & to control audible
notifcation appliances (horns) via Input 2 (IN2). This facilitates
the ability to silence audible notification appliances (horns)
independently of visual notification appliances (strobes) during
certain operations.
Note: If common trouble (C “FAULT” N.C.) or dry contact
(C “DRY1” N.C. & C “DRY2” N.C.) input options are not used,
these terminal pairs must be shorted (connect jumper) to remain
inactive. For optional hookups, (Fig. 4, pg. 8).
Two outputs may be connected in parallel for a maximum NAC
output capability of 4 amp. When paralleling two (2) outputs, bridge
(pos +) to (pos +) and (neg -) to (neg -). Both of the
corresponding output switches must be set to follow the same
input. Install two (2) 2.2K ohm EOL resistors in parallel across
the last notification appliance.
Paralleled output circuit configuration is non-power limited.
Fig. 2
Horn
Legend Strobes Horn Strobes
OPEN SWITCH
CLOSED SWITCH
Switch Detail
SW1
--- DC +
SW2
+ OUT1 --
OUT1 OUT2 OUT3 OUT4
INP1 INP2
FAULT
-
-- AUX +
NO "REMOTE " C
1 2 3 4
O N
1 2 3 4
O N
1 2 3 4
O N
1 2 3 4
O N
NO C NC C "FAULT" NC
AUX
RESET
OUT1 OUT3
OUT2 OUT4
INPUT SELECT
TEMPORAL
STROBE SYNC
IN > OUT SYNC
IN1+ IN1-- IN2--
IN2+ C"DRY1" NC
RET1+ RET1-- RET2--
RET2+ C"DRY2" NC
+OUT2 -- + OUT3 -- + OUT4 --
INPUT SELECT
TEMPORAL
STROBE SYNC
IN > OUT SYNC
UPPER TERMINALS
LOWER TERMINALS
Return
to FACP
Return
to FACP
From
FACP
NAC1
From FACP
NAC2
AL800LGK
Class A hookup:
•Switches SW1 & SW2 on AL800LGK logic board must be
in the closed position for proper termination of NAC.
Loop 1 starts on Output 1 and terminates on Output 3.
Loop 2 starts on Output 2 and terminates on Output 4.
Both of the corresponding output switches must be set to
follow the same input.
• It is recommended (not required) to control visual
notification appliances (strobes) via Input 1 (IN1) &
to control audible notifcation appliances (horns) via Input 2
(IN2). This facilitates the ability to silence audible notification
appliances (horns) independently of visual notification
appliances (strobes) during certain operations.
Note: If common trouble (C “FAULT” N.C.) or dry contact
(C “DR
Y1” N.C. & C “DR
Y2” N.C.) input options are not used, these
terminal pairs must be shorted (connect jumper) to remain
inactive. For optional hookups, (Fig. 4, pg. 8).
Fig. 3
Note: The sync mode will only synchronize
notification appliances with synchronization
capability. Contact signal manufacturer for more
detailed info. The same synchronization mode
must be selected for all outputs.
Note: The sync mode will only synchronize
notification appliances with synchronization
capability. Contact signal manufacturer for more
detailed info. The same synchronization mode
must be selected for all outputs.
- 8 -
Optional hookups:
1- Battery and AC monitoring: AC or Battery Fail condition will cause the common trouble input
(C “FAULT” N.C.) to report back to the FACP via input 1 and input 2. The common trouble input may also
be used for other optional supervisory monitoring. To report AC and Battery Trouble connect the battery and AC
Fail relay output shown in (Fig. 4A) to the common trouble input.
2- Dry contact input (IN1DRY, IN2DRY) (IN1DRY, IN2DRY) can be used to alarm output from an addressable
module (these inputs are unidirection and cannot report back to trigger module).
Note: If common trouble (C “FAULT” N.C.) or dry contact (C “DRY1” N.C. & C “DRY2” N.C.) input options
are not used, these terminal pairs must be shorted (connect jumper) to remain inactive (Fig. 4D).
3- Auxiliary output (-AUX+) provides 12VDC or 24VDC at 1 amp max. The output voltage is determined by
the setting of switch marked SW1 on the Power Supply Board.
It can be reset by a momentary closure across terminals (N.O. REMOTE C) or by pressing AUX RESET button
on the AL800LGK logic board.
Ground Fault Detect: Factory set disabled (Fig. 4B). To enable ground fault detection remove insulating washer
between the board and standoff of the lower right power supply board mounting screw (Fig. 4C).
+
DC
---
AC AC
+
BAT
---
OPEN = 24V SW1 CLOSED = 12V
DC
AC
RL2
RL3
RLY1
PTC2
AC TROUBLE
DELAY OPTION
J2
IC3
IC2
AC FAIL
NC C NO
BAT FAIL
NC C NO
These circuits are used to
monitor AC and Bat Fail and
will cause a simultaneous trouble
condition to the FACP's IN1 and IN2
N.O. Reset Switch
Digital Communicator or
Local Annunciator Dry output Contact
(Form "C" contacts)
4-wire Smoke
Detector
+
--
+
--
4-wire Smoke
Detector
Fire
Alarm
Control
Panel
(FACP)
EOL Power
Supervision Relay
(Not Supplied)
EOL
Resistor
from
FACP
Black
Lead
White
Lead
115VAC/60 Hz, 3.2 amp
(Connect to seperate
unswitched AC circuit)
SW1
-- DC +
SW2
+ OUT1 --
OUT1 OUT2 OUT3 OUT4
INP1 INP2
FAULT
NO "REMOTE" C
NC C NO C "FAULT" NC
AUX
RESET
OUT1 OUT3
OUT2 OUT4
INPUT SELECT
TEMPORAL
STROBE SYNC
IN > OUT SYNC
IN1+ IN1-- IN2--
IN2+ C "DRY1" NC
RET1+ RET1-- RET2--
RET2+ C "DRY2" NC
+ OUT2 -- + OUT3 -- + OUT4 --
INPUT SELECT
TEMPORAL
STROBE SYNC
IN > OUT SYNC
-- AUX +
UPPER TERMINALS
LOWER TERMINALS
Addressable
Control Module
Trigger Output
See Note 2
XFMRXFMR
Fig. 4
AC TROUBLE
DELAY OPTION
AC FAIL
NC C NO
BAT FAIL
NC C NO
Optional Hookup Diagram:
Fig. 4A Fig. 4C
Plastic
Washer
Stand-Off
Power Supply
Board
Plastic
Washer
Stand-Off
Power Supply
Board
Ground Fault
Detection
Ground Fault
Detection Disabled
(Factory Set)
Fig. 4B
NC C NO C "FAULT" NC
Fig. 4D
- 9 -
2.2K
EOL
2.2K
EOL
2.2K
EOL
2.2K
EOL
Sync
Module
AL800ULADA
ADA Compliant
NAC Power
Extender
FACP
(Fire Alarm
Control Panel)
EOL
FACP
(Fire Alarm
Control Panel)
Sync
Module
AL800ULADA
ADA Compliant
NAC Power
Extender
EOL
Sync
Module
EOL
EOL
Note: When using this configuration you must enable the Input to Output Follower Mode (Dip Switch 1 ON)
and disable the Strobe Sync Mode (Dip Switch 2 OFF).
Typical Sync Module Hookups
Fig. 5: Synchronization using one (1) synchronization module with four (4) outputs.
Fig. 6: Synchronization using multiple synchronization modules.
Note: When using this configuration you must disable the Input to Output Follower Mode (Dip Switch 1 OFF)
and disable the Strobe Sync Mode (Dip Switch 2 OFF).
Switch Detail
OPEN SWITCH
CLOSED SWITCH
Horn
Legend Strobes Horn Strobes
- 10 -
Typical Application Diagram for Connecting Horn/Strobes
With Independent Control of Horns and Strobes:
SW1
--- DC +
SW2
+ OUT1 --
OUT1 OUT2 OUT3 OUT4
INP1 INP2
FAULT
--- AUX +
NO "REMOTE " C
NC C NO C "FAULT" NC
AUX
RESET
OUT1 OUT3
OUT2 OUT4
INPUT SELECT
TEMPORAL
STROBE SYNC
IN > OUT SYNC
IN1+ IN1-- IN2--
IN2+ C"DRY1" NC
RET1+ RET1-- RET2--
RET2+ C"DRY2" NC
+ OUT2 -- + OUT3-- + OUT4 --
INPUT SELECT
TEMPORAL
STROBE SYNC
IN > OUT SYNC
UPPER TERMINALS
LOWER TERMINALS
2.2K
EOL
2.2K
EOL
2.2K
EOL
2.2K
EOL
AL800LGK
Horn
Legend Strobes Horn Strobes
When using combination horn/strobes. Follow manufacturer’s
instructions for powering horns and strobes independently.
.875"
1"
1.3"
9.97"
13.53"
2"
2.25" 3.68" 4.56"
1.22"
1.22"
3.25"
1"
13.25"
2"
1.22"
12"
15.5"
8"
4.5"
2.25" 3.68" 4.56"
1.22"
1.25"
2.2"
1"
Enclosure Dimensions:
15.5”H x 12”W x 4.5”D
- 11 -
Altronix Corp.
140 58th Street, Brooklyn, New York 11220 USA, 718-567-8181, fax: 718-567-9056
web site: www.altronix.com, e-mail: [email protected], Lifetime Warranty, Made in U.S.A.
IIAL800ULADA G29E
MEMBER
Notes:
Altronix is not responsible for any typographical errors.
- 12 -

Other Altronix Extender manuals

Altronix AL1002ULADA User manual

Altronix

Altronix AL1002ULADA User manual

Altronix AL802ULADA User manual

Altronix

Altronix AL802ULADA User manual

Altronix AL642ULADA User guide

Altronix

Altronix AL642ULADA User guide

Altronix AL1002ULADAJ User manual

Altronix

Altronix AL1002ULADAJ User manual

Altronix AL1002ULADA User manual

Altronix

Altronix AL1002ULADA User manual

Altronix AL1042ULADA User manual

Altronix

Altronix AL1042ULADA User manual

Altronix AL802ULADA User manual

Altronix

Altronix AL802ULADA User manual

Altronix AL602ULADAJ User manual

Altronix

Altronix AL602ULADAJ User manual

Altronix AL602ULADAJ User guide

Altronix

Altronix AL602ULADAJ User guide

Altronix AL802ADA220J User manual

Altronix

Altronix AL802ADA220J User manual

Altronix AL602ADA220 User manual

Altronix

Altronix AL602ADA220 User manual

Altronix FireSwitch108 User manual

Altronix

Altronix FireSwitch108 User manual

Altronix AL602ADA220J User manual

Altronix

Altronix AL602ADA220J User manual

Altronix AL1042ADA220 User manual

Altronix

Altronix AL1042ADA220 User manual

Altronix AL1042ULADA User manual

Altronix

Altronix AL1042ULADA User manual

Altronix AL642ULADA User guide

Altronix

Altronix AL642ULADA User guide

Altronix AL1002ADA220 User manual

Altronix

Altronix AL1002ADA220 User manual

Altronix AL1042UL2ADA User manual

Altronix

Altronix AL1042UL2ADA User manual

Altronix AL602ULADA User guide

Altronix

Altronix AL602ULADA User guide

Altronix AL602ULADAJ User manual

Altronix

Altronix AL602ULADAJ User manual

Altronix AL642ADA220 User guide

Altronix

Altronix AL642ADA220 User guide

Altronix AL802ULADAJ User manual

Altronix

Altronix AL802ULADAJ User manual

Altronix Pace1STR User manual

Altronix

Altronix Pace1STR User manual

Altronix eBridge PLUS User manual

Altronix

Altronix eBridge PLUS User manual

Popular Extender manuals by other brands

DC Technologies DCX-50 Plus Extension user manual

DC Technologies

DC Technologies DCX-50 Plus Extension user manual

Camplex CMX-HDMI-SFP user manual

Camplex

Camplex CMX-HDMI-SFP user manual

ANTIFERENCE HDMIE50V2 manual

ANTIFERENCE

ANTIFERENCE HDMIE50V2 manual

Biamp Tesira EX-MOD Operation manual

Biamp

Biamp Tesira EX-MOD Operation manual

CYP PU-HBTPL-ZE Operation manual

CYP

CYP PU-HBTPL-ZE Operation manual

weBoost Drive Reach OTR installation guide

weBoost

weBoost Drive Reach OTR installation guide

Gefen DVI-141SB user manual

Gefen

Gefen DVI-141SB user manual

Gefen EXT-DP-141B user manual

Gefen

Gefen EXT-DP-141B user manual

ATEN VE829 user manual

ATEN

ATEN VE829 user manual

D-Link DAP-1860 user manual

D-Link

D-Link DAP-1860 user manual

Avenview WL-VGA-EXT Specification sheet

Avenview

Avenview WL-VGA-EXT Specification sheet

StarTech.com SV565UTPU user guide

StarTech.com

StarTech.com SV565UTPU user guide

Wilson Electronics weboost Office 100 installation guide

Wilson Electronics

Wilson Electronics weboost Office 100 installation guide

D-Link DRA-2060 Technical Support Setup Procedure

D-Link

D-Link DRA-2060 Technical Support Setup Procedure

Contemporary Control Systems TD960801-0MC user manual

Contemporary Control Systems

Contemporary Control Systems TD960801-0MC user manual

HDMI TX user manual

HDMI

HDMI TX user manual

DirekTronik M1-203D-TR user manual

DirekTronik

DirekTronik M1-203D-TR user manual

Ocean Matrix OMX-01HMBT0008 INSTALLATION & SPECIFICATIONS

Ocean Matrix

Ocean Matrix OMX-01HMBT0008 INSTALLATION & SPECIFICATIONS

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.