- 2 - AL1002ULADA
Agency Listings:
• ULListedControlUnitsforFireProtective
SignalingSystems(UL864).
• MEA-NYCDepartmentofBuildingsApproved.
• CSFM-CaliforniaStateFireMarshalApproved.
• FM-FactoryMutualApproved.
• NFPA72Compliant.
Input:
• Powerinput120VAC60Hz,5.0amp.
• Two(2)ClassA,StyleZortwo(2)ClassB,
StyleW,YFACPinputs.
• Two(2)NCdrycontacttriggerinputs.
Output:
• Class2Ratedpower-limitedoutputs.
• 24VDC@10ampmaxtotalalarmcurrent.
• 2.5ampmaxcurrentperoutput.
• Separate1.0ampauxiliaryoutput.
• Programmablesupervisedindicatingcircuitoutputs:
Four(4)ClassB,StyleW,YorTwo(2)ClassA,
StyleZorOne(1)ClassA,StyleZandTwo(2)ClassB,
StyleW,Y(see Application Guide).
•Thermalandshortcircuitprotectionwithautoreset.
Battery Backup:
•Built-inchargerforsealedleadacidorgeltypebatteries.
•Automaticswitchovertostand-bybatterywhen
ACFails.
• Zerovoltagedropwhenswitchingoverto
batterybackup.
Supervision:
•ACfailsupervision(form“C”contact,1amp/28VDC).
Factorysetfor1.5hourswithoptional30seconds
delaysetting(fieldselectable).
• InstantlocalACtroublereportingrelay
(form“C”contact,1amp/28VDC).
•Batterypresenceandlowbatterysupervision
(form“C”contact,1amp/28VDC).
Visual Indicators:
•InputandoutputstatusLEDindicators.
Special Features:
• 2-wirehorn/strobeSyncmodeallowsaudible
notificationappliances(horns)tobesilenced
whilevisualnotificationappliances(strobes)
continuetooperate.
• SyncprotocolsincludePotter/Amseco,Faraday,
Gentex®,SystemSensor®,andCooperWheelock®.
• TemporalCode3,SteadyMode,InputtoOutput
FollowerMode(maintainssynchronizationof
notificationappliancescircuit).
• Compatiblewith12VDCor24VDCfirepanels.
•Outputloopsupervisionsteeredtoinput1orinput2.
• Signalcircuittroublememory(helpsidentify
intermittentloopproblems).
• Commontroubleinputandoutput.
• Groundfaultdetection.
•Unitincludespowersupply,redenclosure,camlock,
andbatteryleads.
Enclosure Dimensions (approx. H x W x D):
15.5”x12”x4.5”(393.7mmx304.8mmx114.3mm).
Overview:
TheAltronixAL1002ULADAisanextremelycosteffective10ampremotepowersupply/batterycharger.Itmaybecon-
nectedtoany12or24voltFireAlarmControlPanel(FACP).PrimaryapplicationsincludeNotificationApplianceCircuit
(NACsuchasstrobesandhorns)expansionsupporttomeetADArequirements.Italsoprovidesauxiliarypowertosupport
systemaccessories.Theunitdeliverselectronicallyregulatedandfiltered24voltpowertoClassB,StyleW,YorClass
A,StyleZNACloopcircuits.Additionally,aseparate1.0Aauxiliaryoutputforfour(4)-wiresmokedetectorsisavailable.
The10ampmax.alarmcurrentcanbedividedbetweenthefour(4)outputsforpoweringNACdevices.Eachoutputis
ratedat2.5ampmax.,andcanbeindependentlyprogrammedforSteady,TemporalCode3orStrobeSynchronization.All
outputsmaybeprogrammedforInputtoOutputFollowerMode(outputwillfollowinput).Innon-alarmconditioninde-
pendentloopsupervisionforClassA,StyleZand/orClassB,StyleW,YFACPNACcircuitsisprovided.Intheeventof
alooptrouble,theFACPwillbenotifiedviathesteeredinput(input1orinput2).Inaddition,therearecommontrouble
outputterminals(NC,C,NO)whichareusedtoindicategeneralloop/systemtrouble.Acommontroubleinputisprovided
foroptionalNC(normallyclosed)devicestoreporttroubletotheFACP.Two(2)FACPsignalingoutputscanbeemployed
anddirectedtocontrolsupervisionandpowerdeliverytoanycombinationofthefour(4)outputs.
Note:TheinformationinthisdocumentisvalidformodelsAL1002ULADAandAL1002UL2ADA.ModelAL1002ULADA
isequivalenttomodelAL1002UL2ADA.
Specifications:
AL1002ULADA - NAC Power Extender