- 4 - Maximal Rack Access Power Controllers (PTC)
Installation Instructions:
Important: Adjust output voltages, and Fire Alarm Interface configuration before installing unit in the rack.
1. Separate bottom and top of rack mount chassis by removing six (6) screws (Rack Mechanical Drawing &
Dimensions, pg. 11).
2. Set output voltage:
SelectdesiredDCoutputvoltagebysettingSW1onthepowersupplyboard(s)(Fig. 1a, pg. 6) to the
appropriate position (Output Voltage and Stand-by Specification Charts, pg. 5).
For Maximal33RD each set of eight (8) outputs can be set for 12VDC or 24VDC (example: eight (8) outputs @
12VDC and eight (8) outputs @ 24VDC).
3. Input trigger programming options:
The unit can be programmed to operate with either a normally open or normally closed input from access control
devicesbysettingswitchesSW3oneithertheACM8CBR-SorACM16CBR-Sboardtotheappropriateposition
(Fig. 2b, pg. 7);OPENforanormallyclosed[NC]triggerinputorCLOSEDforanormallyopen[NO]input.
4. Output programming options:
a. The outputs can be programmed to be either all Fail-Safe (i.e. mag locks), all Fail-Secure (i.e. electric strikes) or
any combination of each by setting the corresponding OUTPUT SELECT dip switches (1-8) on the ACM8R-S
board to the appropriate position; ON for Fail-Safe outputs or OFF for Fail-Secure outputs (Fig. 2a, pg. 7).
Note: the output configuration will follow the input trigger option
b. To enable the FACP Disconnect for an output the corresponding FIRE ALARM INTERFACE switch must be
in the ON position. To disable the FACP Disconnect the FIRE ALARM INTERFACE dip switches (1-8) on the
ACM8CBR-S/ACM16CBR-S board must be in the OFF position (Fig. 2a, pg. 7).
5. Fire Alarm Interface hookup options:
Anormallyclosed[NC],normallyopen[NO]inputorpolarityreversalfromanFACPsignalingcircuitwilltrigger
the selected outputs (Figs. 6-11, pg. 9).ToprogramtheFireAlarmInterfacesetdipswitchesSW1andSW2onthe
ACM8CBR-M board to the appropriate positions (Figs. 3a & 3b, pg. 7) (Fire Alarm Interface Switch Settings pg. 5).
6. Battery Connections:
For access control applications batteries are optional. If batteries are not used a loss of AC will result in the loss of
outputvoltage.Whenbatteriesareusedtheymustbeleadacidorgeltype.Connectone(1)batterytotheterminals
marked[--BAT+]for12VDCoperation.Usetwo(2)12VDCbatterieswiredinseriesfor24VDCoperation
(Fig. 4b/5b, pg. 8). The rack mount enclosure will not accommodate batteries. A separate battery enclosure is required.
Note:Whenusing the Maximal33RD with battery backup two (2) separate batteries or sets of batteries must be used.
7. Battery and AC Supervision outputs:
Connect the appropriate notification signaling device to the terminals marked AC Fail and Battery Fail on the power supply
board(s) (Fig. 4a/5a, pg. 8).Use 22AWGto18AWGfor AC Fail and Low/No Battery reporting.
8. Reassemble the bottom and top of rack mount chassis by fastening the six (6) screws.
(Rack Mechanical Drawing & Dimensions pg. 11).
9. Attach mounting brackets to rack mount Maximal for desired rack or wall installation (Fig. 12-14, pg. 10).
10. Mount in desired rack location. Do not obstruct side air vents.
11. Set the power disconnect circuit breaker to the OFF position (Fig. 15a, pg. 11).
12. Plug power cord into grounded 50/60Hz receptacle (Fig. 15b, pg. 11).
13. Set the power disconnect circuit breaker to the ON position (Fig. 15a, pg. 11).
14. Measure the output voltage before connecting devices. This helps avoid potential damage.
15. Set the power disconnect circuit breaker to the OFF position (Fig. 15a, pg. 11).
16. Input trigger connections:
Connect the Normally Open or Normally Closed input triggers from the access control devices to the removable
terminalsmarked[IN1andGND]through[IN8andGND]forMaximal1RHDandMaximal3RHD.For
Maximal1RD, Maximal3RD and Maximal33RD connect devices to the second set of terminals marked. For Make
surethedevicesmatchsettingsofSW3instep3(Rack Mechanical Drawing & Dimensions pg. 11).
17.Output connections:
Connectthedevicestobepoweredtotheremovableterminalsmarked[--OUT1+to--OUT8+]forMaximal1RHD
and Maximal3RHD. For Maximal1RD, Maximal3RD and Maximal33RD connect devices to the second set of
terminalsmarked[--OUT1+to--OUT8+](Fig. 15c, pg. 11).
18. Fire Alarm Interface connection options:
a. ConnecttheFACPtriggerinputtotheremovableterminalsmarkedFACP1andFACP2.Whenusingthepolarity
reversalfromanFACPsignalingcircuit,connectthenegative[-]totheterminalmarkedFACP1andthepositive
to the terminal marked FACP2 (polarity is in alarm condition) (Rack Mechanical Drawing & Dimensions pg. 12).