- 2 - T2RM78S(D)Q Installation Guide
Overview:
Altronix Trove Mercury rack kits are pre-assembled and consist of Trove enclosures/backplanes with factory installed Altronix power supply/charger
and sub-assemblies. All kits accommodate a variety of Mercury modules for up to eight doors in a single enclosure.
Configuration Chart:
Altronix
Model
Number
115VAC 60Hz
Input Current (A)
Power Supply Board
Input Fuse Rating
Power Supply Board
Battery Fuse Rating
Nominal
DC
Output
Voltage
Range
(VDC)
Maximum Supply
Current for Main and Aux.
Outputs on Power Supply
board and LINQ8ACM(CB)
Access Power Controller’s
outputs
Fail-Safe/Fail-Secure
or
Dry Form “C” Outputs
Current Per
LINQ8ACM(CB) Output
(A)
LINQ8ACM(CB) Board
Input Fuse (PTC)
Rating
LINQ8ACM(CB) Board
Output Fuse (PTC)
Rating
PDS8(CB) Board
Input Fuse (PTC)
Rating
PDS8(CB) Board
Output Fuse (PTC)
Rating
T2RM78SQ
4.2 5A/
250V
15A/
32V
20.17-
26.4 24VDC @ 9.2A 8
2.5 15A/
32V
3A/
32V
10A/
32V
3A/
32V
T2RM78SDQ 2.0 9A 2.5A 9A 2.5A
Hardware:
Spacer | 5/16” Pan Head Screw | Lock Nut
Installing Trove2R into Rack Tower:
Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/ANSI, and with all local codes and authorities having jurisdiction.
These products are for indoor use only and must be installed within the protected premises.
Note: First assemble and Install Z Bracket Wire Management Accesory (refer to Z Bracket Installation pg. 3)
1. Remove backplane from enclosure prior to installing into rack cabinet (do not discard hardware).
2. In order to mount included cUL Listed tamper switch (Tane Model 3/8 ASH FM WH or equivalent),
turn the enclosure upside down and locate mounting holes (Fig. 1, pg. 2).
Insert the tamper switch flying leads into the center knockout of the three (3) holes from outside of the
drawer with the button facing outwards, make sure tamper switch is inserted properly then secure it
with the two (2) screws (supplied). Connect tamper switch wiring to the Access Control Panel input or
the appropriate UL Listed reporting device. To activate alarm signal open the rack drawer.
3. Slide the rack enclosure into an open 2U location in the four post rack cabinet.
4. Utilizing proper fasteners attach front ears to the rack rails (Rack drawer, pg. 8).
5. Attach the rear of the adjustable slides to the rear rails of the rack cabinet with the proper fasteners.
6. Secure the rack cover (Fig. 2a, pg. 3) and rack drawer (Fig. 2b, pg. 3) to earth ground.
7. Ensure that all internal cofigurations (voltage selection, switch settings, etc.) are completed before
mounting backplane back into Trove rack enclosure.
Fig. 1
Back of the drawer,
viewed from outside.
Tamper Switch
mounting location
Fig. 2
Fig. 2a
Fig. 2b