Always “On” UPS GES-701N - GES-302N ABS User manual

GES-N-Series – Single-Phase Input, Single-Phase Output
ABS Approved UPS System
GES-701N – GES-302N ABS
On Line: 700VA, 1kVA, 1.5kVA, 2kVA, 3kVA
Operators Manual
M0309_N_Series_ABS_700-3kVA_User_Manual V2.8 2012-06-12

M0309_N_Series_ABS_700-3kVA_User_Manual V2.8 2012-06-12
THIS PAGE IS INTENTIONALLY BLANK

Always On UPS Systems
Note
The instructions contained in this manual are not intended to cover all of the details or variations
in equipment, or to provide for every possible contingency to be met in connection with
installation, operation, or maintenance. Should further information be desired or should
particular problems arise which are not covered sufficiently for the purchaser’s purposes, the
matter should be referred directly to Always On UPS Systems Inc.
Any electrical or mechanical modifications to this equipment, without prior written consent of
Always On UPS Systems Inc, will void all warranties and may void UL/cUL/CSA listing.
Unauthorized modifications also can result in personal injury, death, or destruction or the
equipment.
Uninterruptible Power Supply
Please complete the Warranty Card supplied with this UPS and return it by mail to Always On
UPS Systems Inc. This activates the warranty.
If additional information or technical assistance is required call:
Always On UPS Systems Inc Sales and Technical Support Line
Toll free at 1-877-259-2976 Ext. 451 or (250) 491-9777 Ext. 451 or Fax (250) 491-9775
Or E-mail at sales@alwaysonups.com or visit our web site at www.alwaysonups.com
Or write to
Always On UPS Systems Inc.
Bldg 1 – 150 Campion Road,
Kelowna, BC,
V1X 7S8,
Canada
Please complete the following information for your records.
Model Number: ______________________________________________________________
Serial Number: ______________________________________________________________
Date of Installation: ____________________________________________________________
Inspected By: ______________________________________________________________
M0309_N_Series_ABS_700-3kVA_User_Manual V2.8 2012-06-12 i

Always On UPS Systems
M0309_N_Series_ABS_700-3kVA_User_Manual V2.8 2012-06-12 ii
THIS PAGE IS INTENTIONALLY BLANK

Always On UPS Systems
IMPORTANT SAFETY INSTRUCTIONS
•THIS MANUAL CONTAINS IMPORTANT INSTRUCTIONS THAT SHOULD BE
FOLLOWED DURING INSTALLATION AND MAINTENANCE OF THE UPS AND
BATTERIES.
•THE UPS SYSTEM IS NOT INTENDED FOR EXTERNAL USE UNLESS
SPECIFICALLY DESIGNED FOR IT.
•ALL SERVICING MUST BE DONE BY QUALIFIED PERSONNEL. DO NOT
ATTEMPT TO SERVICE THIS EQUIPMENT YOURSELF. OPENING OR
REMOVING COVERS WILL RISK EXPOSURE TO DANGEROUS VOLTAGES. DO
NOT LOCATE UPS IN AN AREA WHERE UNAUTORIZED PERSONNEL HAVE
ACCESS.
•THE POWER SUPPLY FOR THIS UNIT MUST BE SINGLE PHASE RATED IN
ACCORDANCE WITH THE EQUIPMENT DATA PLATE. IT MUST BE SUITABLY
GROUNDED.
•DO NOT STAND BEVERAGE CONTAINERS ON THE UNIT.
•EXTERNAL SLITS AND OPENINGS IN THE CABINET ARE PROVIDED FOR
VENTILATION. TO ENSURE RELIABLE OPERATION OF THE PRODUCT AND
TO PROTECT FROM OVERHEATING, THESE OPENINGS MUST NOT BE
BLOCKED OR COVERED. OBJECTS MUST NEVER BE INSERTED INTO
VENTILATION HOLES OR OPENINGS.
•THE POWER OUTLET ON THE UPS DISTRIBUTION PANEL WILL BE LIVE
WHEN THE UNIT’S POWER SWITCH IS ON, WHETHER OR NOT THE UNIT AC
SUPPLY IS PRESENT.
•QUALIFIED PERSONNEL SHOULD BE CONSULTED WHEN:
1. THE POWER CABLE HAS BEEN DAMAGED
2. LIQUID HAS BEEN SPILLED INTO THE UNIT
3. THE UNIT DOES NOT OPERATE NORMALLY EVEN THOUGH THE
OPERATING INSTRUCTIONS HAVE BEEN FOLLOWED
•DO NOT PLACE MAGNETIC STORAGE MEDIA ON TOP OF THE UNIT, AS THIS
CAN RESULT IN DATA CORRUPTION.
•THIS UPS WAS DESIGNED TO POWER ALL MODERN COMPUTER LOADS AND
ASSOCIATED PERIPHERAL DEVICES, SUCH AS MONITORS, MODEMS,
CARTRIDGE TAPE DRIVES, EXTERNAL FLOPPY DRIVES, ETC. DO NOT USE
IT FOR PURE INDUCTIVE OR CAPACITIVE LOADS. IT IS NOT RATED TO
POWER LIFE SUPPORT EQUIPMENT.
CAUTION:
ALL RECORDED MEDIA, SUCH AS DISKETTES, TAPES AND CARTRIDGES,
SHOULD BE KEPT A MINIMUM OF 60CM FROM THE UPS. THE MAGNETIC
FIELD CREATED BY OPERATION OF THE UPS MAY ERASE DATA ON THOSE
DEVICES.
ATTENTION:
INSTALL THE ON-LINE UPS IN A WELL-VENTILATED AREA, AWAY FROM
FLAMMABLE LIQUIDS, GASES, OR EXPLOSIVES. DO NOT LET THE UNIT COME
INTO CONTACT WITH WATER. POTENTIALLY LETHAL VOLTAGES EXIST
WITHIN THIS UNIT AS LONG AS THE BATTERIES ARE CONNECTED. DO NOT
TOUCH ELECTRICAL CIRCUITS WHEN POWER IS CONNECTED TO THE UPS.
TURN THE UPS “OFF” AND DISCONNECT THE UNIT FROM THE POWER SOURCE
BEFORE REMOVING THE COVER PLATES.
ALL REPAIRS SHOULD BE PERFORMED BY QUALIFIED SERVICE PERSONNEL.
READ THIS MANUAL CAREFULLY BEFORE INSTALLING OR USING THE UNIT.
FOLLOW ALL PROCEDURES, AS DESCRIBED, TO INSURE SAFE, RELIABLE
OPERATION OF THE UPS.
SAVE THESE INSTRUCTIONS
M0309_N_Series_ABS_700-3kVA_User_Manual V2.8 2012-06-12 iii

Always On UPS Systems
MORE SAFETY INSTRUCTIONS
•DO NOT USE THIS EQUIPMENT FOR ANY PURPOSE OTHER THAN THE
INTENDED USE.
•EXAMINE THE PACKAGING CONTAINER FOR DAMAGE. NOTIFY THE
CARRIER IMMEDIATELY IF DAMAGE IS PRESENT.
•DO NOT DISASSEMBLE THE UPS.
•DO NOT OPERATE OR LOCATE NEAR WATER OR EXCESSIVE HUMIDITY.
•DO NOT USE OTHER MANUFACTURERS ACCESSORIES. MAY CAUSE DAMAGE
OR UNSAFE CONDITIONS
•KEEP LIQUID AND FOREIGN OBJECTS FROM GETTING INSIDE THE UPS.
•DO NOT BLOCK AIR VENTS IN THE FRONT OF THE UPS OR AIR EXHAUSTS IN
THE BACK.
•DO NOT PLACE OR OPERATE CLOSE TO GAS, HEATERS OR FIRE.
•DO NOT LET POWER CORDS CONTACT HOT SURFACES
•DO NOT PLUG APPLIANCES, SUCH AS HALF BRIDGE RECTIFIED LOAD, INTO
THE UPS.
•USE CAUTION WHEN SERVICING BATTERIES. BATTERY ACID CAN CAUSE
BURNS TO SKIN AND EYES. IF ACID IS SPILLED ON SKIN OR IN EYES, FLUSH
WITH FRESH WATER AND CONTACT A PHYSICIAN IMMEDIATELY.
•DO NOT OPERATE IF THE UNIT IS LEAKING LIQUID OR IF A WHITE POWDERY
RESIDUE IS PRESENT.
•BATTERIES MAY CONTAIN METALS AND OTHER CHEMICAL HAZARDOUS
WASTE. FOR PROPER DISPOSAL, CONSULT YOUR LOCAL STATE AND
FEDERAL EPA AND OTHER ENVIRONMENTAL LAWS AND REGULATIONS.
•USE ONLY THE POWER SUPPLY CORD PROVIDED WITH THIS UNIT. THE
POWER CORD FOR UPS IS WIRED IN ACCORDANCE WITH NATIONAL
ELECTRICAL CODE (NEC) SPECIFICATIONS. BE SURE THAT THE WALL
OUTLET IS ALSO WIRED TO THESE SPECIFICATIONS.
•THE UPS CONTAINS ITS OWN ENERGY SOURCE (BATTERY). THE OUTPUT
RECEPTACLES MAY BE LIVE EVEN WHEN THE UPS IS NOT CONNECTED TO
AN AC SUPPLY.
•ONCE YOU HAVE CONNECTED THE BATTERY CONNECTORS, DO NOT
ATTEMPT TO LIFT THE CABINETS.
•DO NOT CONNECT OR DISCONNECT BATTERY CABINETS WHILE THE UPS IS
OPERATING FROM BATTERY.
SYMBOLS
Protective grounding terminal; a terminal which must be connected to ground
prior to making any other connection to the equipment.
A terminal to or from which an alternating (sine wave) current or voltage may
be applied or supplied.
A terminal to or from which a direct current or voltage may be applied or
supplied.
This symbol indicates the word “phase”.
May be used in lieu of the wording “caution, risk of electric shock” for any
cautionary marking.
M0309_N_Series_ABS_700-3kVA_User_Manual V2.8 2012-06-12 iv

Always On UPS Systems
M0309_N_Series_ABS_700-3kVA_User_Manual V2.8 2012-06-12 v
Table of Contents
1. INTRODUCTION............................................................................................................. 1
1.1. MODES OF OPERATION .................................................................................................. 1
2. PRODUCT DESCRIPTION ............................................................................................ 3
2.1. THEORY OF OPERATION................................................................................................. 3
2.2. BLOCK DIAGRAM .......................................................................................................... 3
2.3. DESCRIPTION OF EACH BLOCK ...................................................................................... 4
2.4. SPECIAL FEATURES........................................................................................................ 5
3. HANDLING....................................................................................................................... 7
3.1. DELIVERY ..................................................................................................................... 7
3.2. INITIAL INSPECTION....................................................................................................... 7
3.3. STORAGE....................................................................................................................... 7
4. INSTALLATION.............................................................................................................. 9
4.1. LOCATION ..................................................................................................................... 9
4.2. ELECTRICAL CONSIDERATIONS.................................................................................... 10
4.3. REAR VIEW DIAGRAMS ............................................................................................... 10
4.4. INPUT,OUTPUT AND EXTERNAL BATTERY CONNECTION ............................................. 11
5. START-UP/SHUTDOWN.............................................................................................. 13
5.1. TURN ON PROCEDURE:................................................................................................ 13
5.2. TURN OFF /SHUTDOWN PROCEDURE:.......................................................................... 13
6. FRONT CONTROL PANEL......................................................................................... 15
6.1. NORMAL DISPLAY....................................................................................................... 15
6.2. UPS METERS DISPLAY ................................................................................................. 15
6.3. BUTTON OPERATION ................................................................................................... 16
6.4. CONTROL PANEL FUNCTIONS ...................................................................................... 16
6.5. UPS CONFIGURATIONS................................................................................................ 16
7. AUDIBLE ALARM ........................................................................................................ 19
7.1. BACKUP MODE ............................................................................................................ 19
7.2. LOW BATTERY ............................................................................................................ 19
7.3. BYPASS ....................................................................................................................... 19
7.4. FAULT......................................................................................................................... 19
8. BATTERY MAINTENANCE........................................................................................ 19
9. ENVIRONMENTAL PROTECTION .......................................................................... 19
10. BATTERY REPLACEMENT ....................................................................................... 21
11. SOFTWARE SETUP FOR STANDARD SOFTWARE APPLICATIONS.............. 23
11.1. CONNECTING THE UPS TO A COMPUTER...................................................................... 23
11.2. RS- 232 STANDARD INTERFACE PORT.......................................................................... 23
11.3. USB PORT................................................................................................................... 23
11.4. EPO PORT (EMERGENCY POWER OFF)......................................................................... 24
11.5. NETWORK TRANSIENT PROTECTOR (700 -3000 VA)................................................... 24
11.6. LOAD SEGMENTS (700 -3000 VA) .............................................................................. 24
12. OPTIONAL EXTRAS .................................................................................................... 25
12.1. PROCEDURE FOR (OPTIONAL)EXTENDED BATTERY CABINETS .................................... 25
12.2. SNMP (NETWORK MANAGEMENT)ADAPTER (OPTIONAL).......................................... 26
12.3. AS-400 AND RELAY CONTACT (OPTIONAL)................................................................ 27
13. TROUBLESHOOTING ................................................................................................. 29
14. TECHNICAL DATA ...................................................................................................... 31
15. CONTACT INFORMATION........................................................................................ 32
15.1. ADDITIONAL PURCHASES OR UPGRADES...................................................................... 32
15.2. QA /WARRANTY QUESTIONS...................................................................................... 32
15.3. SOFTWARE QUESTIONS................................................................................................ 32

Always On UPS Systems
M0309_N_Series_ABS_700-3kVA_User_Manual V2.8 2012-06-12 vi
THIS PAGE IS INTENTIONALLY BLANK

Always On UPS Systems
M0309_N_Series_ABS_700-3kVA_User_Manual V2.8 2012-06-12 1
1. Introduction
Congratulations on your choice of the Always “On N Series On-Line Uninterruptible Power
System (UPS). The N Series features the very latest, top of the line, microprocessor technology
and IGBT transistors for clean, highly regulated, PWM (Pulse Width Modulated) True Sine
Wave power.
For ease of use, the N Series utilizes an LCD display to indicate “load percentage”, “battery
capacity”, input voltage, output voltage, input frequency, output frequency, internal UPS
temperature and the mode of operation. It also provides self-diagnostics, a combination
On/Alarm Silence/Manual Battery Test button, a combination Off/Bypass button, and two
levels of alarms when the unit is operating on battery.
The N Series incorporates an interface port for communications between the UPS and a LAN
server or other computer system with various operating systems installed. This port provides
detailed operating information including voltages, currents, and alarm status to the host system
when used in conjunction with the shutdown software. Also available are the optional SNMP
Adapter to permit remote control, monitoring and notification of UPS conditions via a network
or the internet, and an AS-400 interface to allow for relay communications in PLC or contact
environments.
1.1. Modes of Operation
The N Series UPS is designed to operate as a continuously on-line dual conversion
system in the following modes:
Normal - The critical AC load is continuously supplied by the UPS Inverter. The
input Rectifier derives power from a utility AC source and supplies power to the
Inverter while simultaneously float-charging the storage batteries.
Back-Up - Upon failure of utility AC power, the Inverter obtains power from the
batteries without interruption. There are no interruptions in power to the critical load
upon failure or restoration of the utility AC source.
Recharge - Upon restoration of utility AC power after an outage, the Rectifier will
automatically restart and supply power to the inverter and battery charger.
Automatic Restart - Upon restoration of utility AC power, after an extended outage
and complete battery discharge, the UPS will automatically restart and resume
supplying power to the critical load. Also the battery charger will automatically
recharge the batteries.
Static Bypass - The bypass will provide an alternate path for power to the critical
load and is capable of operating in the following manner:
Automatic - In the event of the inverter overload capacity being exceeded or
should an internal failure occur, the UPS will perform an automatic transfer of
the critical AC load from the inverter to the bypass source.
Manual - Should the UPS need to be taken out of service for limited
maintenance or repair, manual activation of the bypass will cause an immediate
transfer of the criticalAC load from the inverter to the bypass source. The input
rectifier, inverter, and battery charging operations will be inhibited until the user
transfers the UPS back to normal operation.

Always On UPS Systems
M0309_N_Series_ABS_700-3kVA_User_Manual V2.8 2012-06-12 2
THIS PAGE IS INTENTIONALLY BLANK

Always On UPS Systems
2. Product Description
2.1. Theory of Operation
The UPS (Uninterruptible Power Supply) is designed to be installed between utility
(commercial supplied power) and your loads. It is used to protect your loads from
noticing any power fluctuations (eg. Blackouts, brownouts, over-voltage conditions).
The UPS will supply a sufficient amount of steady, constant AC power during these
power fluctuations, allowing the loads to be shutdown properly preventing possible
damage to both hardware and software.
2.2. Block Diagram
Figure 2.2.1
Block Diagram for N Series
M0309_N_Series_ABS_700-3kVA_User_Manual V2.8 2012-06-12 3

Always On UPS Systems
M0309_N_Series_ABS_700-3kVA_User_Manual V2.8 2012-06-12 4
2.3. Description of Each Block
Input Breaker: Prevents the breaker of the distribution panel from tripping when a
UPS fault or over-current condition occurs.
EMI/RFI Filter: This filter attenuates the electrical noise associated with the
polluted utility power to the UPS or noise (THD) generated by the UPS.
Rectifier / Power Factor Correction (PFC): During normal operation, the
rectifier/power factor correction (PFC) circuit converts the utility power (AC power)
to DC power, which in turn is used by the inverter, while ensuring that the waveform
of the input current used by the UPS is close to ideal. This type of conversion and
technology maintains two key objectives: the utility power is used as efficiently as
possible, and the amount of distortion reflected back to the utility is minimized
therefore providing cleaner power to other devices in the building not being protected
by the N Series.
PFC Control: By utilizing control circuits, the current drawn from the utility
power is in-phase with the input voltage. The control circuit also allows the
UPS to have a broader input voltage range (±25%).
Charger: During normal operation, it converts AC voltage drawn from utility power
into regulated DC voltage, which charges or maintains the batteries at the desired
level by a float charge.
Batteries: Sizes will vary in series and series-parallel configurations. Batteries are
Sealed Lead-Acid Valve regulated gel cells.
DC-to-DC Converter: The converter utilizes energy from the battery system and
raises the DC voltage to the DC Bus operating voltage for the inverter. This allows
the inverter to operate continuously at its optimum efficiency and voltage, thus
increasing reliability.
Inverter: The term inverter will denote the solid-state equipment and controls used
to convert power from the input rectifier or batteries to regulated pure sine wave AC
power for supporting the loads. The inverter will produce 50 or 60Hz (auto-
selectable) using Insulated Gate Bipolar Transistors (IGBT’s) switching at
approximately 18kHz, above the audible frequency range, and without low frequency
magnetic components. The inverter is of pulse width modulated (PWM) design
capable of providing the specified AC output with a very small tolerance (±2%), with
little to no distortion.
CPU/Control/User Interface: The CPU controller monitors and maintains all
systems within the UPS while permitting communication between the UPS, user and
peripheral devices.
Static By-pass: A static transfer switch and bypass circuit is provided as an integral
part of the UPS. The inverter has an overload rating of 125% rated load for one
minute, 150% rated load for 20 seconds, 200% rated load for one and a half cycles.
The static bypass will auto transfer to bypass if these overload conditions are
exceeded. The static transfer switch control logic will contain an automatic transfer
control that senses the status of the inverter logic signals, and operating and alarm
conditions. This control circuit will provide an uninterrupted transfer of the load to a
normal input source (or alternate bypass source). Transfers are made when an
overload or malfunction occurs within the UPS, without exceeding the transient limits
specified herein.

Always On UPS Systems
M0309_N_Series_ABS_700-3kVA_User_Manual V2.8 2012-06-12 5
2.4. Special Features
Efficiency Optimizer function
The Efficiency Optimizer function adds cost effectiveness, minimizes power loss and
reduces power consumption. Alternating between bypass and on-line modes is
achieved automatically and in accordance with the conditions of the utility AC power.
On-line mode may be used during times of intermittent power, and bypass mode
when the utility is within selectable parameters in order to obtain greatest efficiency.
Irregularities can be detected in less than a second, and on-line mode reactivated
immediately. Switching back to on-line mode occurs when input voltage is outside
±10% of nominal (± 15% selectable), when input frequency is outside of ±3Hz or
when no input utility is present.
Although high efficiency is standard, the default operation is in on-line mode. The
bypass can be activated in the LCD panel, though on-line can be run permanently if
preferred.
Free Run Mode
The UPS operates in free run mode when input frequency is outside of the selected
Input Frequency Setting (Chapter 6.5). Free run mode is when output frequency does
not match input frequency. When starting the UPS, the frequency regulation detected
is 50 or 60 Hz ±0.25Hz. Please refer to chapter 6.5 if you want bypass available while
running in free run mode.
Diagnostic tests
When you start the UPS, a diagnostic test is automatically executed that checks
electronics, battery, and reports any problems on the LCD display.
An advanced battery management system always monitors the conditions of the
batteries sending any forewarnings if replacement is needed. Otherwise every 30 days
of normal operation, a battery discharge test is performed and, if a problem arises it
will be reported on the LCD display.
Other than during the initial 24 hours, after startup, or while the UPS is in charging
mode, diagnostic tests (please see chapter 6.5) can be performed manually from the
front panel at any time.

Always On UPS Systems
M0309_N_Series_ABS_700-3kVA_User_Manual V2.8 2012-06-12 6
THIS PAGE IS INTENTIONALLY BLANK

Always On UPS Systems
3. Handling
3.1. Delivery
Upon receiving the UPS system, inspect the packaging integrity and the physical
condition of the cabinet carefully.
In the event that physical damage is visible, the carrier must be informed immediately
and a claim filed with them. Inform Always “On as soon as the claim has been filed
and a copy of claim should be faxed to Always “On at (250) 491-9775.
A detailed report of the damage is necessary for carrier insurance claim.
3.2. Initial Inspection
Unpack the UPS carefully, notice the packing method, and retain the box and packing
material. If you must return the UPS at any time, you must repack it the way it was
originally shipped. Visually inspect the UPS for damage that may have occurred
during shipment. If there is damage, or anything is missing, contact the dealer from
whom you purchased the unit, and save the packaging for future shipment. When the
unit has passed the initial inspection, record the Installation date on the back panel of
the unit and in the space provided towards the front of this manual.
Included with UPS System:
1. User manual
2. Communication cable
3. Software package
4. Power Cord (for the 700VA, 1kVA and 1.5kVA UPS systems only).
3.3. Storage
1. If the on-line UPS is to be stored prior to installation, it should be placed in a
dry, well-ventilated area where it will not be exposed to dirt, moisture or other
contaminants.
2. Extreme storage temperatures are:
a. -30ºC to +60ºC without battery
b. -20ºC to +45ºC with battery for a short period
3. Maximum storage period for battery is 6 months at 20ºC or 3 months at 30ºC.
Important:
1. When the UPS and/or battery banks are to be stored for longer than 3 months, it is
recommended the batteries are recharge every 3 months.
2. Do not stack these units.
M0309_N_Series_ABS_700-3kVA_User_Manual V2.8 2012-06-12 7

Always On UPS Systems
M0309_N_Series_ABS_700-3kVA_User_Manual V2.8 2012-06-12 8
THIS PAGE IS INTENTIONALLY BLANK

Always On UPS Systems
4. Installation
The UPS is intended for installation in a temperature-controlled indoor area, free of conductive
contaminants. Installation should be conducted by qualified individuals.
4.1. Location
The N Series UPS is intended for installation in a temperature and humidity
controlled indoor environment, free of conductive contaminants with unrestricted
airflow. Ambient temperature must not exceed 40ºC (104ºF).
IMPORTANT: Maximum battery life is obtained by placing the battery in a room at
an ambient temperature of 15ºC to 25ºC. Battery life decreases by half for every
10ºC above 25ºC.
Air vents are located on the front, rear and sides of the UPS system. Do not position
the UPS in an enclosed area with restricted airflow. Allow a minimum of 100mm (4
inches) around the UPS, with a minimum of 300mm (12 inches) at the rear for easy
operator access to the connections and the rear panel mounted
input/output/battery/maintenance breakers. (Figure 4.1.1)
Maintenance and Servicing of the N Series requires access to all sides of the UPS
system and battery banks. Provide the necessary free space and flexible wiring to
allow complete access to the UPS system.
Figure 4.1.1
Top View
M0309_N_Series_ABS_700-3kVA_User_Manual V2.8 2012-06-12 9

Always On UPS Systems
4.2. Electrical Considerations
The UPS shall be installed by a qualified technician and wired in accordance with
local and national electrical codes.
The following information is for recommendation only.
Standard Load VA Rating F (Hz) Panel
Breaker Size Input Output
Voltage Current Voltage Current
700VA/490W 700VA (110) 50/60 15A 87-140Vac 9A max 120V 5A
1000VA/700W 1000VA (110) 50/60 15A 80-138Vac 12A max 120V 8.3A
1000VA/700W 1000VA (220) 50/60 15A 160-276Vac 6A max 208/220 4.8A/4.55A
1500VA/1050W 1500VA (110) 50/60 15A 80-138Vac 18A max 120V 12.5A
1500VA/1050W 1500VA (220) 50/60 15A 160-276Vac 9A max 208/220 6.2A
2000VA/1400W 2000VA (110) 50/60 20A 80-138Vac 20.3A max 120V 12.6A
2000VA/1400W 2000VA (220) 50/60 15A 160-276Vac 10.2A max 208/220 9.61A/9.1A
3000VA/2100W 3000VA (110) 50/60 30A 80-138Vac 30.5A max 120V 24.9A
3000VA/2100W 3000VA (220) 50/60 20A 160-276Vac 14.7A max 208/220 14.4A/13.6A
Table 4.2.1 Electrical information for proper installation, breaker and cable ratings
4.3. Rear View Diagrams
Interface
(optional) EPO Rs232/Dry Contact
Inerface
Network
Transient
Pro t e c t o r
Circuit
Breaker
Input
Outlet
USB
Externa l
Battery
(optional)
Interface
(optional) EPO Rs232/Dry Contact
Inerface
Network
Transient
Pro t e c t o r
Circuit
Bre a ke r
Input
Outlet
USB
Externa l
Battery
(optional)
M0309_N_Series_ABS_700-3kVA_User_Manual V2.8 2012-06-12 10
Figure 4.3.1
Rear view of the 700VA, 1kVA, 1.5kVA UPS 120VAC Figure 4.3.2
Rear view of the 700VA, 1kVA, 1.5kVA UPS 220VAC

Always On UPS Systems
4.4. Input, Output and External Battery
Connection
The 700VA, 1,000VA and 1,500VA (701N, 102N and 152N) come with a 6’ cord,
complete with a 5-15P connection that will plug into a regular wall receptacle (Figure
4.4.1).
The 2,000VA and 3,000VA have a terminal strip connection to which will require a
connection to a cord to (Figure 4.4.2). Ensure that the cable is long enough to place
the UPS system and allow for maintenance on the UPS system in the future (See 4.1
Location).
The cable sizes, input breakers/outlets and distribution methods used during
installation are subject to the local and national electrical codes of practice,
therefore are not detailed here.
Permanent wiring must be routed to the terminal strip using appropriate materials as
required by local and national codes.
External battery bank connections are described later in this manual.
Ensure UPS is provided with an adequate ground (earth).
Figure 4.4.1
700VA, 1,000VA and 1,500VA input connection
M0309_N_Series_ABS_700-3kVA_User_Manual V2.8 2012-06-12 11
Figure 4.4.2
2,000VA and 3,000VA input connection
EXT BATT
B+ INPUT
B- I/P
LI/P
NI/P
GND
OUTPUT
O/P
GND O/P
L
O/P
N

Always On UPS Systems
M0309_N_Series_ABS_700-3kVA_User_Manual V2.8 2012-06-12 12
THIS PAGE IS INTENTIONALLY BLANK
This manual suits for next models
1
Table of contents
Other Always “On” UPS UPS manuals

Always “On” UPS
Always “On” UPS M4101 User manual

Always “On” UPS
Always “On” UPS DC UPS Systems User manual

Always “On” UPS
Always “On” UPS GES-325V User manual

Always “On” UPS
Always “On” UPS GES-242NX-R Setup guide

Always “On” UPS
Always “On” UPS GES-801V User manual

Always “On” UPS
Always “On” UPS Limousin II User manual