Always “On” UPS GES-801V User manual

Always “On” UPS Systems Inc.
GES V-Series – Single Phase Input, Single Phase
Output
Uninterruptible Power Supply
GES-801V, GES-102V, GES-102VR, GES-152V, GES-152VR,
GES-222V, GES-222VR
Line Interactive (PWM): 800VA, 1kVA, 1.5kVA, 2.2kVA
User Manual
M0102_V_Series_801-222V_Manual V2.3 2012-06-12

Always “On” UPS Systems Inc.
SAVE THESE INSTRUCTIONS
This manual contains important instructions for the GES-801V, GES-102V, GES-102VR,
GES-152V, GES-152VR, GES-222V, GES-222VR and should be followed during installation
and maintenance of the UPS and batteries.
The UPS contains voltages that are potentially hazardous. Please contact our dealers or
qualified personnel for service.
Servicing of the batteries should be performed or supervised by personnel knowledgeable with
batteries and the required precautions. Keep unauthorized personnel away from batteries.
When replacing batteries, replace with the same model number, type and rating.
CAUTION: Do not dispose of battery or batteries in a fire. The batteries may explode.
CAUTION: Do not open or mutilate the battery or batteries. Released electrolyte is harmful
to the skin and eyes. It may be toxic.
CAUTION: A battery can present a risk of electrical shock and high short circuit current.
The following precautions should be observed when working on or with the batteries.
−Remove watches, rings, or other metal objects.
−Use tools with insulated handles.
−Wear rubber gloves and boots.
−Do not lay tools or metal parts on top of batteries.
−Disconnect charging source prior to connecting or disconnecting battery terminals.
−Determine if the battery is inadvertently grounded. If inadvertently grounded, remove
source of ground. Contact with any part of a grounded battery can result in electric
shock. The likelihood of a shock will be reduced if grounds are removed during
installation and maintenance (applicable to a UPS and a remote battery supply not
having a grounded supply circuit).
CAUTION: To ensure the safety and performance of the UPS, never load the UPS with a hair
dryer, heater, laser printer or other types of inductive loads.
M0102_V_Series_801-222V_Manual V2.3 2012-06-12

Always “On” UPS Systems Inc.
SAFETY INSTRUCTIONS
1. The UPS has its own internal energy source (battery), therefore the output receptacles may
have electricity present even though the UPS is disconnected from the utility power.
2. The DC voltage provided from the internal battery is 24Vdc for 801V, 102V, 152V,
102VR, 152VR. 48Vdc for 222V, 222VR.
3. The isolated ground wire (green or green with yellow stripe) must meet national wire
requirements.
4. The power plug to connect with the UPS has to be equipped with a ground plug.
5. Battery must be replaced or serviced by qualified, knowledgeable, personnel.
6. Replacement battery must be the type, quantity and configured the same as the
original(s).
7. To avoid explosions, keep open flame and other heat emitting sources away from
battery.
8. Do not disassemble or damage the battery. The electrolyte is toxic and especially
harmful to the eyes and skin.
9. The battery contains high voltages and currents that are dangerous. To maintain secure
operation and performance of the UPS, the user must exercise basic and regular
maintenance.
10. Please follow the precautions below when dealing with the UPS:
1. Do not remove the UPS cover unless authorized by factory. Removing the cover
will void the warranty.
2. The UPS can only be connected to a 2-pole/3-wire plug.
3. Do not install the UPS in an environment with excessive humidity.
4. Do not allow liquids or foreign objects to get inside the UPS.
5. Allow for air circulation through the UPS. A minimum clearance of 10cm is
required on all sides.
6. Do not load the UPS with appliances such as a hair dryer, heater, vacuum, kettle,
etc.
7. Keep the UPS away from direct sunlight and heat-emitting sources.
8. Install the UPS as close as possible to the load for maximum protection.
11. Storage Requirements
1. Recharge the UPS batteries every 6 months for no less than 8 hours at a time.
2. Under a high ambient temperature environment, recharge the UPS batteries every
3 months for no less than 8 hours at a time
12. High Voltage Risk:
1. High voltages might exist between the battery terminal and the grounding
system, if the battery circuit has not been disconnected from the UPS circuit.
Please check this voltage before connecting.
2. Disconnect the battery wires before proceeding with maintenance. High voltages
may be present between the UPS internal components and battery even after the
input power is disconnected.
M0102_V_Series_801-222V_Manual V2.3 2012-06-12

Always “On” UPS Systems Inc.
M0102_V_Series_801-222V_Manual V2.3 2012-06-12
Table of Contents
1. INTRODUCTION 1
2. PRESENTATION 2
2.1. Front Panel 2
2.2. Rear Panel 4
3. INSTALLATION 6
3.1. Unpacking and Inspection 6
3.2. Placement 6
3.3. Connect Computer Interface (Optional) 6
3.4. Connect to Utility 6
3.5. Charging the Battery 6
3.6. Connecting the Loads 6
3.7. Connecting the Telephone / Modem / Ethernet Lines (Optional) 7
3.8. Storage Conditions 7
3.9. Extended Storage 7
4. OPERATION 8
4.1. Switching “On” the UPS 8
4.2. Switching “Off” the UPS 8
4.3. Self-Test 8
4.4. Silence the Alarm 8
4.5. Cold Start 8
4.6. Shutdown Mode 9
4.7. Green Function 9
5. AUDIBLE ALARM 10
5.1. Back-Up (Slow Alarm) 10
5.2. Low Battery (Rapid Alarm) 10
5.3. Overload (Continuous Alarm) 10
5.4. Replace Battery (Continuous Alarm) 10
6. SOFTWARE OPTIONS 10
6.1. UPSMON Software 10
6.2. Interface Kits 10
6.3. Computer Interface Port 11
6.4. Open Collector (Dry Contact) Communication 11
6.5. RS-232 Communication 11
7. BATTERY REPLACEMENT 13
8. TROUBLESHOOTING 14
8.1. General Problems 14
9. TOWER SPECIFICATIONS 15
10. RACK MOUNT SPECIFICATIONS 16
11. CONTACT INFORMATION 18
11.1. Additional Purchases or Upgrades 18
11.2. QA / Warranty Questions 18
11.3. Software Questions 18

Always “On” UPS Systems Inc.
M0102_V_Series_801-222V_Manual V2.3 2012-06-12 1
1. INTRODUCTION
The V-Series is a Line Interactive UPS system that includes the newest and latest
technology enhancements. The Line Interactive technology with AVR function (on-line
voltage boost-up & buck-down) allows for a wide input voltage range of 90 to 150VAC.
The V-Series UPS is ideal protection for microprocessor control loads. After the UPS
has been turned “On” it will protect the load from transients, spikes and other power
aberrations. In the event of a blackout (or severe brownout) the UPS will automatically
switch to back-up mode and maintain power to the load until the software shuts down the
system or when the battery reaches a low voltage state. Also included with our UPS
systems is a cyclic self-testing function to verify both the operation of the UPS and the
condition of the battery.
In addition, the V-Series UPS provides advanced telephone line and Ethernet surge
suppression through the modular connectors on the back panel.
The Line Interactive UPS in conjunction with our monitoring software makes your
UPS operate intelligently and provides you with total protection for all your loads.
Interference to Radio / TV
If this UPS causes interference to radio or television reception, which can be
determined by turning the UPS off and on, the user can attempt to correct the
interference by one or more of following measures:
1. Connect the equipment to an outlet on a circuit different from the one that the
receiver is connected.
2. Increase the separation between the equipment and the receiver.
3. Re-orientate the receiving antenna.

Always “On” UPS Systems Inc.
2. PRESENTATION
2.1. Front Panel
M0102_V_Series_801-222V_Manual V2.3 2012-06-12 2
Figure 2.1.2
102VR Front Panel
78915 610
Figure 2.1.1
Tower Front Panel.
Always
"O
n"
I
1
2
3
4
5
6
Figure 2.1.3
152/222VR Front Panel.
ILine Mode
Boost
INV Mode
Buck
Battery Fault Always"On"
1 2 36 5 4

Always “On” UPS Systems Inc.
M0102_V_Series_801-222V_Manual V2.3 2012-06-12 3
1REPLACE BATTERY indicator (RED LED)
This LED illuminates when the UPS's batteries are no longer useful and
must be replaced.
Note: When replacing the batteries, disconnect the utility power and then
open the case. Take notice of the polarity before installing the new
batteries to avoid a short.
2BUCK AVR (VOLTAGE REDUCTION) indicator (YELLOW LED)
This LED illuminates when the UPS is correcting a high utility voltage
condition. The loads receive normal power.
3BACK-UP indicator (YELLOW LED)
This LED illuminates when the UPS is supplying battery power to the
loads.
4BOOST AVR (VOLTAGE BOOST) indicator (YELLOW LED)
This LED illuminates when the UPS is correcting a low utility voltage
condition. The loads receive normal power.
5LINE NORMAL indicator (GREEN LED)
This LED illuminates when the line-input voltage is normal. (RM version;
also flashes to indicate Backup mode)
6ON/OFF/TEST/SILENCE button (TEST / SILENCE for GES-102VR).
Press and hold the button for more than 3 seconds to turn the UPS “ON”
or “OFF” (not applicable to GES-102VR). Press and hold the button less
than 1 second to activate a self-test, or silence the back up alarm.
7UPS OUTPUT SEGMENT 1 ON / OFF SWITCH
This switch allows independent ON / OFF control of UPS output segment
1 outlets on rear panel.
8UPS OUTPUT SEGMENT 2 ON / OFF SWITCH
This switch allows independent ON / OFF control of UPS output segment
2 outlets on rear panel.
9BYPASS ON/OFF SWITCH
This switch allows independent ON / OFF control of the surge-protected
outlet on rear panel. (This outlet is not supplied backup power in the event
of a power outage)
10 MAIN POWER
This toggle switch is the main power cutoff for the UPS. Use of this
switch will remove power from loads and completely shutdown the UPS.

Always “On” UPS Systems Inc.
2.2. Rear PanelRear Panel
1
23
4
5
7 8
1
3
2
6
8
7
Figure 2.2.1
Rear Panel
Left GES-801, 102, 152V
Ri
g
ht GES-222V
2 3 8 7 5 6
Figure 2.2.2
Rear Panel GES-102VR
OUTPUT
REMOTE
PORT
BREAKER INPUT
IN OUT
3
M0102_V_Series_801-222V_Manual V2.3 2012-06-12 4
8 7 26
Figure 2.2.
Rear Panel GES-3
152VR
OUTPUT
REMOTE
INPUT
BREAKER
3 68 27
Figure 2.2.2
Rear Panel GES-222VR

Always “On” UPS Systems Inc.
M0102_V_Series_801-222V_Manual V2.3 2012-06-12 5
1MAIN POWER
This toggle switch is the main power cutoff for the UPS. Use of this
switch will remove power from loads and completely shutdown the UPS.
2COMPUTER INTERFACE
Both RS-232 and relay signal (Dry Contact) Interfaces are supplied to
support WINDOWS, NOVELL, UNIX, DOS, and other operating
systems.
3TELEPHONE / MODEM / ETHERNET SURGE PROTECTION
Surge protection for telephone line, modem line, and 10BaseT line to
maintain a completely safe connection for INTERNET / INTRANET
service.
4SITE WIRING FAULT INDICATOR (RED LED)
Illuminates when the UPS is connected to an improperly wired AC power
outlet.
Note: This device is available on 110 VAC models only.
5SURGE PROTECTION OUTLET ONLY <NO BACKUP>
This full time surge protection outlet provides protection from surges such
as those created by lightning or connected equipment that has high initial
current. Plug in equipment that does not require power during a blackout,
this could include a printer, scanner, fax, audio device, etc.
6OUTPUT POWER RECEPTACLES
7AC INPUT POWER RECEPTACLE
8INPUT CIRCUIT BREAKER
Trips when the connected loads exceed the protected receptacle's capacity.
The center plungers of the circuit breakers extend when tripped.

Always “On” UPS Systems Inc.
3. INSTALLATION
3.1. Unpacking and Inspection
Examine the packaging for damage. Inform the carrier immediately if damage
is noticed. Retain the packaging for future use.
3.2. Placement
Install the UPS in a protected area with adequate airflow and free of excessive
dust. Do not operate the UPS where the temperature and humidity is outside
the specified limits.
3.3. Connect Computer Interface (Optional)
UPSMON (or other power management software) and an interface kit can be
used with this UPS. Use only kits supplied or approved by the manufacturer.
If used, connect the interface cable to the 9-pin computer interface port on the
back panel of the UPS (See Back Panel). This is optional; UPS will work
properly without a computer interface connection.
3.4. Connect to Utility
Connect the AC input power connector (Included) to utility power.
3.5. Charging the Battery
The UPS charges its battery whenever the UPS is in LINE mode. For best
results, charge the battery for 4 hours initially before connecting the load.
3.6. Connecting the Loads
Plug the loads into the output connectors on the rear of the UPS. To use the
UPS as a master on/off switch, make sure all of the loads plugged into the
UPS are switched on.
Caution:
Never connect a laser printer or plotter to the UPS with other computer
equipment. A laser printer or plotter draws significantly more power on
start-up than when idle, and will overload the UPS. If a laser printer
or plotter requires protection against blackouts, brownouts and over-
voltage the UPS needs to be increased in size to accommodate the
inrush o
f
p
ower.
M0102_V_Series_801-222V_Manual V2.3 2012-06-12 6

Always “On” UPS Systems Inc.
3.7. Connecting the Telephone / Modem / Ethernet Lines (Optional)
Caution:
The line current limiting feature could be rendered inoperable if
improperly installed. Make sure that the line from the wall is plugged
into the connector marked “IN”, and the device to be protected
(telephone, modem, etc.) is plugged into the connector marked “OUT”.
This surge protection device is for indoor use only; never install wiring
during a lightning storm.
Connect a telephone line, modem line, or 10BaseT line into the telephone /
modem / ethernet surge protection sockets on the back of the UPS. The RJ-45
/ RJ-11 modular sockets accept standard single line telephone connections and
10BaseT connectors. This connection will require another length of cable.
This is optional; UPS will work properly without this connection.
3.8. Storage Conditions
Store the UPS covered and upright in a cool, dry location, with its battery fully
charged. Before storing, charge the UPS for at least eight (8) hours. Remove
any accessories in the accessory slot and disconnect any cables connected to
the computer interface port to avoid the unnecessary draining of the battery.
3.9. Extended Storage
During extended storage periods in environments where the ambient
temperature is -15 to +30°C (+5 to +86°F), charge the UPS‘s battery every 6
months.
During extended storage in environments where the ambient temperature is
+30 to +45°C (+86 to +113°F), charge the UPS‘s battery every 3 months.
M0102_V_Series_801-222V_Manual V2.3 2012-06-12 7

Always “On” UPS Systems Inc.
M0102_V_Series_801-222V_Manual V2.3 2012-06-12 8
4. OPERATION
4.1. Switching “On” the UPS
For all but the GES-102VR:
With the UPS plugged in and utility power present, press and hold the On /
Off / Test / Silence Button more than 3 seconds or until the LED is lit. The
UPS will perform self-testing each time it is switched “On”.
For the GES-102VR:
With the UPS plugged in and utility power present, turn the Main Power
toggle switch to the “On” position. The UPS will perform self-testing each
time it is switched “On”.
4.2. Switching “Off” the UPS
For all but the GES-102VR:
Press and hold the On / Off / Test / Silence Button for more than 3 seconds, or
until the Line Normal or Back-Up LED turns off.
For the GES-102VR:
Turn the Main Power toggle switch to the “Off” position.
4.3. Self-Test
Use the self-test to verify both the operation of the UPS and the condition of
the battery. When normal utility power is present, push the On / Off / Test /
Silence (Test / Silence for GES-102VR) Button for less than 1 second. During
the self-test, the UPS operates in back-up mode.
During the self-test, the UPS briefly operates the loads with battery power
(the LED flashes every 2 seconds). If the UPS passes the self-test, it
returns to on-line operation. The LED stops flashing and the LED
remains on. If the UPS fails the self-test it immediately returns to on-line
operation. The loads are unaffected when performing a self-test.
Recharge the battery overnight and perform the self-test again. If the
UPS still fails a self-test, ask our nearest dealer to replace the battery.
4.4. Silence the Alarm
In Back Up mode, push On / Off / Test / Silence (Test / Silence for GES-
102VR) Button for less than 1 second to silence the audible alarm. (This
function will not work when the UPS is in "LOW BATTERY" or
"OVERLOAD" condition.)
4.5. Cold Start
When the UPS is off and there is no utility power, use the cold start feature to
apply power to the loads from the UPS's battery. Press the ON / TEST button
(see Front Panel section for location of the indicator) until the UPS beeps.

Always “On” UPS Systems Inc.
M0102_V_Series_801-222V_Manual V2.3 2012-06-12 9
4.6. Shutdown Mode
In shutdown mode the UPS stops supplying power to the load and waits for
the return of utility power. If there is no utility power present, external devices
(e.g., servers) connected to the computer interface can command the UPS to
shutdown. This is normally done to preserve battery capacity after the graceful
shutdown of protected servers.
4.7. Green Function
In order to conserve battery power when in backup mode the UPS will
automatically shutdown after 5 minutes if the connected loads are operating at
less than 20 watts.
To disable “GREEN FUNCTION” press and hold the “On” button during
initial start-up for at least 3 seconds until a beep-beep sound is heard.

Always “On” UPS Systems Inc.
5. AUDIBLE ALARM
5.1. Back-Up (Slow Alarm)
When in back-up mode, the LED flashes every 2 seconds and the UPS sounds
an audible alarm. The alarm stops when the UPS returns to line normal
operation. Press the On / Off / Test / Silence Button during back-up mode to
silence the beeping.
5.2. Low Battery (Rapid Alarm)
In back-up mode, when the battery energy runs low, the UPS beeps rapidly
until the UPS shuts down from battery exhaustion or returns to line normal
operation.
5.3. Overload (Continuous Alarm)
When the UPS is overloaded (the connected load exceeds the maximum rated
capacity of the UPS) the UPS sounds a continuous alarm to warn of an
overload condition. Disconnect non-essential loads until the UPS stops the
alarm.
5.4. Replace Battery (Continuous Alarm)
The UPS emits a continuous beep if the battery fails the self-test. See replace
battery section for battery replacement or call your dealer for service.
6. SOFTWARE OPTIONS
6.1. UPSMON Software
The UPSMON software uses the standard RS-232 interface to perform
monitoring functions and then provides an orderly shutdown of a computer in
the event of power failure. Moreover, UPSMON displays all diagnostics
through a graphical display, such as Voltage, Frequency, Battery Level, etc.
The software is available for DOS, Windows 3.1x, Windows 95 / 98 / 00 / XP
& Windows NT V3.5 or later.
6.2. Interface Kits
A series of interface kits are available for various operating systems that
provide UPS monitoring. Each interface kit includes the special interface
cable required to convert status signals from the UPS into signals that the
individual operating system will recognize. The interface cable at the UPS
side must be connected to the REMOTE PORT, at the computer side it can be
connected to either COM1 or COM2. For other installation instructions and
powerful features please refer to READ ME file included within the software.
Caution:
Use only factory supplied or authorized UPS monitoring kits!
M0102_V_Series_801-222V_Manual V2.3 2012-06-12 10

Always “On” UPS Systems Inc.
M0102_V_Series_801-222V_Manual V2.3 2012-06-12 11
6.3. Computer Interface Port
The communication port on the back of the UPS may be connected to a host
computer. This port allows the computer to monitor the status of the UPS and
control the operation of the UPS. Its major functions include the following:
1. The ability to broadcast a warning when the power fails.
2. The ability to close any open files before the battery reserves are
exhausted.
3. The ability to turn off the UPS.
4. The ability to make the UPS perform a self-test.
Some computers are equipped with a serial connector to link with the
communication port, in some cases a special plug-in card may be needed.
6.4. Open Collector (Dry Contact) Communication
[Pins for the GES-801V, ES-102V and GES-152V]G
(Pins for the GES-222V)
1. Pin [8] (5) and [6] (2) are open collector outputs that must be pulled up
to a common referenced supply no greater than +40VDC.
2. The transistors are capable of a maximum non-inductive load of
25mADC, use pin [5] (4) as the common.
3. Pin [8] (5) generates a High to Low signal when the battery inside the
UPS has less than 5 minutes back up time left.
4. Pin [6] (2) generates a High to Low signal when the line has failed.
Pin [3] (7) will shut down the UPS is a high is sustained for 0.36
seconds.
6.5. RS-232 Communication
[Pins for the GES-801V, GES-102V and GES-152V]
(Pins for the GES-222V)
5. Pin [3] (7) is the RS-232 data input from computer (RX).
6. Pin [2] (6) is the RS-232 data output to computer (TX).
7. Pin [4] (8) is the RS-232 data transmit bit (DTR).
8. Pin [7] (9) is the RS-232 data receive bit (RTS).
9. Pin [5] (4) is the common or computer ground.
NOTE:
1. Switch rating +40V, 25mADC non-inductive.
2. Pin 7 should be connected to computer ground only.

Always “On” UPS Systems Inc.
M0102_V_Series_801-222V_Manual V2.3 2012-06-12 12
1
2
3
4
5
6
7
8
9
1
2
3
4
5
6
7
8
Low Battery
Mains Failure
Common
UPS Shut Down or
RS-232 RD (PIN 3)
RS-232 TX (PIN 2)
RS-232 RTS (PIN 7)
RS-232 DTR (PIN 4)
Contacts
Normally
Open
Signal High Minimum 1 Second
DB-9 Pin Configuration for the GES-801V, 102V, and 152V
1
2
3
4
5
6
7
8
9
3
6
7
8
4
2
9
5
Low Battery
Mains Failure
Common
UPS Shut Down or
RS-232 RD (PIN 3)
RS-232 TX (PIN 2)
RS-232 RTS (PIN 7)
RS-232 DTR (PIN 4)
Contacts
Normally
Open
Signal High Minimum 1 Second
DB-9 Pin Configuration for the Purple Cable (GES-222V)

Always “On” UPS Systems Inc.
7. BATTERY REPLACEMENT
M0102_V_Series_801-222V_Manual V2.3 2012-06-12 13
Your battery should run anywhere from 3-5 years before it needs to be replaced.
Please follow the instructions below for easy, trouble free, battery replacement.
1. Turn the UPS off (follow procedure previously mentioned).
2. Unplug the UPS from utility power source and disconnect all connected loads.
3. Disconnect AC power cord from unit.
4. For the 801V / 102V / 152V / 222V: Pull on the top of the faceplate until the 2 top
tabs release. Remove the faceplate and set to the side.
For the 152 / 222VR: Using a Phillips screwdriver, remove the 2 screws holding
the faceplate on. Remove the faceplate and set to the side.
For the 102VR: Turn the UPS upside down. Using a Phillips screwdriver remove
the 4 screws holding the top to the bottom. Flip the UPS right side up. Remove
the 8 screws for the handles and the one screw on the back.
5. For the 801V / 102V / 152V / 222V: The battery retainer plate should be visible.
Using a Phillips screwdriver remove the screw at the battery plate and set the
plate to the side.
For the 152 / 222VR: The battery retainer plate should be visible. Using a Phillips
screwdriver remove the 3 screws holding the battery retainer plate on and set
the plate to the side.
For the 102VR: From the back pull the top cover off of the UPS.
6. For the 801V / 102V / 152V / 222V: Carefully pull the batteries out of the UPS.
Remove the connecting wires noting polarity.
For the 152 / 222VR: Carefully pull the batteries out of the UPS using the white
tab hanging in front of the batteries. Remove the connecting wires noting
polarity.
For the 102VR: Remove the connecting wires from the batteries noting polarity.
7. You can now easily remove the battery from the unit
8. Place your new battery in the same position, direction and reconnect the wires.
The red wire to the positive (+) pole and black wire to the negative (-) pole.
9. Reverse the above steps to reassemble the unit.
10. Follow start-up instructions in order to properly reconnect your equipment.
Caution:
Do not dispose of battery in a fire. Do not attempt to open the battery.
When replacing the battery use tools with insulated handles and
remove watches, rings, etc…
WARNING:
Completing the procedure below will void any remaining warranty on
the UPS s
y
stem.

Always “On” UPS Systems Inc.
M0102_V_Series_801-222V_Manual V2.3 2012-06-12 14
8. TROUBLESHOOTING
Please follow the guidelines below for common problems:
9Check UPS input plug and wiring.
9Check UPS input voltage.
Please prepare the information as follows for service personnel:
9UPS model number and serial number
9Description of problem(s) in detail.
8.1. General Problems
Problems Possible causes Solution
UPS has no reaction while
AC power is connected
Breaker at back panel open
No AC input
UPS fault
Battery failure
Replace Fuse / Switch breaker on
Check AC power
Call for service
Call service center to replace batteries
UPS has no reaction while
AC power is connected, yet
starts after pushing power
on/off switch
Breaker at back panel open
No AC input
UPS AC detecting circuit fail
Switch breaker
Check AC power
Call for service
UPS goes into back-up mode
while connected to AC power
Utility voltage or frequency
abnormal
UPS AC detecting circuit failure
Check AC power
Call for service
Battery can not provide
normal back-up power in the
event of a blackout
Battery deteriorated
Batteries not fully charged
Battery charger damaged
Charge batteries and reset
If that doesn’t work call for service
After AC connected to UPS,
alarm sounds short and fast
beeps and UPS shuts down Abnormal utility power Check input power

Always “On” UPS Systems Inc.
M0102_V_Series_801-222V_Manual V2.3 2012-06-12 15
9. TOWER SPECIFICATIONS
M
ODEL GES-801V GES-102V GES-152V GES-222V
I
NPUT
C
apacity 800VA 1kVA 1.5kVA 2.2kVA
V
oltage 120V, 220V +/-25%
F
requenc
y
50 or 60Hz +/-5% (auto sensing)
O
UTPUT
V
oltage (on battery) Simulated sine wave at Line Input +/-5%
F
requency (on battery) 50 or 60Hz +/-0.5%
V
oltage Regulation AVR ±13% of nominal (120V)
T
ransfer Time 2/4 milliseconds, including detection time
P
ROTECTION and
F
ILTERING
Spike Protection 320 joules, 2ms
O
verload Protection UPS automatic shutdown if overload exceeds 110% of nominal for
60 second or 130% for 3 seconds.
U
nit Input Fuse for overload & short circuit protection
10BaseT/Modem Line Network (UTP, RJ-45) compatible jacks
Short Circuit UPS output cut off immediately or input fuse protection
B
ATTERY
T
ype Maintenance-free, Sealed Lead Acid
T
ypical Recharge Time 4 hours (to 90% of full capacity)
P
rotection Automatic self-test & discharge, replace battery indicator
B
ac
k
-up Time 10 - 30 minutes (depending on load)
P
HYSICAL
N
et Weight kg(lbs) 13 (28.6) 15 (33.0) 15.6 (34.3) 26.2 (57.6)
Shipping Weight kg(lbs) 14.2 (31.2) 16.2 (35.6) 16.8 (36.9) 28.2 (62.0)
D
imension mm (inches)
W
xDxH 130x382x201
(5.1x15x7.9) 169x448x227
(6.6x17.6x8.9)
I
nput Inlet IEC 320 power inlet
A
LARM
B
attery Bac
k
-Up Slow beeping sound (about 0.47Hz)
B
attery Low Rapid beeping sound (about 1.824Hz)
O
verloa
d
Continuous beeping sound
I
NTERFACE
R
S-232/Dry Contact YES
C
ONFORMANCE Safety cUL UL1778, CSA C22.2 and FCC Class B
Surge IEEE C62.41 CAT. A
E
NVIRONMENT
A
mbient Operation 6,000 meters max. elevation, 0-95% humidity non-condensing 0-
30°C
A
udible noise <40dBA (1 meter from surface)
Storage Condition 15000 meters max. Elevation
Specifications subject to change without prior notice to reflect upgrades and
improvements in technology.

Always “On” UPS Systems Inc.
M0102_V_Series_801-222V_Manual V2.3 2012-06-12 16
10. RACK MOUNT SPECIFICATIONS
V-SERIES MODEL NO. GES-801V GES-102V GES-152V
GENERAL MAXIMUM CAPACITY 800VA / 495W 1kVA / 600W 1.5kVA / 900W
UPC ORDER CODE 825433 20500
825433 20600
825433 20700
INPUT NOMINAL VOLTAGE 120VAC (optional 220VAC)
VOLTAGE RANGE + / - 25%
FREQUENCY RANGE 50 or 60 Hz (+ / - 5%)
OUTPUT
NOMINAL VOLTAGE 120VAC
VOLTAGE REGULATION + / - 13% of nominal
CURRENT 6.87A 8.33A 12.5A
FREQUENCY 50 / 60Hz (Auto Detected)
WAVEFORM
(ON BATTERY) PWM (Pulse Width Modulated) or Modifi
e
POWER FACTOR < 0.6
CREST FACTOR 3:1 (on battery)
TRANSFER TIME 2 - 4 ms (Typical)
OUTLETS 4+1 Surge 4+1 Surge 4+1 Surge
BATTERY
BATTERY TYPE SEALED LEAD ACID - MAINTENAN
C
QUANTITY 2 2 2
VOLTAGE 24VDC 48
V
RECHARGE TIME 4 HOURS; RECOVERY = 90%, T
Y
BACKUP
POWER TIME
FULL LOAD ≥10 MIN. ≥10 MIN. ≥10 MIN.
HALF LOAD ≥25 MIN. ≥25 MIN. ≥25 MIN.
PENTIUM & 17" MON ≥35 MIN. ≥35 MIN. ≥45 MIN.
PROTECTION
OUTPUT SHORT YES
ABNORMAL VOLTAGE YES
MODEM OR NETWORK SINGLE LINE (2 wire RJ-11) / NETWOR
K
COMPATIBLE JACKS
I/O NOISE PROTECTION COMMON & NORMAL MODE NOISE S
U
This manual suits for next models
6
Table of contents
Other Always “On” UPS UPS manuals

Always “On” UPS
Always “On” UPS GES-242NX-R Setup guide

Always “On” UPS
Always “On” UPS GES-701N - GES-302N ABS User manual

Always “On” UPS
Always “On” UPS DC UPS Systems User manual

Always “On” UPS
Always “On” UPS Limousin II User manual

Always “On” UPS
Always “On” UPS GES-325V User manual

Always “On” UPS
Always “On” UPS M4101 User manual