Amerex 20150 User manual

DESIGN, INSTALLATION,
MAINTENANCE & RECHARGE
MANUAL
NO. 20150
AMEREX
RESTAURANT
FIRE SUPPRESSION SYSTEM
TESTED AND LISTED BY
UNDERWRITERS LABORATORIES
TO UL STANDARD 300
and
UNDERWRITERS LABORATORIES OF
CANADA ULC/ORD 1254.6-1995*
AMEREX CORPORATION
Post Office Box 81
Trussville, Alabama 35173-0081
Phone: (205) 655-3271 Fax: (205) 655-5112
e-mail: sales @amerex-fire.com web page: www.amerex-fire.com
Printed in U.S.A. December 2008
(rev. February 14, 2019) MM#20150-9/2014
No part of this manual may be reproduced or transmitted in any form or by any means electrical or
mechanical, including photocopying or by any storage and retrieval system without the expressed
permission in writing from Amerex Corporation.
AFactory Trained and Authorized Distributor must perform the installation and service of any
Amerex Restaurant Fire Suppression System in strict accordance with this manual.
* ULC Certification does not apply to the STRIKETM or SRM.


THE NEW MANUAL – WHAT IS NEW?
This NEW Restaurant Systems Manual carries a new part number, 20150, for it
is a combining of the two previous manuals, KP Manual PN 12385 rev. “A” and ZD
Manual PN 16640. The combining of the two manuals does not eliminate any of the
limitations of system requirements of the original two manuals, but strives to organize
the information into a comprehensive order with additional informative information for
greater clarity and understanding.
Some of the changes you will notice in the new manual are made to reduce cost
of inventory, printing, manufacturing, ordering and returns. The first item you will notice
is the change in nomenclature, KP 375 or ZD 375 Agent Cylinder Assemblies are now
referred to as a Model 375 Agent Cylinder Assemble. Now there is only one part
number per Model of Agent Cylinder Assembly. No longer do you have to order a
different part number for a KP or ZD Agent Cylinder Assembly nor do you have to stock
two cylinders the same size simply because one is for a KP system and one is for a ZD
system.
Closer examination of the new manual will reveal that the original configured
MRM required that you purchase a MRM and an enclosure (painted or stainless steel)
separately. The new MRM II is supplied pre-installed in an enclosure (painted or
stainless steel) ready to mount on the wall. The new MRM II incorporates the use of a
new ratcheting take up for the automatic detection line. The original MRM used a
manual take up method for the cable tensioning and was part number 11977. The
original MRM version is no longer in production, however if a replacement for an
existing unit is needed or if you are ordering a “Cabinet” enclosure (PN 11978) you can
still order part number 11977 as a replacement or to use in the “Cabinet” enclosure.
The part number now supplies a MRM II unit without the enclosure, but with the new
ratcheting take up. It is 100% interchangeable with the original MRM.
The new manual will still contain service and maintenance instructions for the
original style MRM. Anytime you see a heading that says MRM, it is referring to the
original style unit. If the information is good for both style units it will say MRM / MRM II.
The following arrangement, MRM / MRM II / PRM, indicates that the information is good
for all three units.
Due to the combining of the two manuals the following substitutions should be
used as follows:
KP Manual PN 12385 is superseded by Restaurant Manual PN 20150
ZD Manual PN 16640 is superseded by Restaurant Manual PN 20150
ZD 275 Agent Cyl. Asy. PN 17102 is superseded by Model 275 Agent Cyl. Asy PN 16921
ZD 375 Agent Cyl. Asy. PN 16650 is superseded by Model 375 Agent Cyl. Asy PN 13334
ZD 475 Agent Cyl. Asy. PN 17474 is superseded by Model 475 Agent Cyl. Asy PN 17397
KP/ZD 375 Mounting Bracket PN 16085 is superseded by 375 Mounting Bracket PN 17690


December 2008
LIMITED WARRANTY
Amerex warrants its Restaurant Fire Suppression Systems to be free from defects in material
and workmanship for a period of three (3) years from the date of purchase. During the warranty
period, any defective part will be repaired or replaced (at Amerex option). This warranty is valid
only if each system is installed, serviced and maintained by an Amerex authorized distributor in
strict accordance with Amerex Manual No. 20150. All work must be performed using genuine
Amerex replacement parts. This Warranty does not cover defects resulting from modification,
alteration, misuse, exposure to corrosive conditions or improper installation or improper
maintenance. Warranties on component items not manufactured by Amerex are provided by
others whose warranty, evaluation and judgment will be final.
ALL IMPLIED WARRANTIES, INCLUDING BUT NOT LIMITED TO, WARRANTIES OF
FITNESS FOR PURPOSE AND MERCHANTABILITY, ARE LIMITED TO THE TIME PERIOD
AS STATED ABOVE. IN NO EVENT SHALL AMEREX CORPORATION BE LIABLE FOR
INCIDENTAL OR CONSEQUENTIAL DAMAGES. Some states do not allow limitations on how
long an implied warranty lasts or the exclusion or limitation of incidental or consequential
damages, so that the above limitations or exclusions may not apply to you.
Amerex Corporation neither assumes nor authorizes any representative or other person to
assume for it any obligation or liability other than as expressly set forth herein. This Warranty
gives you specific legal rights, and you may also have other rights that vary from state to state.
To obtain performance of the obligation of this Warranty, write to Amerex Corporation, P. O. Box
81, Trussville, Alabama 35173-0081, USA for instructions.


TABLE OF CONTENTS
Section 1 – General Information
UL Listing ...............................................................................................1-1
Design ...................................................................................................1-1
General Information Zone Defense ……………………………………...…1-2
Definition of Terms ……………………………………………………1-3 to 1-6
Revision Record …………………………………………………………….. 1-7
Section 2 – System Components
Kitchen Wet Chemical Agent .................................................................2-1
Agent Cylinder/Assembly Models 275 / 375 / 475 ..................................2-1
Cylinder Mounting Bracket .....................................................................2-2
Distribution Hose (DISCONTINUED)...........................................................2-2
Agent Cylinder/Assembly Model 600 ....................................................2-2
Cylinder Valve Assembly Model 600 ......................................................2-3
Cylinder Mounting Bracket Model 600 ...................................................2-3
Discharge Fitting Kit KP 600 ..................................................................2-3
Pneumatic Actuator …………………………………………………………..2-3
MRM / MRM II / SRM / SRM OEM .................................................2-4, 2-4a
PRM........................................................................................................2-5
Detection Tubing ....................................................................................2-5
End of Line Fitting...................................................................................2-5
Tubing Support Clip................................................................................2-5
Low Pressure Indicator ………………………………………………………2-5
Nitrogen Actuation Cylinder ...................................................................2-6
Enclosure MRM .....................................................................................2-6
Cabinet ..................................................................................................2-6
Actuation Hose & Discharge Nozzle.......................................................2-7
Nozzle Swivel Adapter & Nozzle Caps ..................................................2-7
Detector .................................................................................................2-8
Test Links ..............................................................................................2-8
Corner Pulley .........................................................................................2-8
Cable & Eyebolt Support.........................................................................2-8
JOB & Globe Fusible Links ....................................................................2-9
Conduit Offset ........................................................................................2-9
Linear Fusible Link Termination Kit ……………………………………… 2-9
Cable Segment – Link to Link ……………………………………………… 2-9
Manual Pull Station ..............................................................................2-10
Adapters ..............................................................................................2-10
Quick Seal Compression Fitting............................................................2-10
Mechanical Gas Valve..........................................................................2-11
Electric Gas Valve.................................................................................2-11
Manual Reset Relay..............................................................................2-11
Mechanical Gas Valve Kit.....................................................................2-12
ASCO Mechanical Gas Valve...............................................................2-13
Ansul Mechanical Gas Valve................................................................2-13
Snap Action Switch...............................................................................2-14
Vent Plug..............................................................................................2-14
Horn & Strobe ………………………………………………………………..2-14
Electrical Control Head (ECH) ……………………………………………..2-15
Electric Control Head, Electric Control Head KP600,……………………2-3a

Section 3 – KP Design
Duct Protection Limitations – Single Nozzle ...........................................3-1
Duct Protection Limitations – 2 Nozzle ...................................................3-2
Duct Protection Limitations – 3 Nozzle ...................................................3-3
Transition Limitation...................................................................... 3-1 & 3-3
Nozzle Location & Aiming (Special for Short Vertical Rise Duct) .....................3-4
Duct Protection Limitation – Multiple Nozzle...........................................3-4
Plenum Protection Limitations ................................................................3-5
KP APPLIANCE PROTECTION
Fryer Protection .............................................................................3-6, 7 &8
Range Burner Protection ....................................................3-9, 10, 11 & 12
Wok Protection......................................................................................3-12
Griddle Protection...................................................................3-13, 14 & 15
Char-broiler Protection..........................................................................3-16
Lava Rock Protection............................................................................3-16
Solid Fuel Appliances ...........................................................................3-17
Upright Broiler Protection......................................................................3-18
Salamander …………………………………………………………...…….3-18
Char-Broiler Protection ……………………………………………………. 3-19
Nieco 9025 Chain Char-Broiler ………………………………………....... 3-20
Duke FBB Chain Char-Broiler ………………………………….....……….3-21
Duke Char-Broiler+ Duke Hood ……………………………………...……3-22
Back Shelf Protection …………………………………….3-23, 24, 25, 26 &27
Nozzle Application Chart.......................................................................3-28
Agent Cylinder Selection.......................................................................3-29
Actuation Network Limitations...............................................................3-29
General Piping Requirements...............................................................3-30
Distribution Network – Single Cylinder..................................................3-31
Distribution Network – Twin Cylinder....................................................3-32
KP Distribution Piping …………………………………………….….3-33, 3-33A
Spot Detection Network Limitations (MRM / MRM II)............................3-34
Linear Fusible Link Limitations – Spot Detection..................................3-35
Linear Fusible Link Detection Network – Lanyard System ……………..3-36
Fusible Link Selection ……………………………………………………..3-37
PRM Limitations ……………………………………………………………3-37
Manual Pull Station Network Limitations...............................................3-38
Dual MRM Installation for Single Hazard …………………………………3-38A
Mechanical Gas Valve Applications......................................................3-39
Electric Gas Valve Applications............................................................3-40
Wiring Diagrams ...................................................................................3-41
Snap Action Switch Applications...........................................................3-42
System Design – General………………………………………………… 3-43
Zone of Protection ………………………………………….……3-44, 45 & 46
Distribution Network – Single Cylinder..................................................3-47
Section 3 – ZD Design
Kitchen Hood Fastener ……………………………………………………..2-16
Flexible Hose ………………………………………………………………...2-17
Actuation Network Limitations SRM.....................................................3-29a

Section 4 – System Installation
General...................................................................................................4-1
Installing the Agent Bracket & Assembly Model 275, 375, 475..... 4-1 & 4-2
Installing the Agent Bracket & Assembly Model 600...............................4-2
Installing the Pneumatic Actuator............................................................4-3
Installing Cylinder Enclosure …………………………………………..……4-3
Installing the PRM & Detection Tubing .............................................4-4 & 5
Installing Detection Tubing Termination Fitting …………………………...4-6
Installing the MRM / MRM II..............................................................4-7 & 8
Setting the MRM II …………………………………………………………....4-9
Setting the MRM ……………………………………………………………4-10
Installing the Linear Fusible Link Detection Network …………………....4-11
Installing the Manual Pull Station (MRM or PRM).................................4-12
Recessed Installation of Manual Remote Pull Station...................4-12 & 13
Installing the Actuation Network - Limitations ...............................4-14 & 15
Installing the Distribution Piping Network..............................................4-16
Installing High Temperature Blow-off Cap ………………………………4-17
Installing the Mechanical Gas Valve (MRM or PRM)..............4-17, 18 & 19
Installing the Electrical Gas Valve (MRM or PRM)................................4-20
Installing the Mechanical Gas Valve Kit …………………………….…….4-21
Installing the Snap Action Switch (MRM or PRM).................................4-22
Installing the Electrical Control Head (ECH) ……………………………. 4-23
Installing a Nut & Stub Style Fastener ……………………………4-24 & 4-25
Installing a Flexible Nozzle Branch Hose ……………………………...…4-26
Section 5 – System Testing
Detection Network Testing......................................................................5-1
Manual Pull Station Testing & Mechanical Gas Valve Testing................5-2
Distribution Piping Network Testing........................................................5-2
Distribution Network – Twin Cylinder....................................................3-48
Zone Defense Piping Limitations …………….……………………...3-49 & 50
Detection Network Limitations ……………………………………………..3-51
Installing the Electric Control Head KP600............................................4-2a
Installing the Electric Control Head........................................................4-2b
Installing the SRM Enclosure.................................................................4-7a
Installing the SRM Actuation Network - Limitation...............................4-14a
Installing the Linear Actuator................................................................4-14b
Electrical Gas Valve Testing...................................................................5-3
Electrical Control Head .……………………………………………………...5-4
Section 6 – System Maintenance
Maintenance Requirements..........................................................6-1, 2 & 3

Appendix A - LPCB Certification
Appendix B - SOLAS Certification
MSDS Sheet Kitchen Wet Chemical Agent
Section 7 – System Reset & Recharge
Reset Procedures for MRM / MRM II......................................................7-1
Reset Procedure for PRM …………………………………………………..7-2
Recharge Procedure Model 275/375 / 475 Cylinder Asy......................7-3
Recharge Procedure KP 600............................................................7-4 & 5
Nitrogen Cylinder Recharge..........................................................7-6, 7 &8
Reset Procedure for the ECH ………………………………………….……7-9
Reset Procedure for SRM ………………………………………………....7-2a
Reset Procedure for Electric Control Head KP600……………………....7-2b
Reset Procedure for Electric Control Head ...........……………………....7-2c
Appendix C - STRIKETM Manual

SECTION 1
GENERAL INFORMATION
MANUAL P/N 20150
AMEREX
RESTAURANT
FIRE SUPPRESSION SYSTEM
Tested and Listed by
Underwriters Laboratories, Inc.
to UL Standard 300
EX 4658
Tested and Listed by
Underwriters Laboratories of Canada
to ULC/ORD 1254.6-1995*
December 2008
* ULC Certification does not apply to the STRIKETM or SRM.


February 2019
Section 1 General Information Page 1 – 1
Amerex Restaurant Fire Suppression System (EX4658)
GENERAL INFORMATION
The Amerex KP / ZD Series Restaurant Wet Chemical Fire Suppression System is designed and has been
tested to provide fire protection for commercial cooking operations covering the hood, ducts, plenum and
appliances. Amerex Restaurant Fire Suppression Systems are a pre-engineered type as defined in NFPA
17A – Standard for Wet Chemical Extinguishing Systems. It is manufactured by the Amerex Corporation,
Trussville, Alabama.
It is essential that all installations of the Amerex KP / ZD Series Systems be performed in compliance with this
manual. Those individuals responsible for the design, installation, operation and maintenance of
the Amerex Restaurant Fire Suppression System must be trained by Amerex and hold a current
Amerex Certificate. All piping limitations, nozzle coverages, detector placements, etc. have been
proven and established through exhaustive testing by Underwriters Laboratories, Inc. Use of
components other than those referenced in this manual, or installations exceeding limitations stated in this
manual will void all of the Amerex KP / ZD Series System listings.
LISTINGS:
The Amerex KP / ZD Series Fire Suppression Systems are a listed pre-engineered fire extinguishing systems.
The KP & ZD systems are listed with Underwriters Laboratories, Inc. – USA per UL 300 fire test specification;
Underwriters Laboratories of Canada, Inc. per ULC/ORD 1254.6 – 1995 and Loss Prevention Certification
Board – UK per LPS 1223 rev. B. The use of the STRIKETM panel and SRM releasing device is not ULC
Certified. Testing required for listings under these standards involve live fire tests under specific conditions
involving commercial kitchen hoods, ducts and appliances. Each test fire is allowed to reach its maximum
intensity before agent is discharged. Each test was repeated using both maximum and minimum piping,
variations in agent storage cylinder pressure to simulate maximum and minimum temperature
ratings. Duct fire tests were extinguished with fans off and fans on; dampers open and closed. Splash tests
for various appliances were conducted to assure that discharge of the agent would not cause excessive
splashing of hot grease to provide greater employee safety during commercial cooking operations.
UL Standard 300 introduces a series of tests byspecifically addressing the use of high efficiency fryers,
ranges, woks and the unique fire extinguishing challenges that these appliances present.
DESIGN:
The Amerex KP Series Pre-Engineered Fire Suppression Systems consist of mechanical and electrical
components to be installed by an Authorized Factory Trained and Certified Amerex Restaurant Fire
Suppression Systems distributor. The system is composed of an Agent Cylinder/Discharge Valve charged
with Amerex Kitchen Wet Chemical Agent and aMechanical Release Module (MRM or MRM II),
Pneumatic Release Module (PRM) or a STRIKETM panel / STRIKETM Releasing Module (SRM).The
quantity of detectors, fusible links, nozzles, corner pulleys, pulley tees and manual pull stations will vary
depending on kitchen design.
The system operates either automatically if actuated by a detector or manually if actuated by a manual pull
station. Upon system operation, energy sources for the cooking appliances are required to be shut off
immediately. Electrical shutdown devices or suitable gas valves are referenced in this manual. Other
equipment such as audible/visual signaling devices can be added where required.
The Amerex Restaurant Fire Suppression System suppresses fire in commercial cooking equipment by
spraying Amerex Wet Chemical Agent in a pre-determined manner onto cooking appliances and into exhaust
ducts, filters and plenum areas. The primary means of fire suppression is either by saponification of surface
grease or by cooling the surface of oils and hot metal surfaces with fine droplets of agent, reducing the
temperature of the oil and appliance below the auto-ignition point.
Upon system discharge, the exhaust fans should be left on to aid in dispersal of the liquid suppressant that
results in cooling the plenum and duct. Any integral make-up or supply air should be automatically shut off
along with all cooking appliances. Some local Authorities Having Jurisdiction require exhaust fans to be shut
down by the fire suppression system. Check local fire codes, AHJ and Department of Health in the specific
area that the system is being installed for special installation requirements.
The Amerex Restaurant Fire Suppression System agent storage cylinders and cartridge shall not be installed
in environments below 32° For above 120° F (0° C to 49° C).

February 2019
Section 1 General Information Page 1 - 2
Amerex Restaurant Fire Suppression System (EX 4658)
GENERAL INFORMATION – ZONE DEFENSE SYSTEM
The Amerex KP and ZD SeriesPre-Engineered System consists of mechanical and electrical
components to be installed by an Authorized Factory Trained and Certified Amerex Restaurant Fire
Suppression Systems distributor. The system is composed of an Agent Cylinder Assembly charged
with Amerex Kitchen Wet Chemical Agent and a Pneumatic Release Module (PRM) or an MRM, MRM II
using a linear link detection network.
The system operates either automatically, if actuated by a rupture in the pressurized thermal responsive
tubing or by the separation of a thermal link or manually if actuated by a manual pull station. Upon system
operation, energy sources for the cooking appliances are required to be shut-off immediately. Electrical
shutdown devices or suitable gas valves are referenced in this manual. Other equipment such as
audible/visual signaling devices can be added where required.
The Amerex ZD and KP Series Systems use the same components and share the same UL Listings and
limits for the protection of the exhaust duct, plenum and dedicated appliance protection. They do not share
the same piping limitations or installation philosophy. This manual provides the unique limitations which apply
to a Zone Defense Fire Suppression System.
What isthe basic difference between a KP and ZD System Philosophy?
The Amerex Zone Defense System was developed for the kitchen that changes out it’s cooking appliances
frequently to accommodate the change in menu or cooks. The ZD System provides a detection system and
protection system which allows for the moving and rearranging of appliances without changing the fire
suppression piping or detection device locations. This is accomplished by using a detection network that will
detect a fire no matter where it occurs under the hood and will extinguish cooking appliances located
anywhere under the hood, as long as they are inside the “Zone of Protection”. Also the appliances must be
capable of being extinguished from overhead. Appliances such as upright broilers, salamanders, covered
tilting skillets, chain feed pizza ovens, etc. are all appliances that cannot be extinguished from overhead, but
require specific nozzles with specific aiming for the individual appliance. The use of a “back shelf” over
appliances also will block the application of agent from overhead nozzles and therefore requires the use of
“Dedicated Appliance Protection” for an appliance with a back shelf.
The Amerex Kitchen Protection Fire Suppression System differs from the ZD System in the manner in which it
protects appliances and detects a fire under the hood. The KP System uses individual “Dedicated Appliance
Protection” for each appliance under the hood requiring protection. A choice of the fire detection method may
be a standard thermal link network or one of the two linear detection networks. (PRM or Linear Fusible Link).
The KP &ZD Series Systems have their distinct application use in the field of kitchen protection. They both
provide superior protection from the hazards of commercial cooking.
How do I obtain MSDS Sheets?
MSDS sheets may be downloaded for the Amerex Internet Website:
http://www.amerex-fire.com/msds/msd/10
MSDS sheets may also be mailed to you by requesting them byphone or mail:
Amerex Corporation
7595 Gadsden Highway
P.O. Box 81
Trussville, AL 35173
Phone: 205/ 655-7602

DEFINITION OF TERMS
ACTUATION NETWORK: Copper tubing, piping, hose, or combination of the three that allows nitrogen to be
supplied from the Mechanical Release Module or Pneumatic Release Module to the Agent Cylinder
Assembly(s).
AGENT CYLINDER / DISCHARGE VALVE: Pressurized vessel with valve assembly containing Amerex Wet
Chemical restaurant fire suppression agent and expellant gas (nitrogen/argon).
AUTHORITY HAVING JURISDICTION (AHJ): The organization, office or individual responsible for
“approving” equipment, an installation or a procedure. The phrase “Authority Having Jurisdiction” is used in
NFPA documents in a broad manner since jurisdiction and approval agencies vary as to their responsibilities.
Where public safety is primary, the “Authority Having Jurisdiction” may be a federal, state, local or other
regional department or individual such as a fire chief, fire marshal, chief of a fire prevention bureau, labor
department, health department, building official, electrical inspector or others having statutory authority. For
insurance purposes, an insurance inspection department, rating bureau or other insurance company
representative may be the "Authority Having Jurisdiction"; at government installations, the Commanding
Officer or departmental official may be the "Authority Having Jurisdiction".
AUXILIARY EQUIPMENT: Listed equipment used in conjunction with the Amerex Restaurant Fire
Suppression System to shut down: power, fuel and make-up air. Auxiliary equipment also operates
dampers, sound alarm signals or initiate fire alarm systems.
“BAG TEST”: A means of testing agent distribution piping to guarantee that each nozzle is discharging equal
or proper amounts of agent. Upon completion of a system installation, bags are placed over each nozzle and
the system is fully discharged. These bags are then weighed and compared for proper agent distribution
according to the system design.
BLOW-OFF CAP: A cap (made of rubber or metal with a restraining strap) that covers the nozzle tip to keep
grease from plugging the orifice.
BRANCH DUCT: Ductwork for exhaust from a single hood or hazard to a common duct.
NITROGEN CYLINDER: A small, sealed steel cylinder containing nitrogen (refillable by distributor) used to
actuate the agent cylinder/discharge valve(s).
CABLE: 1/16” diameter stainless steel cable (7 x 7 strand, 480# tensile strength) used to connect detectors,
mechanical gas valves and manual pull stations to the MRM.
COMMON DUCT: Ductwork for exhaust from two or more separate hazards.
CONDUIT OFFSET: A factory formed section of conduit that allows the cable for manual pull stations, gas
valves and detectors to make a smooth transition into the Mechanical Release Module or Pneumatic Release
Module.
COOKING APPLIANCE: Includes but is not limited to ranges, fryers, griddles and charbroilers.
CORNER PULLEY: A device used with the detection network, mechanical gas valve and manual pull station
which allows the cable to change direction 90° and still move freely for system operation.
DAMPER: A valve or plate located within a duct or its terminal equipment for controlling the flow of exhaust
gases and air. Damper’s may also be present on cooking appliances.
DEDICATED APPLIANCE PROTECTION NOZZLE: A nozzle dedicated to the protection of a cooking
appliance with an enclosed cooking hazard, like an upright broiler, which cannot be protected with “zone of
protection” nozzles. Therefore, must be protected with nozzles explicitly listed for that appliance.
December 2008
Section 1 General Information Page 1 – 3
Amerex Restaurant Fire Suppression System (EX4658)

DETECTOR: (NFPA 96 “Electrical, pneumatic, thermal, mechanical or optical sensing instrument or sub
components of such instruments whose purpose is to cause an automatic action upon the occurrence of
some pre-selected event”.): MRM or MRM II: For our purpose this is a thermal-mechanical device consisting
of a detector bracket, detector linkage and fusible link which will automatically actuate the fire extinguishing
system at a predetermined temperature. PRM: A pneumatic tube that will automatically actuate the fire
extinguishing system at a predetermined temperature will be used with the PRM.
DETECTION NETWORK: MRM or MRM II: A continuous cable run through EMT conduit, corner pulleys and
detectors that provide a mechanical input to the mechanical release module in order to actuate the system
automatically. PRM: A continuous run of pressurized thermal responsive tubing that provides a mechanical
input to the pneumatic release module in order to actuate the system automatically.
DETECTOR LINKAGE:The device that supports the fusible link on the cable.
DISTRIBUTION NETWORK: The piping network consisting of supply lines, supply branch lines and nozzle
branch lines that serve as a means to deliver agent from the agent cylinder/discharge valves through the
nozzles.
DUCT:A continuous passageway for the transmission of airand vapors which, in addition to the containment
components themselves, may include duct fittings, plenums and/or other items or air handling equipment.
ELECTRICAL CONTROL HEAD (ECH): Apneumatic assembly which, when connected to the UL Listed
Amerex SR-X Releasing Control Panel (UL File S24395),will open up to ten (10) Agent Cylinder / Discharge
Valves via the activation of the connected Electric Actuator.
ELECTRIC CONTROL HEAD, KP600 (P/N 26797): A mechanical device that bolts directly to the top of a
KP600 agent cylinder valve that is actuated by a linear actuator from the STRIKETM ECS.
ELECTRIC CONTROL HEAD (P/N 26127): A mechanical device that screws directly to the top of a KP275,
KP375 or KP475 agent cylinder valve that is actuated by a linear actuator from the STRIKETM ECS.
FLOW POINT:The term used to describe the flow capacity of eachnozzle. This information is used to
determine the number of agent cylinder/discharge valves required for a specific installation.
FUSIBLE LINK: A fixed temperature heat detection device used to restrain the operation of the Mechanical
Release Module until the detectors designed temperature is reached. At its designated temperature, the
fusible link will separate, releasing tension on the cable, causing the system to discharge.
GAS TRIP ASSEMBLY:A pneumatic device mounted in the MRM, MRM II or PRM, which upon system
actuation pulls the cable connected to the mechanical gas valve causing itto close and stop the flow of gas.
GAS VALVE: A mechanical or electrical valve used to shut off the supply of gas to the cooking appliances
when the fire suppression system discharges. Such devices are required by NFPA 96 and are to be listed
with the system components. Gas valves must be manually reset.
GREASE: Rendered animal fat, vegetable shortening, vegetable oils or any combination thereof, which is
used for, or the result of, cooking and preparing food. Grease may be liberated and entrained in exhaust air
or may be visible as a liquid or a solid.
GREASE FILTER: A component of the grease vapor removal system that deflects the air and vapors passing
through it in a manner that causes the grease vapor concentration and/or condensation for the purpose of
collection, leaving the exiting air with a lower amount of combustible vapor.
GREASE TIGHT:constructed and performing in such a manner as not to permit the passage of grease
under normal cooking conditions.
HOOD:A device provided for a cooking appliance(s) to direct and capture grease-laden vapors and exhaust
gases, and constructed within the requirements of NFPA 96.
and is ina charged, operable condition.
September 2009
Section 1 General Information Page 1 – 4
Amerex Restaurant Fire Suppression System (EX 4658)

INPUT: An event monitored by the Mechanical Release Module (MRM or MRM II) or Pneumatic Release
Module, which causes a corresponding output(s). (Example: A detector senses fire [input] and the system
discharges [output] and trips the gas valve [output]).
INSPECTION: A “quick check” to give reasonable assurance that the system has not been tampered with.
LINEAR ACTUATOR (P/N 24448): The Linear Actuator is a device that, when electrically activated, extends a
metal shaft to mechanically open agent cylinder (with an electric actuation option) in the AMEREX® KP™ Fire
Suppression System. The Linear Actuator connects to the end of an actuation circuit and is color coded yellow.
LISTED: Equipment, materials, components and parts included in a list published by an organization
acceptable to the AHJ (Authority Having Jurisdiction) and concerned with product evaluation, which maintains
periodic inspection of production of listed equipment or materials and whose listing states either that the
equipment or material meets appropriate standards or has been tested and found suitable for its use in the
specified manner. The listing may not be considered valid unless so labeled.
MAINTENANCE: A “thorough check” to give maximum assurance that the extinguishing system will operate
as intended. Design parameters should be closely examined for hazard changes since the last inspection,
parts and components should be closely examined and tested or replaced if necessary.
MAKE-UPAIR: Air that is brought into the hazard from outside of the area, using a dedicated fan, to aid in
the exhaust of grease-laden vapors.
MANUAL PULL STATION:The device that allows the system to be manually discharged either at the hazard
or from a remote location.
MECHANICAL RELEASE MODULE (MRM / MRM II): An assembly that connects and controls the actuation
cartridge, the detectors, the manual pull station(s), the gas valve, the micro-switch(es) and the agent
cylinder/discharge valve(s). It receives inputs and activates appropriate outputs – including agent release,
auxiliary signals and power or gas shut-off.
SNAP ACTION SWITCHES: A set of dry (unpowered) electrical contacts arranged in various configurations
for initiating appropriate output functions such as signal to the building fire alarm, audible/visual remote signal,
electrical power shut-off, electric gas valve shut-off.
NOZZLE:The device used to deliver a specific quantity, flow and discharge pattern of fire suppression agent
to a specific appliance, duct size or plenum size.
NOZZLE BRANCH LINE:All pipe and fittings leading from the supply branch tee to a system nozzle.
OUTPUT:An action that isinitiated by the mechanical release module in responding to a pre-determined
input. (Examples: Agent release, power shut-off, remote signal, gas valve closure)
PERIMETER INCHES:The sum ofthe measurement of each side of a rectangular ductopening. (Example:
Duct opening measuring 18”x 9” would have 54 perimeter inches [18 + 18 + 9 +9 = 54])
PLENUM:The space defined by the filters and the portion of the hood behind the filters.
PNEUMATIC RELEASE MODULE (PRM): This single hazard control mechanism supervises and controls
one Fire Suppression System. Proven, rugged mechanical components are reliably set into motion with a
simple linear pneumatic detection interface. The control mechanism interfaces with mechanical manual pull
station(s), actuation networks, mechanical gas valves, and offers electrical contacts for shutdown functions.
Refer to the Design and Installation Manual, P/N 16546 for further details.
December 2008
Section 1 General Information Page 1 – 5
Amerex Restaurant Fire Suppression System (EX 4658)

PRE-ENGINEERED SYSTEM: Those systems having pre-determined flow rates, nozzle pressures and
quantities of agent. These systems have the specific pipe size, maximum and minimum pipe lengths,
flexible hose specifications, number or fittings and number of types of nozzles prescribed by a testing
laboratory. The hazards protected by pre-engineered systems are specifically limited as to type and
size by a testing laboratory based on actual fire tests. Limitations on hazards that can be protected by
these systems are contained in the manufacturer’s installation manual, which is referenced as part of
the listing.
“PUFF TEST” (or “AIR TEST”): A test to determine that the distribution network piping is clear. The
test is conducted by running nitrogen through the piping and confirming that all nozzles are clear.
PULLEY TEE: A device similar to a corner pulley except there is a change in direction on the cable
from two manual pull stations or two mechanical gas valves. It unites either two gas valves or two
manual pull stations to a single control point.
SALAMANDER BROILER:See upright broiler.
SAPONIFICATION: The reaction of fats and/or oils to alkaline materials, producing soap-like foam. Fire
extinguishing agents based on sodium bicarbonate, potassium bicarbonate, potassium acetate and potassium
carbonate will cause saponification when discharged onto hot grease. Rendered animal fat and oils containing
high percentages of saturated fat saponify better than cooking oils containing low percentages of saturated fat.
SERIES DETECTOR: Any detector located between the Mechanical Release Module (MRM or MRM II) and
the terminal detector.
STRIKETM: Electronic Control System (ECS) for use with KPTM Fire Suppression Systems. (Ref. UL File
S35485)
STRIKETM RELEASING MODULE (SRM): The STRIKETM Releasing Module is used to actuate the agent
cylinder discharge valve either automatically or manually by puncturing a nitrogen cylinder.
STRIKETM RELEASING MODULE (SRM), OEM: The SRM, OEM lacks the stainless steel enclosure and is
used in hood end cabinet or OEM installations.
SUPPLY LINE:That portion of the agent distribution network piping that runs from the agent cylinder
assembly outlet or distributor block to the first tee.
SUPPLY BRANCH LINE: All pipe and fittings leaving the first tee in the system and ending with the last
nozzle in the last nozzle branch line.
TERMINAL DETECTOR: The last detector (or only detector) in the detection network. It is at this point that
the cable for the detection network ends or is terminated.
TEST LINK: This device is used in place of a fusible link in order to easily test the detection network. The test
link is easily cut, simulating a fusible link separating under fire conditions. It is usually located on the terminal
detector and is used solely for test purposes.
UPRIGHT BROILER: A cooking appliance using intense radiant heat and conductive heat with the foot and/or
the radiant heat source not being limited for a horizontal mode. Most of these cooking appliances incorporate
a removable drip tray and may be used specifically for holding or warming foods.
VENT CHECK: Adevice installed in the actuation network that is used to safely relieve pressure and to
prevent a slow, unwanted build-up of pressure in the actuation network.
ZONE of PROTECTION – A horizontal foot print below and within the perimeter of the hood, in which the
cooking appliances are to be positioned. The discharge nozzles within the “Zone of Protection” are spaced at
pre-determined intervals to provide protection for eligible appliances within the “Zone of Protection” without the
need for re-aiming or repositioning of nozzles. An exception to this practice is for dedicated appliances such
as the upright broiler. Dedicated appliances require appliances specific nozzles protection, which will require
further review after movement of the appliance for possible re-aiming or repositioning of nozzle(s).
February 2019 Section 1 General Information Page 1 – 6
Amerex Restaurant Fire Suppression System (EX 4658)

February 2019 Section 1 General Information Page 1-7
Amerex Restaurant Fire Suppression System (EX 4658)
Revision Record
Page Revision Date
2-1 & 2-2 7-30-09
2-6 & 2-15
9-15-09
1-4 & 1-7
4-23
5-3
7-9
2-14 & 3-38
4-1-11
6-1 & 6-3
5-1 & 5-4
3-38A
1-2 6-1-11
2-2, 2-3 & 4-210-1-11
4-24, 4-25 & 2-16 1-1-12
2-17, 3-33, 3-33A & 4-26 3-1-12
TABLE OF CONTENT
2-10 5-1-12
2-2, 3-21a & 4-210-30-13
7-2 7-17-14
2-3a, 2-4a, 2-9, 3-29a, 4-2a, 4-2b,
02-14-194-7a, 4-14a, 4-14b, 7-2a, 7-2b & 7-2c.
Add Appendix C (26692 STRIKE™)

SECTION 2
SYSTEM COMPONENTS
MANUAL P/N 20150
AMEREX
RESTAURANT
FIRE SUPPRESSION SYSTEM
Tested and Listed by
Underwriters Laboratories, Inc.
to UL Standard 300
Effective November 21, 1994
EX 4658
Tested and Listed by
Underwriters Laboratories of Canada
To ULC/ORD 1254.6-1995*
December 2008
* ULC Certification does not apply to the STRIKETM or SRM.
Table of contents