FBII XL-5 User manual

N9146-1 10/98
;
;/
/
;
;/
/
6HFXULW\6\VWHP
8VHU*XLGH
9HUVLRQ

– 2 –
Table Of Contents
Introduction .................................................................................................................................4
LCD Keypad Layout....................................................................................................................5
LED Keypad Layout....................................................................................................................8
System Operation......................................................................................................................12
Arming The System...................................................................................................................13
System Ready............................................................................................................................13
System Not Ready.....................................................................................................................14
Stay ...............................................................................................................................................16
Stay Procedure ..........................................................................................................................16
Auto-Stay Mode (optional)........................................................................................................16
Instant..........................................................................................................................................18
Instant Procedure......................................................................................................................18
Instant – Stay..............................................................................................................................19
Instant – Stay Procedure..........................................................................................................19
Bypass ..........................................................................................................................................20
Bypass Procedure......................................................................................................................20
Forced Arming ...........................................................................................................................22
Forced Arming Procedure.........................................................................................................22
Unbypass .....................................................................................................................................23
Unbypass Procedure .................................................................................................................23
Group Bypass (Optional).........................................................................................................24
Group Bypass Procedure ..........................................................................................................24
Group Unbypass ........................................................................................................................25
Group Unbypass Procedure......................................................................................................25
User Code Definition................................................................................................................26
User Definition Procedure........................................................................................................27
User Deletion..............................................................................................................................29
User Deletion Procedure...........................................................................................................29
Disarming....................................................................................................................................30
Disarm Procedure .....................................................................................................................30
Keypad Auxiliary Conditions.................................................................................................32
Duress...........................................................................................................................................33
Quick Commands ......................................................................................................................34
Common Partition Display [# 0]...............................................................................................34
Quick Arming [# 1]....................................................................................................................36
Quick Forced Arming [# 2]........................................................................................................36
Time Set [# 3] ............................................................................................................................36
Zone Directory [# 4]...................................................................................................................39
Quick Bypassing [# 5] ...............................................................................................................39
Chime Mode [# 6] ......................................................................................................................39

Table Of Contents (cont’d)
– 3 –
Partition Assignment [# 7] .......................................................................................................40
Glossary .......................................................................................................................................42
Recommendations For Proper Protection..........................................................................45
Recommendations For Smoke And Heat Detectors................................................................45
Recommendations For Proper Intrusion Protection...............................................................46
Emergency Evacuation............................................................................................................47
System Testing...........................................................................................................................48
Battery Test...............................................................................................................................49
Owners Information .................................................................................................................50
About The Manufacturer.........................................................................................................51
Statements – Problems – Warnings.......................................................................................52
Warranty......................................................................................................................................55

– 4 –
Introduction
Congratulations on your decision to protect your home or business
with this Security System. The system has been designed with
reliability and ease of operation in mind.
Please take a few minutes to review the contents of this manual. In
order to realize the full potential of this system it is important that
you feel comfortable with its operation. The following pages will
familiarize you with the procedures for operating the Security System.
The system can be operated from different styles of keypads: model
XK-716 and XK-516 LED keypads containing indicator lights or model
XK-7LC and XK-5LC LCD keypads containing a two-line readout.
Please determine the type of keypads present within your system.
This manual covers the XL-4, XL-4B, XL-4C and XL-5 systems. The
systems differ with the following Underwriters applications:
XL-4 Household Burglary and Fire
XL-4B Commercial Burglary
XL-4C Commercial Fire and Burglary
Thank You,
FIRE BURGLARY INSTRUMENTS
NOTE: This owner's manual contains important information and is
not to be removed by anyone but the occupant of the premise.

– 5 –
LCD Keypad Layout
The XK-7LC or XK-5LC keypad contains everything necessary to
operate the Security System. The LCD (liquid crystal display) provides
a two line by sixteen-character English readout display to show the
current system status. The keypads appear as follows:
LCD KEYPAD LAYOUT
1 2 3
45 6
78 9
✴0 # CODE
INSTANT
BYPASS
STAY
2
3
4
5
6
9
1
Model XK-7LC LCD Keypad
7
8
1 2 3
45 6
7 8 9
*0 #
Model XK-5LC LCD Keypad
(Shown with Cover Open)
3
2
4
5
6
10
7
1

LCD Keypad Layout (cont’d)
– 6 –
1 – DISPLAY AREA
Two line by sixteen-character liquid crystal display. This area
contains the current system status using easy to read English
language descriptions programmed by your installer.
2 – ARM/DISARM INDICATOR
This light indicates whether the system is currently armed (activated)
or disarmed (deactivated). In addition to this constant visual
indication, the display area will provide additional information
concerning the current system status. This indicator will blink when
an alarm has occurred.
3 – STAY
The STAY key is used to activate (arm) the system with the exception
of interior protection. This will provide exterior protection of your
location while allowing full access through the premise. This mode
would be used when arming the system and you might be walking
through protected interior zones.
4 – BYPASS
The BYPASS key will be used to temporarily turn off protection to a
portion of your Security System. This could be performed, for example,
to ignore an open window that would prevent the arming of your
system. Certain zones such as FIRE detection zones are always active
and cannot be bypassed.
5 – INSTANT
The INSTANT key is used to activate (arm) the system and eliminates
the entry time delay. This would cause an immediate alarm if
someone came through an exit/entry zone.
6 – CODE
Function key used when entering or changing the User access codes of
your Security System.

LCD Keypad Layout (cont)
– 7 –
7 – NUMERICAL SECTION
The numerical section of the keypad operates similar to a telephone or
calculator. The digits 0 - 9, # and ✴are clearly marked and are used to
operate the system.
8 – PULL OPEN DOOR
The front of the XK-7LC keypad contains a door that pulls open.
Behind this door is a card which can be filled out to describe the areas
protected (zones) by your Security System.
9 – AC INDICATOR
This light indicates that AC power is connected to the Security
System. The system also contains battery backup to operate the
system in the event of a power failure.
10 – EMERGENCY KEYS
These keys generate Fire, Medical, or Panic signals when certain key
combinations are entered.

– 8 –
LED Keypad Layout
The LED based system contains indicator lights to display the current
status of your Security System. NOTE: The LED keypads can only be
used to display the status of the first sixteen zones. NOTE: This style
of keypad cannot be used with the XL-4C control panel. The keypad
has the following appearance:
LED KEYPAD LAYOUT
1 2 3
45 6
78 9
✴0 # CODE
INSTANT
BYPASS
STAY
RDYSTAYBAT
87645213
INSCOM
16151412 1310911
17
8
9
10
11
13
Model XK-716 LED Keypad
12
23456
14
Model XK-516 LED Keypad
(Shown with Cover Open)
123
45 6
789
*0 #
9
10
11
12
13
14
15
16
COM
INS
PWR
1
2
3
4
5
6
7
8
BAT
STAY
RDY
113
8
7
9
10
11
15
23 456
14

LED Keypad Layout (cont’d)
– 9 –
1 – ZONE STATUS
The indicator lights marked 1-16 display the current status of the first
sixteen zones connected to your Security System. The lights show
whether any zones are currently in alarm, bypassed, in trouble, or
faulted (not ready) status. The status of each zone is represented as
follows:
ALARM Fast Blinking
TROUBLE Slow Pulse
BYPASSED Slow Low Intensity Blinking
NOT READY Solid ON
Each light will only reflect one condition at a time. If a zone contains
multiple conditions at the same time the highest priority status from
the above list will appear.
2 – COMMUNICATIONS FAILURE
If the COM light BLINKS then there has been a communications error
with the Central Station.
3 – LOW BATTERY
If the BAT indicator BLINKS then the backup battery within the
system is low.
4 – STAY
The STAY light will be ON when the system has been armed in the
stay mode, which means that the system has been activated with the
exception of interior zones.
5 – INSTANT
The INS indicator will be ON when the system has been armed in the
INSTANT mode. This means that the system has been activated and
the entry delay has been eliminated.

LED Keypad Layout (cont’d)
– 10 –
6 – READY INDICATOR
The light marked RDY shows whether the system is ready to be
armed. If the light is off then a condition exists within at least one of
the zones preventing system arming.
7 – ARM/DISARM INDICATOR
This light indicates whether the system is currently ARMED (ON) or
DISARMED (OFF). In addition to this constant visual indication, the
zone indicator lights will provide additional information concerning
the current zone status. This light will also blink if there is an alarm
condition present.
8 – STAY
The STAY key is used to activate (arm) the system with the exception
of interior protection. This will provide exterior protection of your
location while allowing full access through the location. This mode
would be used when arming the system and you might be walking
through protected interior zones.
9 – BYPASS
The BYPASS key will be used to temporarily turn off protection of a
portion of your burglary protection. This could be performed, for
example, to ignore an open window that would prevent the arming of
your system.
10 – INSTANT
The INSTANT key is used to activate (arm) the system and eliminates
the entry delay. This would cause an immediate alarm if someone
came through an exit/entry zone.
11 – CODE
Function key used when entering or changing the User access codes of
your system.

LED Keypad Layout (cont’d)
– 11 –
12 – PULL OPEN DOOR
The front of the XK-716 keypad contains a door that pulls open.
Behind this door is a card which can be filled out to describe the areas
protected (zones) of your Security System.
13 – AC INDICATOR
This light indicates that AC power is connected to the Security
System. Battery backup exists to operate the system in the event of a
power failure.
14 – NUMERICAL SECTION
The numerical section of the keypad operates similar to a telephone or
calculator. The digits 0 - 9, # and ✴are clearly marked and are used to
enter commands to the Security System.
15 – EMERGENCY KEYS
These keys generate Fire, Medical, or Panic signals when certain key
combinations are entered.

– 12 –
System Operation
Throughout this manual the following notation will be used to
describe action taken at the keypads:
BYPASS Depression of the Function Key labeled BYPASS
INSTANT Depression of the Function Key labeled INSTANT
STAY Depression of the Function Key labeled STAY
CODE Depression of the Function Key labeled CODE
[USER] Entry of your user code (see note below)
✴Key labeled ✴(located to the left of 0)
#Key labeled # (located to the right of 0)
+Indicates the simultaneous depression of two keys.
For example, # + 3 indicates that the # and 3 keys
should be pressed at the same time.
☞USER CODE NOTE: The [USER] code can be selected by your
installer to be either a four or seven digit code. If a seven-digit
user code is selected then the user code will be the three-digit
user number followed by the four-digit user code. For example, if
user number 3 has a code of 6429 then the seven digit user code
would be 0036429.

– 13 –
Arming The System
ARMING the system will activate all portions of your Security
System. Arming can only be performed if all zones are READY. For
example, if a protected door is open the system cannot be armed.
☞Note: Your installer can program your system to be armed if
certain zones are not ready. Contact your installer to determine
whether this applies to your system.
System Ready
Ready Indications
LCD Based Keypads
If the system is ready to be armed the following message will appear
in the display area of the LCD keypad:
SYSTEM READY
The second line of the display can display a system wide descriptor
(example SMITH RESIDENCE) and may scroll through other system
conditions that are present.
LED Based Keypads
On LED keypads the READY indicator must be ON.
Arming Procedure
Enter your user code into the keypad:
[USER]
On LCD keypads the following display appears:
ON:AWAY ……
... Exit Now .....
The ARMED indicator light will now be lit (LED and LCD keypads)
and you may exit through a door designated by your installer as an
exit/entry zone for a fixed time period known as the exit delay. Once
the exit time period has expired the EXIT NOW indication will
disappear.
Your exit time is _______
Your entry time is _______

Arming The System (cont’d)
– 14 –
System Not Ready
Ready Indications
LCD Based Keypads
If the system is not ready to be armed the LCD display will display
the zone or zones not ready as follows. For example:
NOT READY Zne 012
Master Bedroom
This display indicates that zone number 12 is not ready. This might
mean that a window or door remains open. When the problem with
zone 12 has been resolved, the READY display will appear. The zones
correspond to the areas of protection set up by your installer.
☞Note: If more than one zone is not ready then the display will
scroll through the zones approximately every 2 seconds.
LED Based Keypads
On the LED keypads the individual zone lights display the zones
which are not ready as follows:
ALARM Fast Blinking
BYPASS Slow blinking low intensity
TROUBLE Slow Pulse
NOT READY Solid ON
Action Required
If the system is NOT READY, one of the following actions is required
if you want to ARM the system:
- Make the zone(s) ready. Determine which zones are not ready by
looking at the keypad and perform what is necessary to ready the
zone(s). For example if zone 12 represents the Bedroom Window,
then closing the window should make that zone ready.
or
- Bypass the zone(s) not ready. Bypassing should only be performed if
the zone cannot be made ready or intentionally will remain not

Arming The System (cont’d)
– 15 –
ready. Zones that are bypassed are not protected when the system
is armed.
NOTE: It is possible to arm the system without the back-up battery
connected.
NOTE: In a commercial burglary alarm installation (model XL-4B or
XL-4C) a brief pulsing audible output is provided by the keypad to
indicate successful receipt of the closing signal at the Central Station.
If not heard, CALL FOR SERVICE.
In a commercial burglary installation (model XL-4B) the bell will
energize briefly after entry of the user code during arming. If not
heard, CALL FOR SERVICE.

– 16 –
Stay
The STAY mode is another way to ARM your system while you remain
in the location. The STAY mode will deactivate any interior protection
zones, which means that you will be free to walk throughout your
location without activating the alarm system.
In order to enter the STAY mode, the system must be ready. (See
previous description).
Stay Procedure
Stay [USER]
Depress the STAY key followed by your user code.
☞Remember that you must DISARM the system to leave the
premise.
Note: The STAY option will automatically be reset after the system is
disarmed.
Indications
LCD Keypads
After a successful STAY arming the following display will appear:
ON: STAY . . . . . . .
In addition, the ARMED indicator will be lit. In the STAY mode only
the external or perimeter burglary protection is active. You are free to
walk around the location without activating any of the interior
protection zones.
LED Keypads
On LED keypads both the ARMED and STAY lights will be lit.
Auto-Stay Mode (optional)
Another option that can be programmed by your installer is the
Auto-Stay mode. This feature will arm the system and will bypass
only those interior zones preselected by your installer. For example, you

Stay (cont’d)
– 17 –
can stay in your location and walk freely through the living section of
your location and have certain portions of the interior protection
active in the rest of your home.
To auto stay arm simply enter your user code [USER] and remain
within the location (do not leave through the exit/entry door). This will
arm the system and only bypass those interior zones selected by your
installer. LCD keypads will contain the following display:
ON: AUTO STAY . . . .

– 18 –
Instant
The INSTANT mode arms the system and eliminates the entry and
exit time delay intervals. If anyone enters or exits through an
entry/exit zone the alarm system will instantly activate.
The system must be READY to select the INSTANT option.
Instant Procedure
Instant [USER]
Depress the INSTANT key followed by your user code.
Note: The INSTANT option will automatically be reset after the
system is disarmed.
Indications
LCD Keypads
Upon successful INSTANT ARMING of the system the ARMED
indicator will be lit and the following display appears:
ON: AWAY INSTANT
LED Keypads
Upon successful INSTANT arming of the system the ARMED and
INSTANT indicators will be lit.

– 19 –
Instant – Stay
The INSTANT STAY mode will arm the system with the
characteristics of both the INSTANT and STAY modes. The system
will be armed with the interior portions bypassed and the entry delay
will be suspended.
The system must be READY in order to enter this mode.
Instant – Stay Procedure
INSTANT STAY [USER]
or
STAY INSTANT [USER]
Depress the INSTANT and STAY keys in any order followed by your
user code.
Indications
LCD Keypads
ON: STAY INSTANT
LED Keypads
After a successful INSTANT STAY arming the ARMED, STAY and
INSTANT indicators will be lit.

– 20 –
Bypass
Bypasses are performed to eliminate burglary zones that are not ready
or faulty from activating the Security System.
Bypass Procedure
BYPASS [USER] ZN
Depress the BYPASS key followed by your user code and the three
digit zone number (000 - 072) to be bypassed.
The zone number to be bypassed is shown as ZN. For example, if your
user code is 7356 and you want to bypass zone 16 enter:
BYPASS 7 3 5 6 0 1 6
Press the bypass key followed by 7 3 5 6 (your user code), and 0 1 6
(desired zone to be bypassed).
Multiple zones may be bypassed by repeating the sequence for the
desired zones within a fifteen-second time period as follows:
EXAMPLE:
BYPASS [USER] 002 BYPASS 056 BYPASS 071
The sequence displayed above would have bypassed zones 2, 56 and
71.
Zones can be bypassed if the user performing the bypass is authorized
to perform bypasses and the zone has been defined by your installer as
bypassable.
If the zone has already been bypassed, the sequence will unbypass the
zone except if the system is armed and the unbypassed zone is still not
ready. Unbypass means that the zone returns as an active burglary
zone.
After the bypass (or unbypass) command has been accepted the unit
will emit a continuous beep and keypads will display the bypassed
zones as follows:
This manual suits for next models
1
Table of contents
Other FBII Security System manuals

FBII
FBII Star XL4800 EZ User manual

FBII
FBII XL-4 User manual

FBII
FBII XL4600DL User manual

FBII
FBII XL-21 User manual

FBII
FBII XL Star 4500 User manual

FBII
FBII OMNI-400 EU Assembly instructions

FBII
FBII LEGEND SERIES User manual

FBII
FBII XL-2S Silver User manual

FBII
FBII OMNI-600EU User manual

FBII
FBII OMNI-408EU User manual
Popular Security System manuals by other brands

Lutron Electronics
Lutron Electronics radioRA RA-QS-SEC-1 manual

Esse-ti
Esse-ti Helpy L200 TL user manual

Dynacord
Dynacord PROMATRIX 9000 Release notes

Honeywell
Honeywell ADEMCO VISTA-40 Installation and setup guide

DA System
DA System Aplique 6/14COM installation guide

Acroprint
Acroprint ARES III user manual