
PAGE 4 Pub.No. 11-AC19D1-1
INSTALLER'S GUIDE
10. Replace liquid service pressure tap port cap and valve stem
cap. These caps MUST BE REPLACED to prevent leaks.
Replacevalvestemand pressure tapcapfingertight, then tighten
an additional 1/6 turn.
11. The gas valve can now be opened. For a ball type gas valve,
openthegas valvebyremoving theshut-offvalve cap andturning
the valve stem 1/4 turn counterclockwise, using 1/4" Open End or
Adjustable wrench. See Figure 4. For brass gas line service valve
opening, follow 9 and 10 above. See Figure 5.
12. The gas valve is now open for refrigerant flow. Replace valve
stem cap to prevent leaks. Again, these caps MUST BE RE-
PLACED to prevent leaks. Replace valve stem and pressure tap
cap finger tight, then tighten an additional 1/6 turn. See Figure 4.
If refrigerant lines are longer than 15 feet and/or a different size
than recommended, it will be necessary to adjust system refriger-
ant charge upon completion of installation. See page 6 and unit
Service Facts.
E. ELECTRICAL CONNECTIONS
▲ WARNIN
:
Wheninstallingorservicingthis
equipment, ALWAYS exercise basic safety precautions to
avoid the possibility of electric shock.
1. Power wiring and grounding of equipment must comply with
local codes.
2. Power supply must agree with equipment nameplate.
3. Install a separate disconnect switch at the outdoor unit.
4. Ground the outdoor unit per local code requirements.
5. Provide flexible electrical conduit whenever vibration trans-
mission may create a noise problem within the structure.
6. The use of color coded low voltage wire is recommended to
simplify connections between the outdoor unit, the thermostat
and the indoor unit.
Table 1 — NEC Class II Wiring
ing the change in delta-T, we can determine the need for defrost.
The coil sensor also serves to sense outdoor coil temperature for
termination of the defrost cycle.
FAULT IDENTIFICATION
A fault condition is indicated by the flashing light on the defrost
control inside the heat pump control box.
In normal operation, the defrost control light will flash once each
second. If the light is flashing more than once per second or not at
all, refer to the service manual for that unit.
PIN IDENTIFICATION (See Figure 6)
1. TEST_COMMON (Shorting any of the other pins to this pin
causes the function of the other pin to be executed. Leaving this
pin open results in the normal mode of operation.)
2. TST = Test (Shorting TEST_COMMON to this pin speeds up
all defrost board timings.)
3. FRC_DFT = Forced Defrost (Short TEST_COMMON to this
pin for two (2) seconds to initiate a forced defrost. Remove the
short after defrost initiates.)
DEFROST CONTROL CHECKOUT
Normal operation requires:
a LED on board flashing 1 time/second.
b. 24V AC between R & B.
c. 24V AC between Y & B with unit operating.
d. Defrost initiation when FRC_DFT pin is shorted to
TEST_COMMON pin.
If a defrost control problem is suspected, refer to the service
information in control box.
▲ WARNIN
:
Do NOT connect 24 VAC to T1
(ODS-A) terminal. ODS-A thermistor WILL BE BLOWN.
G. COMPRESSOR START-UP
After all electrical wiring is complete, SET THE THERMOSTAT
SYSTEMSWITCH IN THEOFF POSITION SO COMPRESSOR
WILL NOT RUN, and apply power by closing the system main
disconnect switch. This will activate the compressor sump heat
(whereused). Donot change theThermostatSystem Switchuntil
power has been applied for one (1) hour. Following this procedure
will prevent potential compressor overload trip at the initial
start-up.
6PINIDENTIFICATION
24 VOLTS
WIRE SIZE MAX. WIRE LENGTH
18 AWG 150 FT
16 AWG 225 FT.
14 AWG 300 FT.
7. Table 1 defines maximum total length of low voltage wiring
from outdoor unit, to indoor unit, and to thermostat.
8. Mount the indoor thermostat in accordance with instruction
included with the thermostat. Wire per appropriate hookup
diagram (included in these instructions).
F. DEFROST CONTROL
The demand defrost control measures heat pump outdoor ambi-
ent temperature with a sensor located outside the outdoor coil. A
second sensor located on the outdoor coil is used to measure the
coil temperature. The difference between the ambient and the
coldercoiltemperature isthedifference ordelta-Tmeasurement.
This delta-T measurement is representative of the operating
state and relative capacity of the heat pump system. By measur-