
Drafthood- This water heater has been shipped with a draft diverter for which it was designed with reference to the horizontal and vertical
planes. If removed, the draft diverter shall be replaced in the same position and secured to the jacket top by the screws with which it was installed.
Vent Piping- This water heater must be connected to a masonry chimney or venting system approved by local codes or ordinances. The vent
connector used to attach the draft diverter outlet to the chimney or approved vent must be of the same diameter as the drafthood outlet or larger.
For proper venting in certain installations, a larger vent connector may be needed. Consult venting tables in National Fuel Gas Code ANSI
Z223.1/NFPA 54 latest or current or local code officials for proper application in your area.
Better combustion is achieved by avoiding numerous elbows in the vent piping. Horizontal piping must be sloped upward at least 1/4 inch per linear
foot of length. All connections in venting system must be securely fastened with sheet metal screws or other approved method. Check local codes
and ordinances.
Failure to install a proper venting system can result in fire, injury, or death. When an existing Category I appliance is removed or replaced, the original
venting system may no longer be sized to properly vent the attached appliances. An undersized system will cause formation of condensate, leakage,
spillage, water heater malfunction, etc.
Schedule periodic cleaning every 6 months for the condensate disposal system and the screens in the vent terminal; also We recommend checking
in on your condensate neutralizers every month.
WATER CONNECTIONS
Installation- Refer to Figure 5 for typical installation. Connect the hot and cold water supply to the water heater, hot to the location marked
"HOT" and cold to the location marked "COLD". Note: If making cold water connection on top, determine that the dip tube is in place. If sweat
connections are used, sweat tubing to adapter before attaching adapter to the top cold water inlet as it may contain a nonmetallic dip tube. When
making these connections, use a good grade of pipe joint compound. Be familiar with the location of the shut-off valve in the cold water line feeding
the water heater (See Figure 5). If a valve is not present, one shall be installed as shown in Figure 5.
Do not install a check valve or other device that would prevent reverse flow of water ("closed system") unless required by local codes. A closed
system will result in frequent operation of the relief valve. Provisions must be made for protection against thermal expansion in the event of a closed
system (Page 1). Warranties do not cover pressure bulges and/or deformities.
This water heater is capable of delivering high temperature hot water at any faucet in the system. Care must be taken whenever using
hot water to avoid scalding injury. Certain appliances require high temperature hot water (such as dishwashers and automatic clothes
washers). In order to prevent potential scald injury, install an anti-scald tempering valve in the water system.
CAUTION
7
GAS PIPING
Use clean black iron pipe or equivalent material approved by local codes and ordinances for gas piping. Install a ground-joint-union in the supply line
as close to the 'water heater as possible. A manual gas shut-off valve should be above floor level and readily accessible. A drip leg (consisting of a pipe
tee, 4 inch nipple, and a cap) should be installed as shown in Figure 5.
Make sure the gas supplied to the heater is the same type as listed on the rating plate. DO NOT ATTEMPT TO USE THIS WATER HEATER WITH
ANY GAS OTHER THAN THE TYPE LISTED ON THE RATING PLATE.
Compound used for the connection of all gas piping should be resistant to the action of liquefied petroleum (L.P.) gases. Apply pipe dope sparingly
to the male threads only. DO NOT apply pipe dope to the gas valve inlet. Make certain that no pipe dope has become lodged in the inlet screen of
the gas valve. This will restrict the flow of gas. When attachment of gas piping to gas valve inlet is made, extreme care must be taken to prevent pipe
dope from entering the gas valve inlet and to avoid excessive torque to prevent cracking of the gas valve inlet housing. The suggested maximum
torque is 31.5 lbs-ft. The manufacturer of this water heater will not be liable for any damage or injury caused as a result of a cracked gas inlet from
excessive torque.
TYPICAL INSTALLATION
Terminal Clearances (uses room air for combustion)
A
Clearance above grade,
veranda, porch, deck, or
balcony
12 in (30 cm) H
Clearance to each side of
center line extended above
meter/regulator assembly
3 ft. (91 cm) within a height
15 feet (4.5 m) above the
meter assembly.
BClearance to window or
door that may be opened
4 ft (1.2 m) below or
to side
of opening;
1 ft (300 mm) above
opening
IClearance to regulator
vent outlet 3 ft. (91 cm)
CClearance to permanently
closed window 0 in. J
Clearance to a non-mechanical
air supply inlet into building or
combustion air inlet to any other
appliance
4 ft. below or to side of
opening,1ft. (300 mm) above
opening
D
located above the terminal within
a horizontal distance of 2 feet
(61 cm) from the center line
of the terminal
12 in.† K Clearance to a mechanical air
supply inlet
3 ft. (91 cm) above if within
10ft (3m)
Horizontally
EClearance to unventilated 12 in. L
Above paved sidewalk or paved
driveway located on public
property
7 ft (2.13 m ) for mechanical
draft systems (category
I appliances); vents for
category II and IV appliances
cannot be located above
public walkways or other
areas where condensate or
vapon can cause a nuisance
or hazard
FClearance to outside
corner 24 in. M Clearance under veranda, porch,
deck, or balcony
12 in. ‡
G Clearance to inside corner 18 in.
In accordance with the current ANSI Z223.1/NFPA 54, National Fuel Gas Code:
† 1.Where local experience indicates condensate is a problem with Category IV appliances, the vent shall not terminate:
• over public walkways; or
• where condensate vapor could cause damage or could be detrimental to the operation of regulators, relief valves or other equipment.
TERMINATION CLEARANCES SIDE WALL
Note:The following picture and table are intended to illustrate clearance requirements, and do not serve as a
substitute for locally adopted installation codes.