QUICK REFERENCE GUIDE
MODELS - TCWH180S-AS & TCWH199S-AS
CHAPTER 1 - BEFORE INSTALLATION
CHAPTER 2 - CONSIDER INSTALLATION SITE
B.MOUNTING ON THE WALL
C. GAS PIPING
D. WATER PIPING
12” of the bottom connections of the water heater.
1. This water heater requires the use of direct vent type pipe as specified by American
Standard Water Heaters. DO NOT use materials that are not specified for use with
this water heater.
2. Always install water heater exhaust vent / intake pipe terminations 12 inches
above maximum expected snowaccumulation levels.
4. The power supply required is 120VAC at 60Hz. Failure to provide the correct
power supply could result in electric shockorfire.
Locate the water heater in a site where leakage from the water heater or
connections will not result in damage to the site adjacent to the water heater.
When such locations cannot be avoided, it is recommended that a suitable drain
pan,adequatelydrained,be installed under the water heater. Install the
water heater in a location that allows for proper clearances to combustible and
noncombustible construction. Consult the rating plate for proper clearances.
Please refer to the installation manual before mounting the water heater.
Ensure the mounting location can support the weight of the filled water
heater.
Drill four (4) holes with a 15/32 drill bit in the locations on the wall bracket.
Mount the wall bracket level on the wall with four (4) anchor bolts.
Align the grooves on the back of the water heater with the tongue on the
wall mounting bracket.
Remove the four screws on the water heater front cover. Remove the
frontcover.
The gas connection fitting on the water heater is ¾” female NPT.
The supply line mustbesized for the maximumoutput of the water heater model
being installed. If there are additionalgas appliances connected to the same supply
line, size the supply line according to the COMBINED
total maximum BTUH draw for the appliances as if they were operating at the
same time.
DO NOT operate the water heater until all connections havebeen completed
and the heat exchanger is filled with water.
Ensure pipe material is suitable to meet local codes and standards. The pipe
must be clean and without blemish. DO NOT apply torch heat within
Installation Clearances from Non -
Combustibles / Combustibles
Recommended Service and Proper
Operation Clearances
Top
9 in. (228.6 mm)
9 in. (228.6 mm)
Back
5/8 in. (15.9 mm)
5/8 in. (15.9 mm)
Front 6 in. (152.4 mm)
24 in. (609.6 mm) or more (Front of
Water heater)
(A combustible door or removable
panel is acceptable front clearance.)
Right Side
3 in. (76.2 mm) 3 in. (76.2 mm)
Left Side
Bottom
12 in. (304.8 mm)
12 in. (304.8 mm)
Minimum Clearances
WARNING
3. Check the water heater rating plate to ensure the water heater is set to
operate on the gas supplied and that the gas supply line is sized to the Btu/h
required for this water heater. (Rating plate shown by example only).
CHAPTER 3 - INSTALLATION
A. INCLUDED ACCESSORIES
www.americanstandardwaterheaters.com
TCWH180S-AS / TCWH199S-AS REV 06/16
561 New York Drive, Pomona,
California 91768
Read the Installation Manual carefully and be sure that your water heater has
been properly assembled BEFORE reviewing these instructions. Failure to
follow the instructions included in the Installation Manual exactly as written
could result in fire, explosion, electrical shock, or other situation that could
result in property damage, serious personal injury, or death. Installation and
service must be performed by a qualified plumber, licensed gas fitter, or a
professional technician in accordance with all local codes. Improper installation
and/or operation by an unqualified person WILL VOID the warranty. This
water heater must be installed in accordance with all local codes. In the
absence of local codes, follow ANSI Z223.1 / NFPA 54 or CAN/CSA B149.1,
Natural Gas and Propane Installation Code, as applicable.
2
2” Combustion Air /
Vent Pipe
3” Combustion Air /
Vent pipe
MaxMax
15’
(4.5M)
2
100’
(30M)
6
NOTE: Ensure all vents are properly supported.
I. Power Connections
II. Dip Switch
A. OPEN THE WATER AND GAS LINE VALVES
B. ADJUST CONTROL PANEL ON WATER HEATER FRONT COVER
C. MEASURING INLET GAS PRESSURE
LP GAS
NATURAL GAS
Minimum Pressure
3.5” WC
Minimum Pressure
3.5” WC
Maximum Pressure
14” WC
Maximum Pressure
14” WC
NOTICE
NOTE TO CONSUMER: PLEASE KEEP ALL INSTRUCTIONS FOR
FUTURE REFERENCE.
Dip Switch
Off
On
1 – 3
Not used
Not used
Not used
Not used
4
5
Gas Type
LP
NG
6
High Fire
Normal
High Fire
7
Low Fire
Normal
Low Fire

1. Check Installation completely.
2. Check for leaks along Gas Pipes & Installation.
3. Check Exhaust Vent and Intake Pipe Instal lation for leaks. Ensure all vent pipes
are properly supported.
4. Check Condensate Drain Installation.
5. Ensure DIP switches areproperly installed.
6. Check the Electrical Supply Power connections are correct.
7. Check Burner Flame for proper operation.
WARNING
The pipe size used for the supply of heated water should be the same size
used for the water return pipe. The correct size of the hot water supply
pipe should be ¾” diameter. Install tankless isolation valves to avoid future
service.
E. CONDENSATE DRAIN CONNECTION
Condensate must be drained in accordance with all
local codes & regulations. Follow local codes
regarding the disposal of condensate & drainage.
Diagram left; (1) Condensate to neutralizer, (2) to
floor drains, (3) to bathtub, (4) to condensate
pump. Use only corrosion resistant materials for
the condensate drain lines, such as ½” PVC,
CPVC, Polypropylene, or the included plastic hose.
If a neutralizer is installed, periodic replacement of
the limestone (or neutralizing agent) will be
required. The rate of depletion of limestone varies
upon usage of the water heater. During the first
year of operation, check the neutralizer every few
months for depletion.
F. VENTING
Acceptable Vent Lengths (PVC, CPVC, PP)
Models
TCWH180S-AS
TCWH199S-AS
Maximum
Number of
Elbows
Maximum
Number of
Elbows
G. POWER CONNECTIONS & DIP SWITCH
Ensure that all electrical connections and wiring are installed in accordance with
all local codes. In the absence of local codes, follow the National Electrical Code,
NFPA 70, and/or CSA C22.1 Electrical Code-Part 1 in Canada. For your safety,
turn off the electrical power supply at the service entrance panel before making
any electrical connections to avoid possible electrical shock hazard. Failure to do
so may result in property damage, severe personal injury, or death.
NOTE: DO NOT disconnect the power supply during normal water heater
operation.
Ensure water heater is powered ON. Press & hold the button for standby
mode. Current ‘DHW’ set-point will display and flash. Concurrently, the caution
mark ‘H’ will display. Current ‘DHW’ set-point can be changed by rotating the dial.
After changing the temperature, press the Center Button to save settings.
NOTE: Refer to Installation Manual when adjusting gas pressure.
1. The water heater and its individual shutoff valve must be disconnected from
the gas supply during pressure testing of the system at test pressures greater
than ½ psi (3.5 kPa).
2. The water heater must be isolated from the gas supply by closing the manual
shutoff valve during pressure testing of the gas supply at test pressures equal to
or greater than ½ psi (3.5 kPa).
The minimum and maximum inlet gas line pressures must meet the requirements
shown below:
Do not attempt to ignite/operate water heater until all connections have been
completed and the heat exchange is filled with water. Doing so will damage the
water heater and void the warranty.
NOTICE: American Standard Water Heaters reserves the right to make product
changes or updates without notice and will not be held liable for typographical
errors in literature.
www.americanstandardwaterheaters.com
TCWH180S-AS / TCWH199S-AS REV 06/16
CHAPTER 5 – FINAL CHECK
CHAPTER 4 – AFTER INSTALLATION
12" OVER
MAXIMUM SNOW
LEVEL OR 24" -
WHICHEVER IS
GREATER
VENT KIT
EXHAUST
MAINTAIN 12"
MINIMUM
CLEARANCE ABOVE
HIGHEST ANTICIPATED
SNOW LEVEL OR
GRADE, WHICHEVER IS
GREATER
IMPORTANT:
INTAKE LEG
MUST
BE FACING UP
INTAKE
MAINTAIN 12"
MINIMUM
CLEARANCE ABOVE
HIGHEST
ANTICIPATED SNOW
LEVEL OR GRADE,
WHICHEVER IS
GREATER
IMPORTANT:
INTAKE LEG MUST
BE FACING UP
CONCENTRIC VENT KIT
CONCENTRIC VENT KIT
1” MIN.
EXHAUST
Relief Valve
Gas Valve
Isolation Valve
Cold Water Inlet Line
Hot Water Outlet Line
Gas Supply Line
Discharge Pipe Condensate Drain Pipe
561 New York Drive, Pomona,
California 91768

Other manuals for TCWH180S-AS

1

This manual suits for next models

1

Other American Standard Water Heater manuals

American Standard D80-125 Manual

American Standard

American Standard D80-125 Manual

American Standard ULN80-125 Manual

American Standard

American Standard ULN80-125 Manual

American Standard Standard Residential Manual

American Standard

American Standard Standard Residential Manual

American Standard PLC 75-76 Manual

American Standard

American Standard PLC 75-76 Manual

American Standard 75-76 AS Manual

American Standard

American Standard 75-76 AS Manual

American Standard TCWH199S-AS Installation manual

American Standard

American Standard TCWH199S-AS Installation manual

American Standard TCWH-199-AS Installation manual

American Standard

American Standard TCWH-199-AS Installation manual

American Standard VAPORSHIELD Residential 30 Manual

American Standard

American Standard VAPORSHIELD Residential 30 Manual

American Standard TCWH180S-AS Guide

American Standard

American Standard TCWH180S-AS Guide

American Standard ULN 100-76R Manual

American Standard

American Standard ULN 100-76R Manual

American Standard HE 70-125 Manual

American Standard

American Standard HE 70-125 Manual

Popular Water Heater manuals by other brands

TriangleTube 30 Installation & maintenance manual

TriangleTube

TriangleTube 30 Installation & maintenance manual

Ariston AURES Series manual

Ariston

Ariston AURES Series manual

A.O. Smith T-H2S-DV troubleshooting guide

A.O. Smith

A.O. Smith T-H2S-DV troubleshooting guide

Haier FCD-JTHMG100-III Mode d'emploi

Haier

Haier FCD-JTHMG100-III Mode d'emploi

Bradford White U4-30T6FRN Specification sheet

Bradford White

Bradford White U4-30T6FRN Specification sheet

PVI Industries 40L125A-MXIF Installation & maintenance manual

PVI Industries

PVI Industries 40L125A-MXIF Installation & maintenance manual

evoheat EVO MAX 32 manual

evoheat

evoheat EVO MAX 32 manual

Rinnai ByPass Servo troubleshooting manual

Rinnai

Rinnai ByPass Servo troubleshooting manual

Midea MWH-38P3 instruction manual

Midea

Midea MWH-38P3 instruction manual

STIEBEL ELTRON DHB-E 21 Si Operating and installation instructions

STIEBEL ELTRON

STIEBEL ELTRON DHB-E 21 Si Operating and installation instructions

Lochinvar Harmony Installation and operation manual

Lochinvar

Lochinvar Harmony Installation and operation manual

Seaward S1900 owner's manual

Seaward

Seaward S1900 owner's manual

Joannes Clizia 24 AS Instructions for use, installation and maintenance

Joannes

Joannes Clizia 24 AS Instructions for use, installation and maintenance

Westinghouse 080 use and care manual

Westinghouse

Westinghouse 080 use and care manual

VEGAS SPA SOLUTIONS VEGAS-24 instructions

VEGAS SPA SOLUTIONS

VEGAS SPA SOLUTIONS VEGAS-24 instructions

Haier FCD-6.6 instruction manual

Haier

Haier FCD-6.6 instruction manual

Kenmore POWER MISER 153.336334 owner's manual