ANDIVI TRC-D
TECHNICAL MANUAL
08/14, fw. ver. V1.2, V1.3

Andivi – TRC-D – Technical Manual
2
08/14, fw. ver. V1.2, V1.3
ATTENTION!
In the event of an incorrect connection of the room controller or a short circuit in
the installation and actuators, irreparable damage to the room controller can occur.
Therefore, pay special attention during the installation and follow the instructions
carefully!
• Carefully read these instructions before starting the installation.
• Room controller Andivi must be installed according to applicable standards.
• Before any intervention, make sure the power is turned off.
CAREFUL!
Regular maintenance of convectors can avoid excessive burdens of the room
thermostat, which can lead to the destruction of it. When a building is under
construction, the bearings in the convectors can often get too dusty, which can lead
to excessively high starting current that can damage or destroy the room thermostat.

Andivi – TRC-D – Technical Manual
3
08/14, fw. ver. V1.2, V1.3
FRONT VIEW (LEGEND OF SYMBOLS) 4
INSTALLATION 5
MOUNTING ON ELECTRIC BOX 5
MOUNTING THE FRONT COVER 5
WIRING EXAMPLE 5
OPERATION 6
ROOM CONTROLLER TYPES 6
USER MODE OPERATION 6
WORKING MODE 7
COOLING MODE 7
HEATING MODE 8
“ON” FUNCTION 8
ANTI-FREEZING PROTECTION 8
ECONOMY MODE 9
PROTECT MODE 9
FIRMWARE VERSION 9
ENGINEER MODE OPERATION 10
Table: Engineer Mode menu items description 11
NETWORK SPECIFICATIONS 13
Table: Read/Write Coils (function code 01/05/15) 14
Table: Read discrete input (function code 02) 15
Table: Read/write holding register (function code 03/06/16/23) 16
Table: Read input register (function code 04) 18
WARRANTY, CONDITIONS
19
INDEx

4
08/14, fw. ver. V1.2, V1.3
Intelligent room controller
TRC-D TECHNICAL MANUAL
Item Description
1 FIRE icon or FLAKE icon Fire icon for Heating action; Flake icon for Cooling action
2 ON/ACTIVE icon Indicate room controller ON status
3 SLEEP icon [not used]
4 CLOCK icon Indicate Protect mode
5 DOWN button Decrease setting / Previous item
6 UP button Increase setting / Next item
7 FAN SPEED button Toggle to change fan speed over Auto / Off / Stage I / Stage II / Stage III
8 POWER ON/OFF button Turn room controller on/off
9 MODE button Cooling/Heatingchangeover/Settingconrmation
10 HOUSE WITH THERMOMETER icon Indicate Anti-Freezing active
11 AUTO icon Automatic fan mode
12 FAN icon Indicate fan state
13 LCD Display temperature and operation data
14 MOON icon Indicate Economy mode
15 THERMOMETER icon Temperature set-point mode
2
3
4
5
6
7
8
9
10
11
12
13
14
15
Fig 1-1: Front view

Andivi – TRC-D – Technical Manual
5
08/14, fw. ver. V1.2, V1.3
INSTALLATION
MOUNTING ON ELECTRIC BOX
MOUNTING FRONT COVER
WIRING EXAMPLE
1. Separate the back plate from the controller by loosening the cover screw.
2. Align the mounting holes on the screw holes of the electric box. Suitable is a 3-module electric box 3M, for example Gewiss
GW24203, GW24207; TEM Catez DM30, HM30. The electric box is mounted vertically.
3. Fix the back plate on the electric box by tightening the back plate screws. Suggested for use is Philips wider “truss head”
or “washer head” #6-32x 3/4”(20mm).
4. DO NOT let the bolt head rise above the wall of the mounting holes of the back plate. It might cause a short circuit of the
room controller.
1. Lock front cover on the back plate by tightening the cover screw underneath with screwdriver of Philips electronic instrument
type or similar.
All wires that come from electric box must be inserted above the retainers of respective terminal block before tightening the
captive screws.
N L
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
ESI2
ESI
C+
C -
RS
COM
I.
II.
III.
Cooling/Heating valve
Economy mode input (ECON)
Remote sensor (RS)
Protect mode input (PROT)
Modbus
Fan
N L
I.
II.
III. FAN
Cooling valve
Heating valve
Economy mode input (ECON)
Remote sensor (RS)
Protect mode input (PROT)
Modbus
Fig. 2-1:
2-Pipe Control, 230VAC
Fig. 2-2:
4-Pipe Control, 230VAC

Andivi – TRC-D – Technical Manual
6
08/14, fw. ver. V1.2, V1.3
The type of room controller is selectable in the Engineer mode and over the Modbus communication.
ThersttierofoperationincludessettingsasFigure3-1shows.Tooperate:
1. Press POWER button ON or OFF to turn on/off the room controller. In ON state, icon ON is activated.
2. At state ON, press any other button to start the User Mode operation. Press FAN SPEED button to toggle over different fan
speeds. Press MODE button to toggle working modes over Cooling/Heating. Press UP or DOWN button to increase/decrease
temperature set-point.
3. If no button is pressed for 10 seconds, it will return to current temperature display with the latest setting.
Item Description
B - Type 4-Pipe Heating or Cooling (Manually Selectable)
C - Type 4-Pipe Heating and Cooling (Auto changeover)
E - Type 2-Pipe Heating or Cooling (Manually Selectable)
Item Description Remarks
1 Current Temperature Display current temperature
2 Temperature Setting Set the temperature set-point
3 Cooling/Heating Select Toggle to change the working
mode over Cooling/Heating
Only applied to models with Cooling/
Heating mode selectable types.
4 Fan Auto/Continuous Toggle to change fan speed over
Auto / Off / Stage I / Stage II / Stage III
Fig. 3-1:
User Mode operation
sequence
ROOM CONTROLLER TYPES
USER MODE OPERATION
OPERATION
Current
Temperature
Temperature
Setting
0.5ºC
Cooling/
Heating
Select **
FAN
AUTO
Continuous
4
3
2
1
* Back to 1 when no
button was pressed for 10s
** For Cool or Heat
selectable Models only

Andivi – TRC-D – Technical Manual
7
08/14, fw. ver. V1.2, V1.3
1. For Cooling or Heating mode manually
selectable type (B, E), working mode
depends on the users’ setting.
2. For Cooling and Heating mode
automatical changeover type (C),
working mode depends on the Room
temperature as following:
WORKING MODE
Room
Temperature
Dead Band
(DB)
½ DB
Cooling Mode
Heating Mode
Set-point
(SP)
COOLING MODE
Valve control for Cooling mode
FAN control for Cooling mode
Set-point
Cooling
Cooling
Set-point
Room
Temperature
1/3
Proportional
Band (PB)
1/3 PB
Stage
Differential
Valve
active
Valve
not active
Room
Temperature
Stage
Differential
Fan Stage III
Fan Stage III
Fan Stage III
Fan Off
Set-point
Cooling
Cooling
Set-point
Room
Temperature
1/3
Proportional
Band (PB)
1/3 PB
Stage
Differential
Valve
active
Valve
not active
Room
Temperature
Stage
Differential
Fan Stage III
Fan Stage III
Fan Stage III
Fan Off

Andivi – TRC-D – Technical Manual
8
08/14, fw. ver. V1.2, V1.3
hEATING MODE
Valve control for Heating mode
Fan Stage III
Set-point
Heating
Fan Stage III
Fan Stage III
Fan Off
Room
Temperature
1/3
Proportional
Band (PB)
1/3 PB
Stage
Differential
Heating
Stage
Differential
Set-point
Valve
active
Valve
not active Current
Temperature
FAN control for Heating mode
If POWER ON/OFF button is locked, it is not possible to switch the room controller ON or OFF locally with the button. But the ON/
OFF state can be changed by the Modbus communication.
ON FUNCTION
1. If the present temperature falls under 10°C (adjustable in Engineer mode and Modbus), a Heating valve opens to 100%. This
is active always, even when the room controller is off. In the 4-Pipe system (B or C), a Heating valve on terminal 4 activates.
In the 2-Pipes system (E), a valve output on terminal 2 activates. Anti-Freezing Protection is ON by default, but it is also
switchable to OFF in the Engineer mode and Modbus.
2. If the present temperature falls under PtCF (default 10°C), a FIRE icon and a HOUSE WITH THERMOMETER will be active on
LCD.
ANTI-FREEZING PROTECTION
Fan Stage III
Set-point
Heating
Fan Stage III
Fan Stage III
Fan Off
Room
Temperature
1/3
Proportional
Band (PB)
1/3 PB
Stage
Differential
Heating
Stage
Differential
Set-point
Valve
active
Valve
not active Current
Temperature

Andivi – TRC-D – Technical Manual
9
08/14, fw. ver. V1.2, V1.3
Economy mode can be activated with the digital input on terminal 14 or with the Modbus coil, address 3. Active Economy
mode is indicated with the MOON icon on LCD. If the present temperature in this mode is between Economy Cooling set-
point and Economy Heating set-point, no cooling or heating action is active. If the present temperature is outside these limits,
corresponding cooling or heating action will be activated. If both, Economy and Protect mode are active, Protect mode will have
priority.
ECONOMY MODE
Type Room controller OFF Room controller ON
2-Pipe system (E) Valve is always ON Valve is always ON
4-Pipe system (B or C) Heating valve is always ON Heating valve is always ON
Room
Temperature
Valve
active
Valve
not active
0.5
Differential (°C)
Anti-
Freezing
PtCF
(Temp. for
Anti-Freezing)
Valve control for Anti-Freezing
Protection
Protect mode can be activated with the digital input on terminal 11 or with the Modbus coil, address 2. Active Protect mode is
indicated with the CLOCK icon on LCD. If the present temperature in this mode is between Protect Cooling set-point and Protect
Heating set-point, no cooling or heating action is active. If the present temperature is outside these limits, corresponding
Cooling or Heating action will be activated. If both, Economy and Protect mode are active, Protect mode will have priority.
PROTECT MODE
ThermwareversioncanbereadwiththePOWER ON/OFF button pressed for over 5 seconds.
FIRMWARE VERSION

Andivi – TRC-D – Technical Manual
10
08/14, fw. ver. V1.2, V1.3
It is highly recommended for this mode to be operated by trained engineers because it is related to system parameters that will
affect the control results. To operate:
1. Press UP and DOWN buttons for over 5 seconds to enter Engineer mode.
2. Press UP or DOWN button to rotate the menu item and press MODE button to enter the item.
3. Press UP or DOWN button to change the setting and press MODEbuttontoconrmthesettingandreturntomenuitem
selection. If no button is pressed for 10 seconds, it will go back to menu item selection. The setting won’t be changed then.
4. To leave Engineer mode, rotate till “End” and press MODE button or leave the button intact for 10 seconds.
5. Engineer mode can be locked for the user. In this case, it is not possible to enter this mode with the above procedure. For
safety reasons, entering the Engineer mode is still possible with the UP and DOWN buttons pressed for over 60 seconds.
6. Engineermodeoperationowchart:
ENGINEER MODE OPERATION
E02
Setting
Previous No button pressed
for 10s under menu
item selection
E01
Setting
E02
End User
Mode
E01
Fig. 4-1:
Engineer mode operation
sequence

Andivi – TRC-D – Technical Manual
11
08/14, fw. ver. V1.2, V1.3
ENGINEER MODE MENU ITEMS DESCRIPTION
Item Mnemonic Description °C Type °F Type Step
Default Range Default Range
1 ESIC Protect (PROT) Cooling set-point 30.0 20.0~40.0 86.0 68.0~104.0 0.1°C/°F
2 ESIH Protect (PROT) Heating set-point 15.0 00.0~25.0 59.0 32.0~77.0 0.1°C/°F
3LOC
Locking buttons and functions
18
(Lock
MODE
and
POWER
buttons)
0~127
18
(Lock
MODE
and
POWER
buttons)
0~127 1
Bit Value:
0: Unlock / enable
1: Lock / disable
Bit Denition:
Bit 0: Local PROTECT
detection
Bit 1: MODE button
Bit 2: UP/DOWN
button
Bit 3: FAN SPEED
button
Bit 4: ON/OFF button
Bit 5: Local Economy
detection
Bit 6: Engineer mode
Bit 7: Not used
Examples:
0: Unlock / enable all
1: Disable Local
PROTECT
2: Lock MODE button
3: Both 1 and 2
4: Lock UP/DOWN
button
5: Both 1 and 4
7: 1, 2, and 4
8: Lock FAN SPEED
button
16: Lock POWER
button
127: Lock/disable all
4 baud Baud rate 19200
2400 bps
4800 bps
9600 bps
19200 bps
19200
2400 bps
4800 bps
9600 bps
19200 bps
5 Prty Parity / Data / Stop bits 8N2
8O1
8E1
8N1
8N2
8N2
8O1
8E1
8N1
8N2
6 nodE Modbus Node ID 247 1~247 247 1~247 1
7 Unit Unit °C °C/°F °C °C/°F
8 type Type of room controller E-type B,C,E E-type B,C,E
9 db Deadband for Cooling/Heating valve control 4.0 0~10.0 7.2 0~18.0 0.1°C/°F
10 Pb Not used
11 diFF Stage differential 0.5 0.1~1.0 0.9 0.1~1.8 0.1°C/°F
12 SP-L Low limit for temperature set-point 10.0 0~50.0 50.0 32.0~122.0 0.1°C/°F
13 SP-H High limit for temperature set-point 30.0 0~50.0 86.0 32.0~122.0 0.1°C/°F
14 ESI PROTECTcontactdenition 1 0~1 1 0~1 0: N.O. / 1: N.C.
15 OFSt Offset for built-in temperature sensor 0.0 -9.0~9.0 0.0 -17.0~17.0 0.1°C/°F
16 rS Source of temperature sensor 0 0~2 0 0~2
0: Built-in /
1: Remote
2: Built-in +
remote
(average)
17 F-Pb Proportional band for fan control 4.0 0~10 7.2 0~18 0.1°C/°F
18 i-db Not used
19 LFAn Lowest fan speed used for fan auto mode 0 0~1 0 0~1 0: Stop /
1: Low speed
20 PvLC Display present value of temperature or set-
point for normal displaying 0 0~1 0 0~1 0: Display PV /
1: Display SP
21 PtCF Present temperature to anti-freezing 10 0~15 50 32~59 0.1°C/°F
22 AntF Anti-Freezing Protection On On/Off On On/Off
23 I-t Not used
24 Pit Period of sensor suffocating time 20 0~120 20 0~120 1 sec.
25 ESI2 Economycontactdenition 1 0~1 1 0~1 0: N.O. / 1: N.C.
26 EoSt Offset for external temperature sensor 0.0 -9.0~9.0 0.0 -17.0~17.0 0.1°C/°F
27 ES2C Economy (ECON) Cooling set-point 27.0 20.0~40.0 80.6 68.0~104.0 0.1°C/°F
28 ES2H Economy (ECON) Heating set-point 18.0 00.0~25.0 64.4 32.0~77.0 0.1°C/°F
29 Fand Fan off delay 0 0~600 0 0~600 10 sec.

Andivi – TRC-D – Technical Manual
12
08/14, fw. ver. V1.2, V1.3
30 OP-L Not used
31 SPAn Not used
32 rE-C Not used
33 rE-H Not used
34 HFAn Maximum fan speed 3 0~3 3 0~3 1
35 OutC
Output control
Bit Value:
0: output controlled with internal r. controller
1: output directly controlled via Modbus
communication
Bit denition:
Bit 0: DO1 - output Cooling valve
Bit 1: DO2 - output Heating valve
Bit 2: DO3 - output Fan Stage I
Bit 3: DO4 - output Fan Stage II
Bit 4: DO5 - output Fan Stage III
Bit 5 – Bit7: Not used
Note: Max. 3 outputs can be active at the
same time.
0 0~31 0 0~31 1
36 Outr
Inverted valve outputs
Bit Value:
0: Normal output N.O.
1: Inverted output N.C.
Bit denition:
Bit 0: DO1 - output Cooling valve
Bit 1: DO2 - output Heating valve
Bit 2 - bit7: Not used
0 0~3 0 0~3 1
37 FAnr Fan control 1 0~1 1 0~1
0: In fan Manual
mode fan is
active also in
case of inactive
Cooling/Heating
valve /
1: Fan can be
active only in
case of active
Cooling/Heating
valve
38 FCOL Fan enable in Cooling mode 1 0~1 1 0~1 0: Disabled /
1: Enabled
39 FHEt Fan enable in Heating mode 1 0~1 1 0~1 0: Disabled /
1: Enabled
40 Ao1d Not used
41 AO2d Not used
42 tFAn Minimum time previous fan stage upward 300 0~9990 300 0~9990 10 sec.
43 IFAn Integral time (I-part) PI regulator for fan
control 1000 0~9990 1000 0~9990 10 sec.
44 ESIt Protect mode ON delay time via digital
input 0 0~600 0 0~600 10 sec.
45 FOnt Fan ON delay time in AUTO mode 10 0~9990 10 0~9990 10 sec.
46 Ret1 Return to factory defaults
47 tESt Self-diagnostic
48 End Exit Engineer mode

Andivi – TRC-D – Technical Manual
13
08/14, fw. ver. V1.2, V1.3
Transmission
• Physical layer: RS485 (2 wires)
• Baud rate: 19200 bps
• Data format (RTU mode): 1 start bit, 8 data bits, no parity check, 2 stop bit
Modbus
• Address range: 1~247.
• Suppose function code: 1, 2, 3, 4, 5, 6, 15, 16, 23.
• Data format: address | function code | data 1 | … | data n | CRC-16 low byte | CRC-16 high byte
• Data bytes: 252 bytes (max.)
• Temperature representation: the original temperature degree value has to be multiplied by 10 to be saved in the register.
• Examples: 25.5°C is represented by: 00 FF (in hex) i.e. 255 (in dec.)
• 5.0°C is represented by: 00 32 (in hex) i.e. 50 (in dec.)
NETWORK SPECIFICATIONS

Andivi – TRC-D – Technical Manual
14
08/14, fw. ver. V1.2, V1.3
Function
code
Register
address Description Definition
05/15 1 Remote room controller On/Off control 0: Off / 1: On
05/15 2
Remote control for Protect mode
(Active only when the local PROTECT detection is disabled. Please refer to
Modbus holding register address 6, and Engineer table parameter 03 - LOC.)
0: Protect mode not active /
1: Protect mode active
05/15 3
Remote control for Economy mode
(Active only when the local ECONOMY detection is disabled. Please refer to
Modbus holding register address 6, and Engineer table parameter 03 - LOC.)
0: Economy mode not active /
1: Economy mode active
05/15 4
Direct control for DO1 - Cooling valve
(Active only in case of active bit 0 of output direct control register - refer to
Modbus holding register address 38 and Engineer table parameter 35 - OutC.)
0: Not active / 1: Active
05/15 5
Direct control for DO2 - Heating valve
(Active only in case of active bit 1 of output direct control register - refer to
Modbus holding register address 38 and Engineer table parameter 35 - OutC.)
0: Not active / 1: Active
05/15 6
Direct control for DO3 - Fan Stage I
(Active only in case of active bit 2 of output direct control register - refer to
Modbus holding register address 38 and Engineer table parameter 35 - OutC.)
0: Not active / 1: Active
05/15 7
Direct control for DO4 - Fan Stage II
(Active only in case of active bit 3 of output direct control register - refer to
Modbus holding register address 38 and Engineer table parameter 35 - OutC.)
0: Not active / 1: Active
05/15 8
Direct control for DO5 - Fan Stage III
(Active only in case of active bit 4 of output direct control register - refer to
Modbus holding register address 38 and Engineer table parameter 35 - OutC.)
0: Not active / 1: Active
READ/WRITE COILS (FUNCTION CODE 01/05/15)
Function
code
Register
address Description Definition
01 1 Status of room controller 0: Off / 1: On
01 2
Status of Protect mode
(Active only when the local PROTECT detection is disabled. Please refer to
Modbus holding register address 6, and Engineer table parameter 03 - LOC.)
0: Protect mode not active /
1: Protect mode active
01 3
Status of Economy mode
(Active only when the local ECONOMY detection is disabled. Please refer to
Modbus holding register address 6, and Engineer table parameter 03 - LOC.)
0: Economy mode not active /
1: Economy mode active
01 4
Status of direct control for DO1 – Cooling valve
(Active only in case of active bit 0 of output direct control register - refer to
Modbus holding register address 38 and Engineer table parameter 35 – OutC.)
0: Not active / 1: Active
01 5
Status of direct control for DO2 – Heating valve
(Active only in case of active bit 1 of output direct control register - refer to
Modbus holding register address 38 and Engineer table parameter 35 – OutC.)
0: Not active / 1: Active
01 6
Status of direct control for DO3 - Fan Stage I
(Active only in case of active bit 2 of output direct control register - refer to
Modbus holding register address 38 and Engineer table parameter 35 - OutC.)
0: Not active / 1: Active
01 7
Status of direct control for DO4 - Fan Stage II
(Active only in case of active bit 3 of output direct control register - refer to
Modbus holding register address 38 and Engineer table parameter 35 - OutC.)
0: Not active / 1: Active
01 8
Status of direct control for DO5 - Fan Stage III
(Active only in case of active bit 4 of output direct control register - refer to
Modbus holding register address 38 and Engineer table parameter 35 - OutC.)
0: Not active / 1: Active

Andivi – TRC-D – Technical Manual
15
08/14, fw. ver. V1.2, V1.3
READ DISCRETE INPUT (FUNCTION CODE 02)
Function
code
Register
address Description Definition
02 1
Status of Protect mode
(Effective only when the local PROTECT detection is enabled. Please
refer to Modbus holding register address 6, and Engineer table
parameter 03 - LOC.)
0: Protect mode not active /
1: Protect mode active
02 2 Status of Heating/Cooling action 0: Not active / 1: Active
02 3 Relay 1 (Cooling valve) 0: Not active / 1: Active
02 4 Relay 2 (Heating valve) 0: Not active / 1: Active
02 5 Relay 3 (Fan Stage I) 0: Not active / 1: Active
02 6 Relay 4 (Fan Stage II) 0: Not active / 1: Active
02 7 Relay 5 (Fan Stage III) 0: Not active / 1: Active
02 8
Status of Economy mode
(Effective only when the local ECONOMY detection is enabled.
Please refer to Modbus holding register address 6, and Engineer
table parameter 03 - LOC.)
0: Economy mode not active /
1: Economy mode active
02 9 Status of Anti-Freezing Protection 0: Not active / 1: Active

Andivi – TRC-D – Technical Manual
16
08/14, fw. ver. V1.2, V1.3
READ/WRITE hOLDING REGISTER (FUNCTION CODE 03/06/16/23)
Function
code
Register
address Description Definition
03/06/16/23 1 SP 0~500 (0~50.0°C)
03/06*/16*/23* 2Heating/Cooling mode (*“Command write” only for
Cooling or Heating mode selectable type) 0: Cool / 1: Heat
03/06/16/23 3 Fan mode 0: Off / 1: Manual Stage I / 2: Manual Stage II /
3: Manual Stage III / 4: Auto
03/06/16/23 4 Protect (PROT) Cooling set-point °C: 200~400 (20.0~40.0°C) / °F: 680~1040 (68.0~104.0°F)
03/06/16/23 5 Protect (PROT) Heating set-point °C: 0~250 (00.0~25.0°C) / °F: 320~770 (32.0~77.0°F)
03/06/16/23 6 LOCK
Locking buttons and functions
Bit Value:
0: Unlock / enable
1: Lock / disable
Bit Denition (Low Byte):
0: Local PROTECT
detection
1: MODE button
2: UP/DOWN buttons
3: FAN SPEED button
4: POWER ON/OFF button
5: Local ECONOMY
detection
6: Engineer mode
7: Not used
Examples:
0: Unlock / enable all
1: Disable Local
PROTECT
2: Lock MODE
button
3: Both 1 and 2
4: Lock UP/DOWN
button
5: Both 1 and 4
7: 1, 2, and 4
8: Lock FAN SPEED
button
16: Lock POWER
button
127: Lock/disable all
03/06/16/23 7 Baud rate 0: 2400 / 1: 4800 / 2: 9600 / 3: 19200
03/06/16/23 8 Data/Parity/Stop bits 0: 8O1 / 1: 8E1 / 2: 8N1 / 3: 8N2
03/06/16/23 9 Modbus node ID 1~255
03/06/16/23 10 °C / °F 0: °C / 1: °F
03/06/16/23 11 Type of room controller 0: E type / 1: B type / 2: C type
03/06/16/23 12 Deadband for Cooling/Heating valve control °C: 0~100 (0~10.0°C) / °F: 0~180 (0~18.0°F)
03/06/16/23 13 Not used
03/06/16/23 14 Stage differential °C: 1~10 (0.1~1.0°C) / °F: 1~18 (0.1~1.8°F)
03/06/16/23 15 Low limit for temperature set-point °C: 0~500 (0~50.0°C) / °F: 320~1220 (32.0~122.0°F)
03/06/16/23 16 High limit for temperature set-point °C: 0~500 (0~50.0°C) / °F: 320~1220 (32.0~122.0°F)
03/06/16/23 17 PROTECTcontactdenition 0: N.O. / 1: N.C
03/06/16/23 18 Offset for built-in temperature sensor °C: -90~90 (-9.0~9.0°C) / °F: -170~170 (-17.0~17.0°F)
03/06/16/23 19 Sensor 0: Built-in / 1: Remote / 2: Built-in + Remote
(average)
03/06/16/23 20 Proportional band for fan control °C: 0~100 (0~10.0°C) / °F: 0~180 (0~18.0°F)
03/06/16/23 21 Not used
03/06/16/23 22 Lowest fan speed used for fan auto mode 0: Stop / 1: Low speed
03/06/16/23 23 Display present value of temperature or set-point
for normal displaying 0: Display PV / 1: Display SP
03/06/16/23 24 Present temperature to anti-freezing °C: 0~150 (0~15.0°C) / °F: 320~1220 (32.0~122.0°F)
03/06/16/23 25 Anti-Freezing Protection 0: Off / 1: On
03/06/16/23 26 Not used
03/06/16/23 27 Sensor suffocating time 0~20 seconds
03/06/16/23 28 ECONOMYcontactdenition 0: N.O. / 1: N.C
03/06/16/23 29 Offset for external temperature sensor °C: - 90~90 (-9.0~9.0°C) / °F: -170~170 (-17.0~17.0°F)
03/06/16/23 30 Economy (ECON) Cooling set-point °C: 200~400 (20.0~40.0°C) / °F: 680~1040 (68.0~104.0°F)
03/06/16/23 31 Economy (ECON) Heating set-point °C: 0~250 (00.0~25.0°C) / °F: 320~770 (32.0~77.0°F)
03/06/16/23 32 Fan off delay 0~600 s
03/06/16/23 33 Not used
03/06/16/23 34 Not used
03/06/16/23 35 Not used
03/06/16/23 36 Not used

Andivi – TRC-D – Technical Manual
17
08/14, fw. ver. V1.2, V1.3
03/06/16/23 37 Maximum fan speed 0: Off / 1: Stage I / 2: Stage II / 3: Stage III
03/06/16/23 38
Output control
Note: Max. 3 outputs can be active at the same
time.
Bit value:
0: Output controlled with internal r. controller
1: Output directly controlled via Modbus
communication
Bit denition:
Bit 0: DO1 - output Cooling valve
Bit 1: DO2 - output Heating valve
Bit 2: DO3 - output Fan Stage I
Bit 3: DO4 - output Fan Stage II
Bit 4: DO5 - output Fan Stage III
Bit 5 - bit7: Not used
03/06/16/23 39 Inverted valve outputs
Bit value:
0: Normal output N.O.
1: Inverted output N.C.
Bit denition:
Bit 0: DO1 - output Cooling valve
Bit 1: DO2 - output Heating valve
Bit 2 - bit7: Not used
03/06/16/23 40 Fan control
0: In fan Manual mode fan is active also in case
of inactive Cooling/Heating valve / 1: Fan can be
active only in case of active Cooling/Heating valve
03/06/16/23 41 Fan enable in Cooling mode 0: Disabled / 1: Enabled
03/06/16/23 42 Fan enable in Heating mode 0: Disabled / 1: Enabled
03/06/16/23 43 Not used
03/06/16/23 44 Not used
03/06/16/23 45 Minimum time previous fan stage upward 0~9990 sec.
03/06/16/23 46 Integral time (I-part) PI regulator for fan control 0~9990 sec.
03/06/16/23 47 Protect mode ON delay time via digital input 0~600 sec.
03/06/16/23 48 Fan ON delay time in AUTO mode 0~9990 sec.
03/06 49 Return to factory defaults 1: Reset to factory defaults

Andivi – TRC-D – Technical Manual
18
08/14, fw. ver. V1.2, V1.3
READ INPUT REGISTER (FUNCTION CODE 04)
NOTICE:
If a value of a register is changed on the room controller (with buttons), a next write command to “this value” will be ignored,
and the room controller will not reply back anything. Those registers are:
1. Modbus Function 05,15 register address 01.
2. Modbus Function 06,16,23 register address 01~48.
For example, if users re-set the set-point value with buttons, a next Modbus command Fun.06/16/23 reg. address 01 from DDC/
BMS will be ignored and the room controller will not reply back any to DDC/BMS sent. (Note: While a value of a register is chang-
ing on the room controller (with buttons), any write command to “this value” will be ignored, but the room controller will reply
back the same data which DDC/BMS sent.)
This special strategy is integrated because registers must be changeable on both sites (master and slave).
Function
code
Register
address Description Definition
04 1 Current temperature 200~1000 (-20.0~100.0°C)
04 2 Fan speed 0: Off / 1: Stage I /
2: Stage II / 3: Stage III
04 3 Cooling controller 0: Not active / 100: Active
04 4 Heating controller 0: Not active / 100: Active
04 5 Cooling valve output 0: Not active / 100: Active
04 6 Heating valve output 0: Not active / 100: Active
04 7 Temperature of built-in sensor -200~1000 (-20.0~100.0°C)
04 8 Temperature of external sensor -200~1000 (-20.0~100.0°C)
04 9 Software version 10H~FFH (V1.0~VF.F)

Andivi – TRC-D – Technical Manual
19
08/14, fw. ver. V1.2, V1.3
ATTENTION!
In the event of an incorrect connection of the room controller or a short
circuit in the installation and actuators, irreparable damage to the room
controller can occur. Therefore, pay special attention during the installation
and follow the instructions carefully!
EU DECLARATION OF CONFORMITY
We, Andivi, declare that this device is in compliance with the essential
requirements and other relevant provisions of Directive 2004/108/EC.
SAFETY WARNINGS
This device must be installed according to the applicable norms.
This device is for indoor use only.
Do not attempt to repair the device yourself; an after-sales service is
available.Anychangesormodicationstothisunitnotexpresslyapproved
by the party responsible for compliance could void the user’s authority to
operate the equipment.
IMPORTANT INFORMATION ABOUT YOUR RIGHTS AND OBLIGATIONS, AS
WELL AS LIMITATIONS AND EXCLUSIONS THAT MAY APPLY TO YOU,
YOUR RIGHTS AND THIS LIMITED WARRANTY
This Limited Warranty gives you specic legal rights. You may also have
other legal rights that vary by state, province or jurisdiction. The disclaimers,
exclusions, and limitations of liability under this Limited Warranty will not
apply to the extent prohibited by applicable law. For a full description of
your legal rights you should refer to the laws applicable in your jurisdiction
and you may wish to contact a relevant consumer advisory service.
WHAT THIS LIMITED WARRANTY COVERS; PERIOD OF COVERAGE
Andivi d.o.o., Zagrebska cesta 102, 2000 Maribor, Slovenia (“Andivi”)
warrants to the owner of the enclosed product that the product contained in
this box (“Product”) will be free from defects in materials and workmanship
for a period of two (2) years [one (1) year for Factory Refurbished Products]
from the date of delivery following the original retail purchase (the
“Warranty Period”). If the Product fails to conform to this Limited Warranty
during the Warranty Period, Andivi will, at its sole discretion, either (a)
repair or replace any defective Product or component; or (b) accept the
return of the Product and refund the money actually paid by the original
purchaser for the Product. Repair or replacement may be made with a new
or refurbished Product or components, at Andivi’s sole discretion.
If the Product or a component incorporated within it is no longer available,
Andivi may replace the Product with a similar product of similar function, at
Andivi’s sole discretion. This is your sole and exclusive remedy for breach of
this Limited Warranty. Any Product that has either been repaired or replaced
under this Limited Warranty will be covered by the terms of this Limited
Warranty for the longer of ninety (90) days from the date of delivery or the
remaining Warranty Period. This Limited Warranty is transferable from the
original purchaser to subsequent owners, but the Warranty Period will not
be extended in duration or expanded in coverage for any such transfer.
TOTAL SATISFACTION RETURN POLICY
IfyouaretheoriginalpurchaseroftheProductandyouarenotsatised
with this Product for any reason, you may return it in its original condition
within thirty (30) days of the original purchase and receive a full refund.
WARRANTY CONDITIONS; HOW TO GET SERVICE IF YOU WANT TO CLAIM
UNDER THIS LIMITED WARRANTY
Before being able to claim under this Limited Warranty, the owner of the
Product must (a) notify Andivi of the intention to claim by sending and e-mail
and providing a description of the alleged failure, and (b) comply with Andivi’s
return shipping instructions, and (c) ship the Product at owner’s cost (except
where prohibited by applicable law) to Andivi for repair or replacement.
Andivi will have no warranty obligations with respect to a returned Product if
it determines, in its reasonable discretion after examination of the returned
Product, that the Product is an Ineligible Product (dened below). Andivi
will bear all costs of return shipping to owner, except with respect to any
Ineligible Product, for which owner will bear all shipping costs.
WHAT THIS LIMITED WARRANTY DOES NOT COVER
This warranty does not cover the following (collectively “Ineligible
Products”): Products marked as “sample” or sold “as is”; or Products that
havebeensubjectto:(a)modications,alterations,tampering,orimproper
maintenance or repairs; (b) handling, storage, installation, testing, or use
not in accordance with the Installation Guide or other instructions provided
byAndivi;(c)abuseormisuseoftheProduct;(d)breakdowns,uctuations,
or interruptions in electric power or the telecommunications network;
or (e) Acts of God, including lightning, re, ood, tornado, earthquake,
or hurricane. This warranty does not cover consumable parts, unless
damage is due to defects in materials or workmanship of the Product, or
software (even if packaged or sold with the Product). Andivi recommends
that you use only authorised service providers for maintenance or repair.
Unauthorised use of the Product or software can impair the Product’s
performance and may invalidate this Limited Warranty.
Andivi does not warrant that operation of the Product will be error-free
or uninterrupted or that the Product will in every case process all data
correctly.
DISCLAIMER OF WARRANTIES
Except as stated above in this limited warranty, and to the maximum extent
permitted by applicable law, Andivi disclaims all express, implied, and
statutory warranties and conditions with respect to the Product, including
theimpliedwarrantiesofmerchantability,tnessforaparticularpurpose.
To the maximum extent permitted by applicable law, Andivi also limits the
duration of any implied warranties or conditions to the duration of this
limited warranty.
LIMITATION OF DAMAGES
In addition to the above warranty disclaimers, in no event will Andivi be
liable for any consequential, incidental, exemplary, or special damages,
includinganydamagesforlostdataorlostprots,arisingfromorrelating
to this limited warranty or the Product, and Andivi’s total cumulative
liability arising from or related to this limited warranty or the Product
will not exceed the amount actually paid for the Product by the original
purchaser.
LIMITATION OF LIABILITY
Andivi disclaims all liability of any kind of Andivi’s distributors. The type of
Product peripherals that may be connected to your Product may change
from time to time. The services may be used to control your heating,
ventilation, and AC system or Product peripherals via the Product. Without
limiting the generality of the disclaimers above, all Product information is
provided for your convenience, “as is”, and “as available”. Andivi does not
represent, warrant, or guarantee that Product information will be available,
accurate, or reliable or that Product information or use of the services or
Product will decrease the energy consumption of your building. You are
solely responsible for all energy bills incurred by your home. You use all
Product information, the services, and the Product at your own discretion
and risk. You will be solely responsible for (and Andivi disclaims) any and
all loss, liability, or damages, including to your HVAC system, plumbing,
building, Product, Product peripherals, and all other items in your building,
resulting from your use of the Product information, services, or Product.
Product information provided by the services is not intended as a substitute
for direct means of obtaining the information. For example, a temperature
reading in the Product information provided by the services is not intended
as a substitute for reading the temperature as directly displayed by the
Product.
VARIATIONS THAT MIGHT APPLY TO THIS LIMITED WARRANTY
Some jurisdictions do not allow limitations on how long an implied
warranty lasts or exclusions/limitations on incidental or consequential
damages, so some of the limitations set out above may not apply to you.
Copyright Andivi © 2014 All rights reserved. Reproduction and distribution
prohibited without written authorization from Andivi.
Table of contents
Popular Thermostat manuals by other brands

Lutron Electronics
Lutron Electronics 33-00155EFS installation guide

Vemer
Vemer Thermo GSM Bianco VE715900 user manual

Campini Corel
Campini Corel ATB100 installation manual

Lennox
Lennox ComfortSense 7500 Installation and setup guide

Tekmar
Tekmar tekmarNet 552 Installation & operation manual

Bryant
Bryant IIT2-WHS-02 installation instructions