Ansul R-102 Manual

One Stanton Street / Marinette, WI 54143-2542, USA / +1-715-735-7411 / www.ansul.com
Copyright © 2014 Tyco Fire Products LP. / All rights reserved. / Part No. 418087-12
DESIGN, INSTALLATION, RECHARGE, AND MAINTENANCE MANUAL
R-102 RESTAURANT
FIRE SUPPRESSION SYSTEM


FOREWORD
UL EX3470 ULC EX3470
2014-SEP-01 REV. 11
R-102 Restaurant Fire Suppression Manual
This manual is intended for use with ANSUL®R-102
Restaurant Fire Suppression Systems.
Those who install, operate, recharge, or maintain these fire
suppression systems should read this entire manual. Specific
sections will be of particular interest depending upon one’s
responsibilities.
Design, installation, recharge, and maintenance of the system
must conform to the limitations detailed in this manual and
performed by an individual who attended an ANSUL training
program and became trained to install, recharge, design, and
maintain the ANSUL system.
Fire suppression systems are mechanical devices. They need
periodic care. Maintenance is a vital step in the performance
of your fire suppression system. As such it must be performed
in accordance with NFPA 96 (Standard for the Installation
of Equipment for the Removal of Smoke and Grease-Laden
Vapors from Commercial Cooking Equipment) and NFPA 17A
(Standard on Wet Chemical Extinguishing Systems) by an
authorized ANSUL distributor. To provide maximum assurance
that the fire suppression system will operate effectively and
safely, maintenance must be conducted at six-month intervals,
or earlier if the situation dictates. Twelve-year maintenance
must include agent tank hydrostatic testing.
ANSUL PART NO. 418087-12
ANSUL, R-102, and the product names listed in this material are marks and/or registered
marks. Unauthorized use is strictly prohibited.

R-102 Restaurant Fire Suppression Manual
p
!DANGER
Indicates a hazardous situation in which a person will expe-
rience serious personal injury or death if the situation is not
avoided.
!WARNING
Indicates a hazardous situation in which a person could expe-
rience serious personal injury or death if the situation is not
avoided.
!CAUTION
Indicates a hazardous situation in which a person could expe-
rience minor or moderate personal injury if the situation is not
avoided.
CAUTION
Addresses practices not related to personal injury, such as
a system part malfunctioning, property damage, or system
failure.
NOTICE
Addresses general practices or observations
related to system function that are not related
to personal injury.
UL EX3470 ULC EX3470
REV. 11 2014-SEP-01
EXPLANATION OF SAFETY ALERTS

UL EX3470 ULC EX3470
2014-SEP-01 REV. 11 PAGE 1
REVISION RECORDR-102 Restaurant Fire Suppression Manual
Indicates revised information.
Indicates change in page sequence.
2014-SEP-01 Complete manual has
been reformatted along
with several revised
pages that contain
updated technical
information. For clarity,
all pages have been
changed to Revision 11,
regardless of previous
revision number.
Technical information
changes have been
noted with a revision
indicator (u).
DATE PAGE REV. NO. DATE PAGE REV. NO.

UL EX3470 ULC EX3470
PAGE 2 REV. 11 2014-SEP-01
REVISION RECORD R-102 Restaurant Fire Suppression Manual
Indicates revised information.
Indicates change in page sequence.
DATE PAGE REV. NO. DATE PAGE REV. NO.

TABLE OF CONTENTS
UL EX3470 ULC EX3470
2014-SEP-1 REV. 11 PAGE TOC-1
R-102 Restaurant Fire Suppression Manual
SECTION PAGES
I. GENERAL INFORMATION 1-1 – 1-4
DESIGN AND APPLICATION 1-1
UL LISTING 1-1
SYSTEM APPROVALS 1-1
DEFINITION OF TERMS 1-1 – 1-3
II. SYSTEM DESCRIPTION 2-1 – 2-2
TOTAL SYSTEM 2-1
Single-Tank 2-1
Double-Tank 2-1
Three-Tank 2-2
Multiple-Tank 2-2
III. SYSTEM COMPONENTS 3-1 – 3-12
EXTINGUISHING AGENT 3-1
AUTOMAN REGULATED 3-1
RELEASE ASSEMBLY
(MECHANICAL)
AUTOMAN REGULATED 3-1
RELEASE ASSEMBLY
(ELECTRICAL)
REMOTE MECHANICAL RELEASE 3-2
SINGLE TANK ENCLOSURE 3-2
ASSEMBLY
RED PAINTED BRACKET ASSEMBLY 3-2
REGULATED ACTUATOR 3-3
ASSEMBLY
AGENT TANK ASSEMBLY 3-3
OEM RELEASE/BRACKET 3-3
ASSEMBLY (FOR OEM
IN-CABINET USE ONLY)
OEM REGULATED ACTUATOR 3-3
ASSEMBLY
TWO TANK ENCLOSURE ASSEMBLY 3-4
24VDC REGULATED RELEASE 3-4
ASSEMBLY
ADDITIONAL SHIPPING ASSEMBLY 3-4
GAS CARTRIDGES 3-5
NOZZLES 3-5
SILICONE LUBRICANT 3-5
SWIVEL ADAPTOR 3-6
RUBBER BLOW-OFF CAP 3-6
METAL BLOW-OFF CAP 3-6
REDUCING COUPLING 3-6
CONDUIT OFFSET ASSEMBLY 3-6
‘‘QUIK-SEAL’’ADAPTOR 3-6
‘‘COMPRESSION-SEAL’’ADAPTOR 3-7
‘‘HOODSEAL’’ADAPTOR 3-7
ASSEMBLY
COCKING LEVER/LOCK PIN 3-7
DETECTORS 3-8
PULLEY ELBOWS 3-8
SECTION PAGES
III. SYSTEM COMPONENTS 3-1 – 3-12
(Continued)
PULLEY TEE 3-8
ANSUL STAINLESS STEEL CABLE 3-8
REMOTE MANUAL PULL STATION 3-9
FLEXIBLE CONDUIT 3-9
MECHANICAL GAS VALVES 3-9
ELECTRICAL GAS VALVES 3-10
MANUAL RESET RELAY 3-10
ELECTRICAL SWITCHES 3-10
ALARM INITIATING SWITCH 3-11
REGULATOR TEST KIT 3-11
FUSIBLE LINK 3-11
MAXIMUM REGISTERING 3-11
THERMOMETER
HOSE/GROMMET PACKAGE 3-11
IN-LINE BURST DISC ASSEMBLY 3-12
(MANIFOLDED SYSTEMS ONLY)
1/4 IN. CHECK VALVE 3-12
NOZZLE AIMING DEVICE 3-12
STAINLESS STEEL ACTUATOR HOSE 3-12
AGENT DISTRIBUTION HOSE AND 3-12
RESTRAINING CABLE KIT
IV. SYSTEM DESIGN 4-1 – 4-76
NOZZLE PLACEMENT 4-1 – 4-31
REQUIREMENTS
Duct Protection 4-1 – 4-3
Transition Protection 4-4
Electrostatic Precipitator 4-4
Protection
Plenum Protection 4-5 – 4-6
Appliance Protection
Fryer – Single Nozzle Protection 4-7 – 4-9
Fryer – Multiple Nozzle Protection 4-10 – 4-12
Tilt Skillet/Braising Pan 4-12
Range Protection 4-13 – 4-17
Griddle Protection 4-18 – 4-21
Chain Broiler Protection 4-21
Horizontal Chain Broiler Protection 4-21
Overhead Chain Broiler Protection 4-22
Salamander Broiler Protection 4-23
Upright Broiler/Salamander 4-23 – 4-24
Protection
Gas-Radiant/Electric Char-Broiler 4-24
Protection
Electric Char-Broiler Protection 4-24
Lava-Rock (Ceramic) Char-Broiler 4-25
Protection
Natural Charcoal Broiler Protection 4-25
Alternate Ceramic/Natural 4-26
Charcoal Char-Broiler Protection
Wood Fueled Char-Broiler Protection 4-26
Wok Protection 4-27
Nozzle Application Chart 4-28 – 4-31
SPECIFIC APPLICATION BY MODEL 4-32 – 4-52
OVERLAPPING NOZZLE COVERAGE 4-53 – 4-60

TABLE OF CONTENTS
UL EX3470 ULC EX3470
PAGE TOC-2 REV. 11 2014-SEP-1
R-102 Restaurant Fire Suppression Manual
SECTION PAGES
IV. SYSTEM DESIGN (Continued) 4-1 – 4-76
TANK AND CARTRIDGE 4-61
REQUIREMENTS
ACTUATION AND EXPELLANT 4-61 – 4-63
GASLINEREQUIREMENTS
DISTRIBUTION PIPING 4-63 – 4-70
REQUIREMENTS
General Piping Requirements 4-63
Supply and Branch Line 4-64 – 4-65
Identification
1.5 Gallon System 4-66
3.0 Gallon System 4-67
6.0 Gallon Manifolded System 4-68 – 4-69
9.0 Gallon System 4-70
DETECTION SYSTEM 4-71 – 4-73
REQUIREMENTS
Detector Identification 4-71
Detector/Pulley Elbow/Conduit 4-71
Off-set Design Limitations
Detector Placement Requirements 4-71 – 4-72
Detection Line Requirements 4-72
Fusible Link Selection 4-72
Electric Thermal Detector 4-73
MANUAL PULL STATION 4-73
REQUIREMENTS
MECHANICAL GAS VALVE 4-74
REQUIREMENTS
ELECTRICAL GAS VALVE 4-74 – 4-75
REQUIREMENTS
Approvals 4-75
ALARM INITIATING SWITCH 4-75
REQUIREMENTS
ELECTRICAL SWITCH 4-75
REQUIREMENTS
V. INSTALLATION INSTRUCTIONS 5-1 – 5-44
INSTALLING RELEASE ASSEMBLY 5-1 – 5-3
COMPONENTS
INSTALLING THE DISTRIBUTION 5-4 – 5-5
PIPING
INSTALLING THE AGENT 5-5 – 5-8
DISTRIBUTION HOSE (FOR
CASTERED/MOVEABLEEQUIPMENT)
INSTALLING THE ACTUATION AND 5-8 – 5-12
EXPELLANT GAS LINE
INSTALLING THE DETECTION 5-13 – 5-16
SYSTEM
INSTALLING REMOTE MANUAL 5-17 – 5-18
PULL STATION
General Installation Requirements 5-17
Installation for Remote Manual Pull 5-17 – 5-18
Station Utilizing EMT Conduit Only
INSTALLING MECHANICAL 5-18 – 5-22
GAS VALVE
INSTALLING REMOTE MANUAL 5-22 – 5-34
PULL STATION OR MECHANICAL
GAS VALVE UTILIZING
FLEXIBLE CONDUIT
SECTION PAGES
V. INSTALLATION INSTRUCTIONS 5-1 – 5-44
(Continued)
INSTALLING ELECTRICAL 5-35
GAS VALVE
INSTALLING ELECTRICAL 5-36 – 5-38
SWITCHES
INSTALLING ALARM 5-39
INITIATING SWITCH
ELECTRICAL SWITCH 5-40 – 5-42
REQUIREMENTS
WIRING 24VDC REGULATED 5-43
RELEASE ASSEMBLY
VI. TESTING AND PLACING IN SERVICE 6-1 – 6-4
TESTING MANUAL PULL STATION 6-1
TESTING MECHANICAL GAS 6-1 – 6-2
VALVES
TESTING ELECTRICAL GAS 6-2
VALVES
TESTING ELECTRIC SWITCH 6-2 – 6-3
TESTING DETECTION SYSTEM 6-3 – 6-4
VII. RECHARGE AND RESETTING 7-1 – 7-6
PROCEDURES
CLEANUP PROCEDURES 7-1
RECHARGE 7-1 – 7-4
RESETTING 7-4 – 7-6
REPLACEMENT CARTRIDGE 7-6
VIII. MAINTENANCE EXAMINATION 8-1 – 8-12
SEMI-ANNUAL MAINTENANCE 8-1 – 8-5
EXAMINATION
ANNUAL MAINTENANCE 8-5
EXAMINATION
12-YEAR MAINTENANCE 8-6 – 8-11
EXAMINATION
IX. APPENDIX 9-1 – 9-18
SYSTEM SELECTION GUIDE 9-1 – 9-4
SYSTEM COMPONENT INDEX 9-5 – 9-8
PARTS LISTS 9-9 – 9-14
MULTIPLE NOZZLE FRYER 9-15 – 9-16
PROTECTION CALCULATION
EXAMPLES
WIRING DIAGRAM 9-16 – 9-17

DESIGN AND APPLICATION
The ANSUL R-102 Restaurant Fire Suppression System is
developed and tested to provide fire protection for restaurant
cooking appliances, hoods, and ducts. It is a pre-engineered
group of mechanical and electrical components for installation
by an authorized ANSUL distributor. The basic system consists
of an AUTOMAN regulated release assembly which includes a
regulated release mechanism and a liquid agent storage tank
housed within a single enclosure. Nozzles, detectors, cartridg-
es, liquid agent, fusible links, pulley tees, and pulley elbows are
supplied in separate packages in the quantities needed for each
fire suppression system arrangement.
The system provides automatic actuation; or it can be actuated
manually through a remote manual pull station. The system is
also capable of shutting down appliances at system actuation.
For appliance shutdown requirements, refer to the current ver-
sion of NFPA 17A, “Standard For Wet Chemical Extinguishing
Systems,” and NFPA 96, “Standard For Ventilation Control and
Fire Protection of Commercial Cooking Operations.”
Additional equipment includes: remote manual pull station,
mechanical and electrical gas valves, and electrical switches
for automatic equipment and gas line shut-off. Accessories can
be added, such as alarms, warning lights, etc., to installations
where required.
The R-102 system suppresses fire by spraying the plenum area,
the filters, cooking surfaces, and the exhaust duct system with
a predetermined flow rate of ANSULEX Low pH Liquid Fire
Suppressant. When the liquid agent is discharged onto a cook-
ing appliance fire, it cools the grease surface, and reacts with
the hot grease (saponification) forming a layer of soap-like foam
on the surface of the fat. This layer acts as insulation between
the hot grease and the atmosphere, thus helping to prevent the
escape of combustible vapors.
Exhaust fans in the ventilating system should be left on. The
forced draft of these fans assists the movement of the liquid
agent through the ventilating system, thus aiding in the fire sup-
pression process. These fans also provide a cooling effect in the
plenum and duct after the fire suppression system has been dis-
charged. The system is UL listed with or without fan operation.
Make up or supply air fans, internal to the exhaust hood(s) being
protected, shall be shut down upon system actuation.
Along with the fire suppression system, the total system design
must include hand portable fire extinguisher(s) located within the
cooking/restaurant area that can be used to manually suppress
a fire that may be burning in an unprotected area. Class K extin-
guisher(s) must be provided for hazards where there is a potential
for fires involving combustible cooking media (vegetable or animal
oils and fats). Refer to NFPA 10, “Standard For Portable Fire
Extinguisher,” for additional information.
UL LISTING
The R-102 Restaurant Fire Suppression System has been test-
ed and is listed by Underwriters Laboratories, Inc. as a pre-en-
gineered system. The system is in compliance with UL Test
Standard 300. These tests require extinguishment of fires which
are initiated in deep fat fryers, ranges, griddles, char-broilers,
woks, upright broilers, chain-broilers, filters, plenum chambers,
hoods, and ducts after pre-loading each appliance with a pre-
scribed amount of cooking grease. Each fire is allowed to prog-
ress to maximum intensity before the fire suppression system
is actuated.
SYSTEM APPROVALS
• UL EX3470
• ULC EX3470
• COA #5663 (NYC)
DEFINITION OF TERMS
Actuation Gas Line: Piping and/or stainless steel braided hose
assemblies from the AUTOMAN Regulated Release Assembly
which supplies high pressure nitrogen or carbon dioxide to the
Regulated Actuator Assembly for multiple-tank system actuation.
Agent Tank: A pressure vessel containing the liquid agent.
AUTOMAN Regulated Release Assembly (Electrical): An
assembly which contains the regulated release mechanism,
agent tank (ordered separately), expellant gas hose, solenoid,
and electric switch within a metal enclosure. The enclosure con-
tains knockouts to facilitate component hookups.
AUTOMAN Regulated Release Assembly (Mechanical): An
assembly which contains the regulated release mechanism,
agent tank (ordered separately), and expellant gas hose within a
metal enclosure. The enclosure contains knockouts to facilitate
component hookups.
Authority Having Jurisdiction: The ‘‘authority having juris-
diction’’ is the organization, office, or individual responsible
for ‘‘approving’’ equipment, an installation, or a procedure.
The phrase ‘‘Authority Having Jurisdiction’’ is used in a broad
manner since jurisdictions and ‘‘approval’’ agencies vary as
do their responsibilities. Where public safety is primary, the
‘‘authority having jurisdiction’’ may be a federal, state, local, or
other regional department or individual such as a fire chief, fire
marshal, chief of a fire prevention bureau, labor department,
health department, building official, electrical inspector, or
others having statutory authority. For insurance purposes, an
insurance company representative may be the ‘‘authority having
jurisdiction.’’ In many circumstances the property owner or his
designated agent assumes the role of the ‘‘authority having juris-
diction;’’ at government installations, the commanding officer or
departmental official may be the ‘‘authority having jurisdiction.’’
Blow-Off Cap: A siliconized rubber or metal cap which covers
the end of the nozzle to protect the nozzle tip and minimize
cooking grease migration into the nozzle orifice.
Branch Line: The agent distribution piping which extends from
the supply line to the nozzle(s).
SECTION 1 – GENERAL INFORMATION
UL EX3470 ULC EX3470
2014-SEP-01 REV. 11 PAGE 1-1
R-102 Restaurant Fire Suppression Manual

DEFINITION OF TERMS (Continued)
Bursting Disc: A disc installed in the tank adaptor which min-
imizes the remote chance of siphoning of the agent into the
discharge piping during extreme temperature variations.
Cartridge: A hermetically sealed, steel pressure vessel con-
taining nitrogen or carbon dioxide gas used to pressurize the
agent tank.
Cooking Appliance: Includes, but is not limited to, fryers, grid-
dles, ranges, upright broilers, chain broilers, natural charcoal
broilers, or char-broilers (electric, lava rock, gas-radiant, or
mesquite).
Cooking Area: Cooking area is defined as the maximum
surface that requires protection. Each type of appliance has a
defined cooking area with parameters that vary for each appli-
ance. For example, the cooking area for a griddle is the entire
flat cooking surface, while a fryer may have two areas that need
consideration, depending on whether the fryer has a dripboard
or not.
Conduit Offset Assembly: A pre-formed piece of conduit which
can be installed between the ANSUL regulated release and the
conduit to allow the wire rope for the detection, gas valve and
remote manual pull station to be installed in a more convenient
manner.
Depth: When referring to depth as a linear dimension, it is the
horizontal dimension measured from front to back of the appli-
ance or plenum.
Detector: A device which includes the detector bracket, detector
linkage, and fusible link used for automatic operation of the fire
suppression system.
Detector Linkage: A device used to support the fusible link.
Discharge Hose Assembly: An agent distribution hose to be
used with castered cooking appliances with castered supports
to allow the movement of the appliance for service or cleaning
purposes.
Distribution Piping: Piping which delivers the extinguishing
agent from the tank to each discharge nozzle. See also Supply
or Branch lines.
Ducts (or Duct System): A continuous passageway for the
transmission of air and vapors which, in addition to the contain-
ment components themselves, may include duct fittings, damp-
ers, duct filters, duct transitions, in-line or end-duct pollution con-
trol units (PCUs), and/or other items or air handling equipment.
Electrostatic Precipitator: A device used to aid in the cleaning
of the exhaust air. This device is normally installed at or near the
base of the ventilation duct or may be included as an integral
part of a pollution control unit (PCU).
Expellant Gas Line: Piping and/or hose which supplies the
nitrogen or carbon dioxide gas from the regulated release
assembly/regulated actuator assembly to each agent tank.
Flexible Conduit: A flexible means to route stainless steel cable
from the AUTOMAN Regulated Release to a manual pull station
or mechanical gas valve.
Flow Number: Term used in system design to describe the flow
capacity of each nozzle used to determine the quantity of tanks
needed to cover a certain group of hazards.
Fusible Links: A fixed temperature heat detecting device
employed to restrain the operation of a mechanical control until
its designed temperature is reached, allowing separation of the
link and system operation.
Gas Valve: An electrically or mechanically operated device
used to shut off the gas supply to the cooking equipment when
the system is actuated.
Gas Valve Air Cylinder: An air cylinder, located in the release
mechanism, which operates pneumatically to mechanically
unlatch a mechanical gas valve actuator, causing the gas valve
to close upon system actuation.
High Proximity: Indicates a distance (vertically) between the
nozzle tip and the surface of the appliance being protected.
Hood: A device provided for cooking appliances to direct and
capture grease-laden vapors and exhaust gases from cooking
appliances. It shall be constructed in a manner which meets the
requirements of NFPA 96.
Liquid Agent: A potassium-based solution used for the knock-
down and suppression of fire.
Low Proximity: Indicates a distance (vertically) between the
nozzle tip and the surface of the appliance being protected.
Maximum Length of Cooking Appliance: The maximum
dimension, on any side, which may be protected by one nozzle.
Maximum Piping: Specified length of piping and number of
fittings which must not be exceeded for each system.
Medium Proximity: Indicates a distance (vertically) between
the nozzle tip and the surface of the appliance being protected.
Minimum Piping: Minimum length of distribution piping required
between the agent tank outlet and any nozzle protecting a
range, fryer, or wok.
Nozzle: A device designed to deliver the liquid agent with a
specific flow rate and stream pattern.
Overlapping Protection: When discharge nozzles are spaced
equally apart over one or more appliances requiring protection.
Nozzles used in this manner provide area protection of eligible
appliances within the protected area. Two types of overlapping
protection is available: full hood continuous protection and group
protection. Overlapping protection is in addition to appliance spe-
cific coverages.
Plenum: The space enclosed by the filters and the portion of the
hood above the filters.
Pre-engineered System: NFPA 17A defines a pre-engineered
system as one which has “…predetermined flow rates, nozzle
pressures, and quantities of liquid agent.” The R-102 system, as
prescribed by UL (Underwriter’s Laboratories), has specific pipe
sizes, maximum and minimum pipe lengths and numbers of fit-
tings, and number and types of nozzles. The hazards protected
by this system are also specifically limited as to type and size by
UL based upon actual fire tests. All limitations on hazards that
can be protected and piping and nozzle configurations are con-
tained in the R-102 installation and maintenance manual which
is part of the UL listing.
SECTION 1 – GENERAL INFORMATION
UL EX3470 ULC EX3470
PAGE 1-2 REV. 11 2014-SEP-01
R-102 Restaurant Fire Suppression Manual

DEFINITION OF TERMS (Continued)
Pulley Elbow: A device used to change the direction of the wire
rope which runs between: the regulated release mechanism
and the detectors, the regulated release mechanism and the
mechanical gas valve, and/or the regulated release mechanism
and the remote manual pull station.
Pulley Tee: A device used to change the direction of two wire
ropes which run from a regulated release or a regulated actu-
ator to two remote manual pull stations, or from two regulated
releases or regulated actuators to a single mechanical gas valve
or from one regulated release or regulated actuator to two gas
valves.
Regulated Actuator Assembly: An assembly which contains
the regulator, pneumatic actuator, agent tank, and expellant gas
hose within a metal enclosure. This assembly is used to pressur-
ize additional agent tanks in a multiple tank system.
Regulated Release Mechanism: An enclosed device within
the AUTOMAN regulated release assembly which releases the
expellant gas, activates alarms, and/or shuts off other devices
when signaled automatically by a detector or manually with a
remote pull station.
Regulator: A device used to regulate the pressure from the
nitrogen cartridge into the agent tank(s) when the system is
actuated.
Remote Manual Pull Station: A device which provides manual
actuation of the system from a remote location.
Remote Mechanical Release: A device that provides actua-
tion gas, activates alarms, and/or shuts off other devices when
signaled automatically by a detector, or manually with a remote
pull station.
Salamander Broiler: A broiler very similar in design to the
upright broiler. A salamander broiler is used for general broiling
of meats and fish, toasting, and holding/warming foods. Most
contain a removable grease drip tray.
Series Detector: Any detector located in-line between the regu-
lated release assembly and the terminal detector.
Silicone Lubricant: A heat-resistant organic compound used to
lubricate O-rings, rubber and mechanical components.
Supply Line: The agent distribution piping which extends from
the agent tank outlet and serves as a manifold for the branch
lines.
Terminal Detector: The last in a series of detectors, or the only
detector used in a single-detector system. This detector is thus
named because it is at the point at which the wire rope ends,
or ‘‘terminates.’’ There is only one terminal detector per detection
system.
Transition: An extension of the hood or canopy which allows for
the smooth transmission of gases, air, and vapors between the
hood opening and the base of the ventilation duct.
Vent Plug: A device used to prevent pressure build-up within
the agent tank or agent distribution lines due to temperature
fluctuations.
SECTION 1 – GENERAL INFORMATION
UL EX3470 ULC EX3470
2014-SEP-01 REV. 11 PAGE 1-3
R-102 Restaurant Fire Suppression Manual

NOTES:
SECTION 1 – GENERAL INFORMATION
UL EX3470 ULC EX3470
PAGE 1-4 REV. 11 2014-SEP-01
R-102 Restaurant Fire Suppression Manual

TOTAL SYSTEM
There are four types of R-102 Restaurant Fire Suppression
Systems:
1. Single-tank System
2. Double-tank System
3. Three-tank System (1 Cartridge)
4. Multiple Tank System (Three Tanks or More – Multiple
Cartridges)
The type of system required for the particular installation will be
determined through the guidelines covered in “System Design.”
Additional equipment which may be required to complete the
system design is explained in the “System Components” sec-
tion. Additional devices covered are: remote manual pull sta-
tions, mechanical and electrical gas shut-off valves, electrical
switches, and pressure switches.
Single-Tank System
The R-102 single-tank system is available with a stainless steel
enclosure and consists of:
1. AUTOMAN Regulated Release Assembly (Electrical or
Mechanical)
2. Nitrogen Cartridge and/or Carbon Dioxide Cartridge
3. ANSULEX Low pH Liquid Fire Suppressant
4. Discharge Nozzles
5. Detection Components
6. Additional Devices (As Required)
The regulated release assembly contains the regulated release
mechanism, agent tank, expellant gas hose for agent tank hook-
up, and enclosure knockouts to facilitate installing detection sys-
tem and additional equipment. Refer to “System Components”
section for individual component descriptions.
FIGURE 2-1
000133
Double-Tank System
The R-102 double-tank system is available with stainless steel
enclosures and consists of:
1. AUTOMAN Regulated Release Assembly (Electrical or
Mechanical)
2. Nitrogen Cartridge and/or Carbon Dioxide Cartridge
3. ANSULEX Low pH Liquid Fire Suppressant
4. Enclosure or Bracket Assembly
5. Discharge Nozzles
6. Detection Components
7. Additional Devices (As Required)
The regulated release assembly contains the regulated release
mechanism, agent tank, expellant gas hose for agent tank
hookup, and enclosure knockouts to facilitate installing expellant
piping, detection system, and additional equipment.
The enclosure or bracket assembly is mounted separately but
within the guidelines of the regulated release assembly expellant
gas piping requirements to ensure simultaneous actuation of the
system. Refer to “System Components” section for individual
component descriptions.
FIGURE 2-2
008321
SECTION 2 – SYSTEM DESCRIPTION
UL EX3470 ULC EX3470
2014-SEP-01 REV. 11 PAGE 2-1
R-102 Restaurant Fire Suppression Manual

TOTAL SYSTEM (Continued)
Three-Tank System (1 Cartridge with Three 3.0 Gal Tanks
ONLY)
The R-102 three-tank system is available with stainless steel
enclosures and consists of:
1. AUTOMAN Regulated Release Assembly (Electrical or
Mechanical)
2. Double Tank Enclosure Assembly
3. Nitrogen Cartridge
4. ANSULEX Low pH Liquid Fire Suppressant
5. Discharge Nozzles
6. Detection Components
7. Additional Devices (As Required)
The regulated release assembly contains the regulated release
mechanism, agent tank, expellant gas hose for agent tank
hookup, and enclosure knockouts to facilitate installing expellant
piping, detection system, and additional equipment.
The double tank enclosure assembly is mounted separately but
within the guidelines of the regulated release assembly expellant
gas piping requirements to ensure simultaneous actuation of the
system. Refer to “System Components” section for individual
component descriptions.
FIGURE 2-3
008322
Multiple Tank System (Three Tanks or More – Multiple
Cartridges)
The R-102 multiple-tank system is available with stainless steel
enclosures and consists of:
1. AUTOMAN Regulated Release Assembly
(Electrical or Mechanical) or AUTOMAN Remote Release
Assembly(ies)
2. Nitrogen Cartridge(s) and/or Carbon Dioxide Cartridge(s)
3. Regulated Actuator Assembly(ies)
4. ANSULEX Low pH Liquid Fire Suppressant
5. Enclosure or Bracket Assembly(ies)
6. Discharge Nozzles
7. Detection Components
8. Additional Devices (As Required)
The regulated release assembly contains the regulated release
mechanism, agent tank, expellant gas hose for agent tank
hookup, and enclosure knockouts to facilitate installing actua-
tion piping, expellant piping, detection system, and additional
equipment.
The remote release assembly(ies) is used in large systems or
multi-hood systems to actuate regulated actuator assembly(ies)
ONLY. The remote release assembly contains a release mecha-
nism (unregulated), with enclosure knockouts to facilitate install-
ing the actuation piping, expellant piping, detection system, and
additional equipment.
Each regulated actuator assembly is mounted separately but
within the guidelines of the regulated release assembly actua-
tion/expellant gas piping requirements to ensure simultaneous
actuation of the system. The assembly contains the pneumatic
actuator, regulator, agent tank, expellant gas hose for agent
tank hookup, and enclosure plugs to facilitate installing expellant
piping.
Each enclosure or bracket assembly is mounted separately but
within the guidelines of the regulated release assembly or reg-
ulated actuator assembly expellant gas piping requirements to
ensure simultaneous actuation of the system. Refer to “System
Components” section for individual component descriptions.
FIGURE 2-4
008323
SECTION 2 – SYSTEM DESCRIPTION
UL EX3470 ULC EX3470
PAGE 2-2 REV. 11 2014-SEP-01
R-102 Restaurant Fire Suppression Manual

EXTINGUISHING AGENT
ANSULEX Low pH Liquid Fire Suppressant (1.5 gallon – Part
No. 79694 or 3.0 gallon – Part No. 79372) is a potassium-based
solution designed for fast knock-down and suppression of
grease-related fires. The agent is shipped in plastic containers
which provide one complete tank charge. (Refer to Section V,
Page 5-2.1, for maximum agent fill capacity.) Agent storage life
expectancy is twelve years and can be stored at a temperature of
–40 °F to 130 °F (–40 °C to 54 °C). Note: When installing agent
in R-102 system, temperature range is 32 °F (0 °C) to 130 °F
(54 °C). The distributor must record the batch numbers and date
of shipment receipt to be filed with each installation record.
“ANSULEX” LOW pH LIQUID FIRE SUPPRESSANT
3.0 GALLON 1.5 GALLON
SHIPPING WT. 35 LB (15.9 kg) SHIPPING WT. 19 LB (8.6 kg)
000136 000137 FIGURE 3-1
REGULATED RELEASE ASSEMBLY (MECHANICAL)
The AUTOMAN Regulated Mechanical Release Assembly (Part
No. 429853) contains the regulated release mechanism, expel-
lant gas hose for agent tank hookup, and enclosure knockouts
to facilitate installing actuation piping; expellant piping; detec-
tion system; and additional equipment. This regulated release
assembly is used in single, double, and multiple-tank systems
and must be mounted to a rigid surface. The release mecha-
nism can be used to interconnect both the actuation and expel-
lant gas lines as required per system design. The regulator is
designed to allow a constant flow of gas into the tank at 110 psi
(7.6 bar) when the system is actuated. The agent tank must be
ordered separately.
In single, double, and multiple-tank systems, the provided
expellant gas hose connects the agent tank to the bottom outlet
of the regulator. In double and multiple-tank system configura-
tions, the back outlet of the regulator is used as an expellant
gas feed for one additional tank-enclosure or tank-bracket
hookup. The enclosure contains the required knockouts to
facilitate this connection. If a pressure switch is to be attached
to the regulator, additional fittings are required.
The tank is mounted within the enclosure. The tank contains
an adaptor/tube assembly with a burst disc union. The burst
disc helps prevent siphoning of the agent up the pipe due to
significant temperature fluctuations in the area where the tank
is located. The tank is stainless steel and, under normal condi-
tions, requires hydrostatic testing every twelve years.
The detection and additional equipment required per system
design are connected to the release mechanism. The enclosure
contains knockouts to facilitate detection and additional hookups.
The system can be actuated automatically or manually.
Automatic actuation occurs when a fusible link within the detec-
tion system separates in a fire condition. Manual actuation of
the system occurs when personnel pull on the remote manual
pull station pull ring.
AUTOMAN REGULATED RELEASE ASSEMBLY
(MECHANICAL)
FIGURE 3-2
009454
REGULATED RELEASE ASSEMBLY (ELECTRICAL)
The AUTOMAN Regulated Electrical Release Assembly (Part
No. 429856) is identical to the mechanical version except it also
contains a factory installed 120 VAC solenoid and electrical
switch.
The solenoid is used to provide electrical actuation of the
release mechanism. The electric switch is used to protect the
solenoid by opening the circuit to the solenoid once the system
is fired. Additional electrical switches can be added as required
for automatic equipment and gas shut-off accessories, as well
as initiating audible and visual alarms.
AUTOMAN REGULATED RELEASE ASSEMBLY
(ELECTRICAL)*
FIGURE 3-3
009455
* Note: AUTOMAN Regulated Electrical Release (Part No. 429856) is not intend-
ed to be used with electric detection.
NOTE: AGENT TANK MUST BE
ORDERED SEPARATELY
(SEE PAGE 3-3)
REGULATOR
SHIPPING WT. 20.9 LB (9.5 kg)
RELEASE
MECHANISM
NOTE: AGENT TANK MUST
BE ORDERED
SEPARATELY
(SEE PAGE 3-3)
SOLENOID
SWITCH
REGULATOR
SHIPPING WT. 22.1 LB (10.0 kg)
SECTION 3 – SYSTEM COMPONENTS
UL EX3470 ULC EX3470
2014-SEP-01 REV. 11 PAGE 3-1
R-102 Restaurant Fire Suppression Manual

REMOTE MECHANICAL RELEASE
The Remote Mechanical Release (Part No. 433485) is used
to actuate up to five R-102 regulated actuators. The remote
mechanical release utilizes a 101-10 carbon dioxide cartridge
as the actuation pressure to operate the regulated actuators.
The release is housed in a stainless steel enclosure.
Also available is an OEM Remote Release/Bracket Assembly
(Part No. 439946). The OEM Remote Release/Bracket contains
the same release mechanism as the standard Remote Release,
and must be installed in a suitable equipment enclosure either
horizontally or vertically. The remote release contains all the
necessary mounting and conduit holes needed to fully install
the assembly. Note: OEM Release/Bracket Assembly must be
installed high enough in cabinet so that there is sufficient room
to install and remove cartridge.
FIGURE 3-4
009456
SINGLE TANK ENCLOSURE ASSEMBLY
The Single Tank Enclosure Assembly (Part No. 429870) is used
in double and multiple-tank systems and must be mounted to
a rigid surface near the regulated release or regulated actuator
assembly its expellent gas line will be connected to.
The enclosure is designed for mounting either a 1.5 gallon (Part
No. 429864) or a 3.0 gallon tank (Part No. 429862) in a mini-
mum amount of space.
ENCLOSURE ASSEMBLY
FIGURE 3-5
000142
RED PAINTED BRACKET ASSEMBLY
The Bracket Assembly (Part No. 429878) is used in double and
multiple-tank systems and must be mounted to a rigid surface
near the regulated release assembly or regulated actuator
assembly that its expellant gas line will be connected to.
The tank bracket is constructed of mild steel and painted red.
It is designed for mounting the tank in a minimum amount of
space. The Bracket Assembly can only be utilized with 3.0 gal-
lon tanks (Part No. 429862).
BRACKET ASSEMBLY
FIGURE 3-6
000141
RELEASE
MECHANISM
SHIPPING WEIGHT:
14.4 LB (6.5 kg)
NOTE: AGENT TANK MUST
BE ORDERED
SEPARATELY
(SEE PAGE 3-3)
MOUNTING
ENCLOSURE
SHIPPING WT.
13 LB (5.9 kg)
MOUNTING
BRACKET
SHIPPING WT. 7 LB (3.2 kg)
SECTION 3 – SYSTEM COMPONENTS
UL EX3470 ULC EX3470
PAGE 3-2 REV. 11 2014-SEP-01
R-102 Restaurant Fire Suppression Manual

REGULATED ACTUATOR ASSEMBLY
The Regulated Actuator Assembly (Part No. 429850) contains the
regulator, pneumatic actuator, expellant gas hose for agent tank
hookup, and enclosure knockouts to facilitate installing expellant
piping. This assembly is used in multiple-tank systems and must
be mounted to a rigid surface.
The regulator contains two outlets 135° apart. One outlet is
used to interconnect the expellant gas hose to the enclosed
agent tank. The other outlet connects an expellant gas line to
an additional enclosure or bracket assembly. The regulator is
designed to allow a constant flow of expellant gas into each
agent tank at 110 psi (7.6 bar).
The pneumatic actuator is designed to puncture the expellant
gas cartridge seal upon receiving pressure from the regulated
release assembly actuation piping. The enclosure contains a
knockout to facilitate distribution piping hookup.
REGULATED ACTUATOR ASSEMBLY
FIGURE 3-7
000143
AGENT TANK ASSEMBLY
The agent tank shipping assembly (3 Gallon (Part No. 429862)
and 1.5 Gallon (Part No. 429864)) consists of a stainless steel
tank and an adaptor/tube assembly. The adaptor/tube assem-
bly contains a burst disc. The burst disc prevents agent leakage
due to significant temperature fluctuations in the area where
the tank is located. Under normal conditions, the tank requires
hydrostatic testing every twelve years. The date of manufacture
is stamped on the tank nameplate.
The tank is shipped uncharged and must be filled with only
ANSULEX Low pH Liquid Fire Suppressant during installation.
FIGURE 3-8
000140
OEM RELEASE/BRACKET ASSEMBLY
(FOR OEM IN-CABINET USE ONLY)
The OEM Regulated Mechanical Release/Bracket Assembly
(Part No. 79493) contains the same regulated release mecha-
nism as the standard AUTOMAN Regulated Release Assembly.
The OEM Regulated Electrical Release/Bracket Assembly (Part
No. 437324*), is identical to the mechanical version except that
it contains a factory installed 120 VAC solenoid and electrical
switch. These release/bracket assemblies must be installed in
a suitable equipment enclosure either horizontally or vertically.
They contain all the necessary mounting and conduit holes
needed to fully install the assembly. The agent tank is installed
separately and need not be bracketed once it is piped and filled.
Note: OEM Release/Bracket Assembly must be installed high
enough in cabinet so that there is sufficient room to install and
remove cartridge.
*Note: OEM Regulated Electrical Release/Bracket Assembly (Part No. 437324) is
not intended to be used with electric detection.
FIGURE 3-9
009457
OEM REGULATED ACTUATOR ASSEMBLY
The OEM Regulated Actuator Assembly (Part No. 418691)
includes the regulator, pneumatic actuator, expellant gas hose
and OEM bracket. Also available is an OEM Regulated Actuator
Assembly with all the above mentioned components except for
the bracket. This assembly is Part No. 418522.
SHIPPING WT. 4 LB (1.8 kg) FIGURE 3-10
002225
PNEUMATIC
ACTUATOR
ASSEMBLY
NOTE: AGENT TANK
MUST BE
ORDERED
SEPARATELY
(SEE PAGE 3-3)
REGULATOR
SHIPPING WT.
19 LB (8.6 kg)
MOUNTING
BRACKET
REGULATOR
RELEASE
MECHANISM
SHIPPING WT.
9.3 LB (4.2 kg)
SECTION 3 – SYSTEM COMPONENTS
UL EX3470 ULC EX3470
2014-SEP-01 REV. 11 PAGE 3-3
R-102 Restaurant Fire Suppression Manual
AGENT
TANK
TANK ADAPTOR/
TUBE ASSEMBLY
3 GALLON
SHIPPING WT.
7 LB (3.2 kg)
1.5 GALLON
SHIPPING WT.
5 LB (2.3 kg)

TWO TANK ENCLOSURE ASSEMBLY
The Two Tank Enclosure Assembly (Part No. 429872) consists
of two expellant gas hoses, two grommets, and the mounting
enclosure. The assembly is used in 9-gallon systems. It can be
coupled with a 3-gallon regulated release assembly or a 3-gal-
lon regulated actuator assembly to give a total of 9 gal (34.1 L)
of agent. Agent tanks must be ordered separately.
The tank enclosure is designed to mount in a minimum amount
of space.
SHIPPING WT.
26 LB (11.8 kg)
FIGURE 3-11
002277
24VDC REGULATED RELEASE ASSEMBLY
The 24VDC Regulated Release Assembly (Part No. 429859) is
used where electric, thermostat detection is required via the use
of a releasing control unit. This assembly consists of a 24VDC
AUTOMAN II-C regulated release mechanism, expellant gas
hose, and enclosure knockouts to facilitate installing actuation
piping, expellant piping, detection system, and additional equip-
ment. Agent tank must be ordered separately.
The system can be actuated automatically or manually.
Automatic actuation occurs when the control panel receives
a signal from the detection circuit. The panel then sends an
electrical signal to the 24VDC regulated release, causing it to
actuate. When actuation occurs, the gas cartridge is punctured,
pressurizing the agent tank and discharging the agent through
the distribution piping. Manual actuation of the system occurs
when personnel pull on the remote manual pull station pull ring.
NOTE: AGENT TANK MUST BE
ORDERED SEPARATELY
(SEE PAGE 3-3)
SHIPPING WT.
34 LB (15.4 kg)
FIGURE 3-12
002279
ADDITIONAL SHIPPING ASSEMBLIES
Several complete shipping assemblies are available containing
both the release or actuator mechanism and the agent tank.
When ordering a complete shipping assembly, order the follow-
ing part numbers:
Shipping Wt.
Part No. Description lb (kg)
430299 3.0 Gallon Mechanical Release 33 (15)
Shipping Assembly including:
429853 Mechanical Regulated
Release Assembly
429862 3.0 Gallon Tank Assembly
430300 1.5 Gallon Mechanical Release 30 (14)
Shipping Assembly including:
429853 Mechanical Regulated
Release Assembly
429864 1.5 Gallon Tank Assembly
430309 3.0 Gallon Regulated Actuator 36 (16)
Shipping Assembly including:
429850 Regulated Actuator Assembly
429862 3.0 Gallon Tank Assembly
430316 1.5 Gallon Stainless Steel Enclosure 18 (8)
Shipping Assembly including:
429870 Single Tank Mounting Box
Assembly
429864 1.5 Gallon Tank Assembly
418511 Hose Assembly
430317 3.0 Gallon Stainless Steel Enclosure 20 (9)
Shipping Assembly including:
429870 Single Tank Mounting Box
Assembly
429862 3.0 Gallon Tank Assembly
418511 Hose Assembly
430324 6.0 Gallon Stainless Steel Enclosure 40 (18)
Shipping Assembly including:
429872 Two Tank Mounting Box
Assembly
429862 3.0 Gallon Tank Assembly (2)
430332 3.0 Gallon Mounting Bracket Shipping 20 (9)
Assembly including:
429878 3.0 Gallon Mounting Bracket
Assembly
429862 3.0 Gallon Tank Assembly
SECTION 3 – SYSTEM COMPONENTS
UL EX3470 ULC EX3470
PAGE 3-4 REV. 11 2014-SEP-01
R-102 Restaurant Fire Suppression Manual

GAS CARTRIDGES
The R-102 system uses gas cartridges to store nitrogen or
carbon dioxide expellant gases under pressure until the system
is actuated, at which time the cartridge seal is punctured and
the released gas expels liquid agent from one or more tanks
through the discharge piping and out the discharge nozzles.
Four nitrogen gas cartridges and three carbon dioxide gas car-
tridges are available as shown in Figure 13.
Cartridges noted as TC/DOT are both Transport Canada (TC)
and Department of Transportation (DOT) approved. Cartridges
noted as DOT are Department of Transportation approved only.
Cartridge selection options are provided in Section 4 under
Tank and Cartridge Requirements.
NITROGEN GAS CARTRIDGES
LT-20-R LT-30-R DOUBLE-TANK LT-A-101-30
CARTRIDGE CARTRIDGE CARTRIDGE CARTRIDGE
000145 000146 000147 000148
CARBON DIOXIDE CARTRIDGES
101-10 CARTRIDGE 101-20 CARTRIDGE 101-30 CARTRIDGE
000149 000150 000151
FIGURE 3-13
Additional cartridge shipping assemblies are available for
European and Australian requirements.
Cartridge European Australian TC/DOT
Description Part No. Part No. Part No.
_________ _______ ______ _______
LT-20-R 428440 428948 423429
LT-30-R 428441 426553 423435
Double Tank 428446 426563 423493
LT-A-101-30 428442 426555 423491
101-10 – CO2 428443 N/A 423439
101-20 – CO2 428445 N/A 423441
101-30 – CO2 428444 N/A 423443
Note: For 101-10 cartridge, Part No. 15850 is DOT only.
NOZZLES
There are 11 types of discharge nozzles each designed to
distribute the liquid agent in a uniform pattern throughout the
hazard area:
1. 1/2N Nozzle 7. 245 Nozzle
2. 1F Nozzle 8. 260 Nozzle
3. 1W Nozzle 9. 290 Nozzle
4. 1N Nozzle 10. 2120 Nozzle
5. 2W Nozzle 11. 3N Nozzle
6. 230 Nozzle
Although these nozzles are similar in appearance and have
certain common parts, the tip of each nozzle is designed for a
specific application and must only be used in those areas. See
Nozzle Application Chart in Section 4 – System Design, for
individual nozzle usage. Nozzles are shipped with metal blow-
off caps included.
A 25 pack of Nozzle O-rings (Part No. 439848) is also available.
FIGURE 3-14
009474
Nozzle Identification Chart
Nozzle
Nozzle Nozzle Package Flow
Type Part No. Quantity No. Nozzle Material
1/2N Nozzle 439837 9 1/2 Chrome-Plated Body
1F Nozzle 439836 9 1 Chrome-Plated Body
1W Nozzle* 439839 25 1 Chrome-Plated Body
1N Nozzle* 439838 25 1 Chrome-Plated Body
2W Nozzle 439840 25 2 Chrome-Plated Body
230 Nozzle 439842 25 2 Chrome-Plated Body
245 Nozzle 439843 25 2 Chrome-Plated Body
260 Nozzle 439844 9 2 Chrome-Plated Body
290 Nozzle 439845 9 2 Chrome-Plated Body
2120 Nozzle 439846 9 2 Chrome-Plated Body
3N Nozzle 439841 9 3 Chrome-Plated Body
*Stainless steel versions are available in the 1W nozzle (Part No. 439864) and
the 1N nozzle (Part No. 439865).
SILICONE LUBRICANT
Dow Corning Compound 111 (Part No. 78112) is available in a
5.3-ounce tube. Compound has excellent qualities for sealing
and lubricating system components.
3/8 – 18 NPT
FEMALE THREAD
SILICONE
O-RING
NOZZLE
IDENTIFICATION INTERNAL CUP
STRAINER INSIDE
SECTION 3 – SYSTEM COMPONENTS
UL EX3470 ULC EX3470
2014-SEP-01 REV. 11 PAGE 3-5
R-102 Restaurant Fire Suppression Manual
2 IN.
(51 mm)
9 IN.
(229 mm)
11 5/8 IN.
(295 mm)
2 1/2 IN.
(64 mm)
2 1/2 IN.
(64 mm)
7 7/8 IN.
(200 mm)
3 9/16 IN.
(90 mm)
17 1/4 IN.
(438 mm)
2 1/2 IN.
(64 mm)
11 5/8 IN.
(295 mm)
2 1/2 IN.
(64 mm)
7 7/8 IN.
(200 mm)
4 3/16 IN.
(106 mm)
12 1/4 IN.
(311 mm)

SWIVEL ADAPTOR
The Swivel Adaptor Assembly consists of a swivel nut, swivel
body and swivel ball. All are chrome-plated. The swivel adaptor
allows any nozzle to be rotated approximately 30° in all direc-
tions. Swivel Adaptors must be ordered as a Swivel Adaptor
Shipping Assembly (Part No. 423572) which contains 25 Swivel
Adaptors or Part No. 419385, which contains 9 Swivel Adaptors.
FIGURE 3-15
000003
METAL BLOW-OFF CAP
The Metal Blow-Off Cap helps keep the orifice of the nozzle free
of grease or other substances that could interfere with agent
distribution.
The Metal Blow-Off Cap Package (Part No. 439861) contains
10 blow-off caps.
Also available is a 10 pack of Stainless Steel Blow-Off Caps
(Part No. 439866).
FIGURE 3-16
009475
REDUCING COUPLING
The reducing coupling (Part No. 436228) is made of stainless
steel material with 3/8 in. x 1/2 in. NPT inlet threads. If neces-
sary, the reducing coupling can be utilized when installing the
Agent Distribution Hose Line Kit (Part No. 435982). Two cou-
plings are required per Agent Distribution Hose.
FIGURE 3-17
CONDUIT OFFSET ASSEMBLY
The conduit offset assembly (Part No. 435961) is used to
change direction of the wire rope on detection, mechanical gas
valve, and remote pull station lines. The conduit offset assem-
bly can only be used in the area where the conduit attaches to
the regulated release assembly. When using the conduit offset
assembly, the maximum number of pulley elbows allowed is
16. The Conduit Offset Shipping Assembly (Part No. 436063)
consists of 6 conduit offsets.
FIGURE 3-18
000153
“QUIK-SEAL” ADAPTOR
The “Quik-Seal” adaptor is a listed mechanical bulkhead fitting
that produces a liquid-tight seal around both distribution piping
and detection conduit which runs through restaurant hoods and
ducts. The “Quik-Seal” adaptor accepts threaded pipe or con-
duit. The adaptor is available for 1/4 in. (Part No. 78196), 3/8 in.
(Part No. 77285), 1/2 in. (Part No. 77287), or 3/4 in. (Part No.
77289) pipe or conduit sizes. When using with EMT conduit, a
conduit connector must be installed in each end of the adaptor.
The “Quik-Seal” Adaptor Shipping Assembly must be ordered
as stated below:
Shipping
Assembly Hole Size
Size Part No. Qty. Required
1/4 in. 78196 24 3/4 in.
3/8 in. 77285 24 1 1/8 in.
1/2 in. 77287 24 1 1/8 in.
3/4 in. 77289 24 1 3/8 in.
FIGURE 3-19
000154
STAINLESS
STEEL WIRE
METAL CAP
SECTION 3 – SYSTEM COMPONENTS
UL EX3470 ULC EX3470
PAGE 3-6 REV. 11 2014-SEP-01
R-102 Restaurant Fire Suppression Manual
CONDUIT
COUPLING
CONDUIT
OFFSET
CONDUIT
CONNECTOR
3/8 – 18 NPT
FEMALE THREAD
3/8 – 18 NPT
MALE THREAD
30 DEGREE
ROTATION
ADAPTOR BODY
GASKET
LOCKWASHER
NUT
1/4 IN.
(6 mm)
1 3/16 IN.
(30 mm)
Other manuals for R-102
2
Table of contents
Other Ansul Fire Alarm manuals
Popular Fire Alarm manuals by other brands

Cooper Notification
Cooper Notification RSS-241575W instruction manual

Texecom
Texecom Ricochet INS742-2 installation manual

Teletek electronics
Teletek electronics SensoMAG B12L/U installation manual

Interlogix
Interlogix ESL installation instructions

Hosiden Besson
Hosiden Besson Tri-Tone Sounder Installation details

Consilium
Consilium Salwico CS4000 installation manual