
MODEL 8145 – SET UP
NOTICE
Before setting up the control for use, the amount of ventilation air being delivered (CFM) by the installed ventilation system must be measured.
Hold for 5 seconds, then release.
Throughout the Set Up Menu, the and buttons are used to change values, the Select button is used enter the value and move on to the next Set
Up Menu item.
TABLE 4 – MODEL 8145 SET UP MENU
Menu Item Values Description
HP or HC HP if wiring to a heat pump.
HC if wiring to furnace and AC.
1 – 10
Number of bedrooms –
used to calculate required
continuous ventilation rate.
LOW
500 – 7500 ft2
Square footage – used to
calculate required continuous
ventilation rate.
30 – 250 CFM Measured outdoor airflow
delivered during ventilation.
OFF,
85°F – 105°F
Ventilation high temperature
limit. Ventilation is limited
when the outdoor temperature
exceeds the setting. Turn OFF if
no high limit is desired.
OFF,
-10°F – 40°F
Ventilation low temperature
limit. Ventilation is limited
when the outdoor temperature
falls below the setting. Turn
OFF if no low limit is desired.
On, “bLnd”, OFF
ON HVAC fan turns on
whenever ventilation occurs.
bLnd (blend) HVAC fan turns
on with ventilation only when
the outdoor temperature is
outside a set range.
OFF HVAC fan is not turned on
with ventilation.
TABLE 4 – MODEL 8145 SET UP MENU
Menu Item Values Description
OFF, 60°F to 5°F
less than Vent.
High Temp. Limit
Only available when bLnd is
selected. When the outdoor
temperature is above the
setting, the HVAC fan will
be turned on to mix (blend)
outdoor air with indoor air for
tempering.
OFF, 5°F less
than Vent. Low
Temp. Limit to
55°F
Only available when bLnd is
selected. When the outdoor
temperature is below the
setting, the HVAC fan will
be turned on to mix (blend)
outdoor air with indoor air for
tempering.
See IMPORTANT
NOTE below.
“codE”, “cFrt”
codE No RH limits and any
missed ventilation due to
temperature is made up per
ASHRAE 62.2-2010.
cFrt (comfort) Adds indoor RH
limits to ventilation; ventilation
missed due to limits is not
made up.
OFF,
45% – 70% RH
Only available when cFrt is
selected. When the outdoor RH
exceeds the setting, ventilation
will not occur.
OFF,
10% – 30% RH
Only available when cFrt is
selected. When the outdoor
RH drops below the setting,
ventilation will not occur.
When all Set Up Menu options have been entered, the control will
display donE.
IMPORTANT NOTE: The 8145 control senses the temperature and humidity of the outdoor air. To prevent extended periods of inactivity, set the
control mode to codE, or if setting to cFrt (comfort), set the RH limits to OFF.
English 9