SETUP & TESTING
Dehumidifier System Settings Table
Note: Dehumidifier control can only be set to whole home if ventilation and humidification are not installed.
System setting Description
Factory default setting (bold)
and setting range
Dehumidifier Control
other dehumidifier settings will be available.)
None (no dehumidification installed)
Whole Home
Air Conditioner
Humidity Setpoint Deadband Select the minimum difference between the humidifier
and dehumidifier setpoints. (Only available if a
humidifier is installed and dehumidifier control is set
to air conditioner. Available in both set-ups.)
10 Percent RH
10 to 20 Percent RH
Cooling
Selects if dehumidification is disabled during a cooling
call. (Only available if dehumidifier control is set to
whole home.)
Yes
Dehumidifier Forces Fan Select if dehumidification can turn on the fan. (Only
available if dehumidifier control is set to whole home.)
Yes
Dehumidifier Service
Reminder
The period for displaying the “Dehum Service
control is set to whole home.)
Off
Dehumidifier Overcooling
Selects the amount of overcooling that can occur
for dehumidification. (Only available if dehumidifier
control is set to air conditioner.)
3°F (1.5°C)
Dehumidify in Vacation
Selects if dehumidification with the air conditioner is
control is set to air conditioner.
No
Yes
Sets the lowest temperature the air conditioner will
available if dehumidifier control is set to air conditioner.)
75°F (23.5°C)
Ventilation System Settings Table
Note: Ventilation can only be installed if humidification is not installed and dehumidifier control is not set to whole home.
System setting Description
Factory default setting (bold)
and setting range
Fresh Air Vent Installed Selects if ventilation is installed.
No
Yes
Fresh Air Forces Fan Selects if ventilation forces the fan on.
Yes
Fresh Air Setup Selects if ventilation is configured through the ASHRAE setup
time will be calculated using the ASHRAE recommendations.
determined based on the Fresh Air Time value.
Timed
ASHRAE
Fresh Air Time Selects how many minutes per hour that ventilation will be
active. (Only available if fresh air setup is set to timed.)
30 MIN/HR
Temp
Selects if ventilation is disabled if the outdoor temperature
is set to timed and an outdoor temperature sensor is installed.)
No
Yes
Sets the high temperature limit for ventilation. (Only available if
high limit outdoor temp set to yes.)
100°F (38°C)
Selects if ventilation is disabled if the outdoor temperature
is set to timed and an outdoor temperature sensor is installed.)
No
Yes
Sets the low temperature limit for ventilation. (Only available if
low limit outdoor temp set to yes.)
10°F (-12°C)
indoor RH limit. (Only available if fresh air setup is set to timed.)
No
Yes
Sets the high indoor RH limit for ventilation. (Only available if
high limit indoor RH is set to yes.)
60%
50% to 70%
SETUP & TESTING
The following tables contain the Indoor Air Quality system settings and their details. Default settings are shown in
bold. Some settings are only present dependent upon the value of other settings.
The use of the included outdoor temperature sensor (recommended) enables additional Indoor Air Quality functionality.
Air Cleaning System Settings Table
System setting Description
Factory default setting (bold)
and setting range
Air Cleaner Installed
air cleaning settings will be available.)
No
Yes
Change Air Filter Reminder Off
Humidifier System Settings Table
Note: A humidifier can only be installed if ventilation is not installed and dehumidifier control is not set to whole home.
System setting Description
Factory default setting (bold)
and setting range
Humidifier Installed
humidifier settings will be available.)
No
Yes
Selects auto or manual mode. Auto mode controls humidity
based on the humidity setting and outdoor temperature.
(Auto mode is only available if outdoor sensor is set to yes.)
Auto
Humidity Setpoint
Deadband
Select the minimum difference between the humidifier and
dehumidifier setpoints. (Only available if a humidifier is
installed and dehumidifier control is set to air conditioner.
Available in both set-ups.)
10 Percent RH
10 to 20 Percent RH
Humidifier Operation Selects when humidification is allowed to occur relative to
heating and fan operation.
Heat Only
Heat or Fan
Forces Fan
Change Water Panel
Reminder
displayed.
Off
1 Per Season
2 Per Season
300 Hours
600 Hours
Water Panel Reminder set
to 1 per Season)
(Change Water Panel
Reminder set to 2 per
Season)
Change Water Panel Reminder set to 1 per Season:
is displayed.
Change Water Panel Reminder set to 2 per Season:
message is displayed.
October
December
January
February
April
June
July
August
September
Second Reminder Start
message is displayed. (Only available when Change Water
Panel Reminder set to 2 per Season.)
October
December
January
February
April
June
July
August
September
INDOOR AIR QUALITY SYSTEM SETTINGS TABLES