TROUBLESHOOTING
DISPLAY IS BLANK
If Power LED is not illuminated at the
equipment control module check the
following:
• Check circuit breaker and reset if
necessary.
• Make sure power switch at heating &
cooling system is on.
• Make sure furnace door is closed securely.
HEATING SYSTEM DOES NOT RESPOND
(“HEATING” APPEARS ON SCREEN)
• Check for 24VAC at the equipment on the
secondary side of the transformer between
power and common. If voltage is not
present, check the heating equipment to
ndthecauseoftheproblem.
• Check for 24VAC between the heat terminal
(W) and the transformer common. If 24VAC
is present, the thermostat is functional.
Checktheheatingequipmenttondthe
cause of the problem.
• Check for loose or broken wires between
the thermostat and the heating equipment.
COOLING SYSTEM DOES NOT RESPOND
(“COOLING” APPEARS ON SCREEN)
• Check for 24VAC at the equipment on the
secondary side of the transformer between
power and common. If voltage is not
present, check the cooling equipment to
ndthecauseoftheproblem
• Check for 24VAC between the cooling
terminal (Y) and the transformer common.
If 24VAC is present, the thermostat is
functional. Check the cooling system to
ndthecauseoftheproblem.
• Check for loose or broken wires between
the thermostat and the cooling equipment.
FAN DOES NOT TURN ON IN A CALL FOR HEAT
• Check Installer Setting Fan Control In
Heating / Heat Pump Auxiliary Type, to
make sure the fan control is properly set to
match the type of system.
HEAT PUMP ISSUES COOL AIR IN HEAT
MODE, OR WARM AIR IN COOL MODE
• Check wiring at the terminal block to
conrmthereversingvalveisconnectedto
the proper terminal. O is active in cooling
and B is active in heating.
HEAT/COOL BOTH ON AT SAME TIME
• Check Installer Setting Equipment Type, to
make sure it is set to match the installed
heating/cooling equipment.
• Check to make sure heating and cooling
wires are not shorted together.
HEATING EQUIPMENT IS RUNNING IN
COOL MODE
• Check Installer Setting Equipment Type, to
make sure it is set to match the installed
heating/cooling equipment.
“HEATING” IS NOT DISPLAYED
• Check Installer Setting Control Setup is set
correctly.
• Change the System Mode to Heat, and set
the temperature level above the current
room temperature.
“COOLING” IS NOT DISPLAYED
• Check Installer Setting Control Setup is set
correctly.
• Change the System Mode to Cool, and set
the temperature level below the current
room temperature.
SPECIFICATIONS
ENVIRONMENT
Temperature (shipping) -30° to 150°F (-34° to 65°C)
Temperature thermostat (operating) 32° to 120°F (0° to 48°C)
Temperature equipment control module
(operating) 32° to 158°F (0° to 70°C)
Relative humidity Operating: 5% to 90% R.H. (non-condensing)
ELECTRICAL
Operating voltage 24VAC (18–30VAC)
Current Maximum: 2.5A (total), 1.0A (single output)
Maximum surge current: 5A
CONTROL
Outdoor, Remote, Leaving and Return
temperature sensor Maximum distance: 300 feet
Room temperature measurement Display range: 32° to 99°F (0° to 40°C)
Return and Leaving temperature measurement Display range: -40° to 160°F (-40° to 71°C)
Outdoor temperature measurement Display range: -40° to 130°F (-40° to 55°C)
Setpoint temperature range Heat: 40° to 90°F (4° to 32°C)
Cool: 50° to 99°F (10° to 37°C)
Setpoint humidity range Humidication:10%to50%R.H.
Dehumidication:40%to90%R.H.