TankmaticSmartRelay
Aquatech‐PressmainInstructionmanual\TankmaticsmartrelayMG‐LT 5
0.2.9 Ensuretheelectricalsupplyisthecorrectvoltage,current,frequencyandtypefortheequipment
suppliedandthatsuitablecircuitprotectionequipmentisinstalledinthesupply.Incorrectelectrical
installationcouldbeanelectricshock/burns/firehazard.
0.2.10 Whenaccessingthecontrolpaneltomakeelectricalconnectionsadoptanti‐staticprocedurese.g.
wearanti‐staticearthedwristband,toavoidriskofdamagingthecontroller.
0.2.11 AllproductsthatarepackagedtoincludePressurevessel(s)/HydraulicAccumulator(s)/Expansion
Vessel(s)areclassedas“Assemblies”underthePressureEquipmentDirective(PED).Whereunitsare
despatchedwith“Loose”vessel(s)forassemblyonsiteitisabsolutelyessentialthattheybeinstalled
asdetailedintheinstructionsusingthefittingsprovidedwhereappropriate.Failuretoobservethis
willnullifycompliancewiththePEDandmaypresentasafetyhazard.Yourwarrantymayalsobe
affected.
0.2.12 WhereHydraulicAccumulator(s)/ExpansionVessel(s)aresuppliedasalooseitem,theymustbe
installed/connectedcorrectlybeforeoperatingtheequipment,otherwiseseriousdamagefromover‐
pressure/pumpoverheatingcouldoccur.
0.2.13 Donotoperatethisequipment/pumpsetpriortocommissioning(section2.2)Thiscouldcause
irreparabledamagetosensors/equipment/pumpset/pipework/systemcomponents.
0.2.14 Isolatethesensors/equipment/pumpsetbeforepressuretestingsystem.Excesspressurecould
irreparablydamagethepressuretransducer,pressureswitches(wherefitted)andthediaphragmsof
pressurevessel/hydraulicaccumulators.
0.2.15 Whereapplicableitistheinstallers’responsibilitytoensuresubsequentpipeworketccanacceptthe
pressuresgeneratedbytheequipment/pumpsetandtoinstallanoverpressuresafetydeviceintothe
systemwithduerespecttothesuctionpressurepresentonthepumpset,thepumpclosedvalve
pressurestatedonthepump,themaximumworkingpressurestatedonanyoftheattachedpressure
vesselsandanyotherdeviceconnectedtothesysteme.g.boilers,calorifiersetc.
0.2.16 Whenchlorinationofthesystemiscarriedout,ensurethatanyresidualchlorineisremovedby
thoroughflushingasdetailedintheHSEapprovedcodeofpracticeL8,toavoiddamagingthe
sensors/equipment/pumpset.Thenormallevelofchlorinationisupto2partspermillion(ppm),but
shockdosingforsterilizationpurposes,at25‐50ppmfor24‐48hoursisacceptableaslongasall
chlorineisremovedoncetheprocessiscomplete.Chlorinationbeyondtheselimitscouldseriously
damagesensors/pumpsetcomponentsandWILLNOTbecoveredbythewarranty.
0.2.17 Theinstaller/userisresponsiblefortheinstallationofthecorrectearthingandprotectionaccordingto
validnationalandlocalstandards.Alloperationsmustbecarriedoutbyasuitablyqualifiedperson.
0.2.18 Theequipmentisonlysuitableforearthreferencedsuppliesandmustbepermanentlyearthedto
avoidelectricshockhazard.
0.2.19 TheequipmentmustbepermanentlyearthedwithappropriatesizedEarthing.
0.2.20 Equipmentcontainingvariablespeeddrives/motorshashighearthleakagecurrent>3.5mAandwill
requireadditionalearthbondingwherebyasingleconductorofincreasedsizeorduplicateearth
conductorsmustbeprovided.
0.2.21 Neverperformhighvoltageresistancetestsoncontrolpanels,variablespeeddrives/motorswithout
firstdisconnectingthepanel/drive/motorfromthecircuitbeingtestedasthiswilldamagethebuiltin
electroniccomponents.
0.2.22 Equipmentcontainingvariablespeeddrives/motorsthathasbeenstored/notpoweredupforlong
periodsoftime(i.e.1yearormore)mayrequirethevariablespeeddrive/motorcapacitorstobe
reformed.PleasecontactAquaTech‐Pressmainformoreinformation.Failuretoreformcapacitorswill
resultindrive/motordamage.
0.2.23 Metalparts(e.g.heatsinks)mayreachtemperaturesof90degreescentigrade.
0.2.24 RCD’s/ELCB’sarenotrecommendedforusewithvariablespeeddrives/motors.Wheretheiruseis
mandatoryusetypeBRCD’s.Forsinglephasesetswithinvertermotorstheearthleakagecircuit
breakermusttripoutwhenearthfaultcurrentswithDCcontent(pulsatingDC)occur.Forthreephase
setswithinvertermotorstheearthleakagecircuitbreakermusttripoutwhenearthfaultcurrents
withDCcontent(pulsatingDC)andsmoothDCearthfaultcurrentsoccur.
0.2.25 RCD’s/ELCB’ssuitableforusewithvariablespeeddrives/motorsarenotsuitableforpersonnel
protection.
0.2.26 EMC–invertermotors0.37kWto5.5kWElectromagneticdisturbance–firstenvironment(residential
areas)–unrestricteddistribution,correspondingtoCISPR11,classB,group1.Invertermotors>5.5kW