ARDETEM TPIs 2T Instruction Manual

ARDETEM - TA CO/122 2T-D 04/18 Any data in this documentation may be modified without prior notice.
ÉTUDES ET RÉALISATIONS
ÉLECTRONIQUES / INSTRUMENTATIONS / AUTOMATISME
Route de Brindas - Parc d’activité d’Arbora - N°2
69510 - Soucieu en Jarrest
FRANCE
Tél. 04 72 31 31 30 - Fax 04 72 31 31 31
Tel. Intern. 33 4 72 31 31 30 - Fax Intern. 33 4 72 31 31 31
http: //www.ardetem.com - e-mail: [email protected]
MODULE OF 2 LOGIC INPUTS
TPIs 2T
User handbook
version 02.02
Software SlimSet

p1
Summary
UE conformity declaration p2
1 . INTRODUCTION p3
1.1 General features p3
1.2 Features of the inputs p3
2 . CONFIGURATION OF THE NETWORK p4
3. DIMENSIONS - MOUNTING p5
4 . CONNECTINGS p7

p2
UE CONFORMITY DECLARATION
The manufacturer:
ARDETEM-SFERE
Route de Brindas
Parc d’activité d’Arbora n°2
69510 Soucieu en Jarrest
France
declares that the following products:
Name: Measure concentrator
Type: TPIs 2T
comply with the following directives and standards:
The EMC Directive 2014/30/UE
EN 61326-1 : 2013
The Low Voltage Directive 2014/35/UE
EN 61010-1 : 2011
The ATEX directive 2014/34/UE
EN 60079-0 : 2011 EN 60079-15 : 2010
Soucieu en Jarrest, February 14, 2017
Jacques Huguet
Signature of the Manager
This appliance has to be installed in an environment defined in pollution
degree 2 / Overvoltage category II or better for a max. altitude of 2000 m.
Before any installation or maintenance work, make sure the power supply
of the instrument is cut.
This symbole indicates that the module is protected by a double or
reinforced isolation.
The person who has designed the system (electrical installation including
the instrument) is sole responsable for the safety and must make sure it
has been designed according to the current safety standards.
This appliance contains electronic components and
should not be disposed of with the domestic waste.
It should be collected with the WEEE (Waste Elec-
trical and Electronic Equipment), according to the
current regulation.
The instrument may be connected to dangerous electrical
voltages.
It must be mounted, connected and implemented respecting
the current specific regulations, by a qualified technician, trai-
ned to the safety regulations, who will have read this manual.

p3
1. INTRODUCTION
• The TPIs 2T is a module of 2 logic inputs, extra narrow (7.2mm) designed
for DIN rail mounting.
• It belongs necessarily to a local network made up of converters and/or
output modules.
The status of its 2 inputs, as well as the result of a logical «or» or «and»
between its 2 inputs can be associated with the converter or with the output
module to perform several functions (eg.: direct driving of a relay, zero reset
of alarm recording, etc.)
• Each converter or module is fixed on the DIN rail via a 5 points footing which
allows the communication and the supply of the TPIs of the network (24Vdc
±30%).
Up to 50 TPIs can be connected on the same bus and up to 200 different
measures can be made to transit ; In this configuration the maximum scan-
ning time is 200ms.
• The programming is performed via the µUSB connector located on the front
face, which is to be connected to a computer of the type PC equipped with
the software SlimSet.
1.1 General features
Operating temperature ......................... -25°C to +70°C
Storage temperature ............................ -40°C to +85°C
Power supply........................................ 16.8 to 31.2 Vdc
Max. power draw .................................. 0.7W
Max. internal dissipation....................... 0.5W
Galvanic partition.................................. 2.5kV-50Hz-1mn between supply,logic
.............................................................. inputs, µUSB
.............................................................. (logic inputs not insulated from each other)
Listed
Installation in ATEX / IECEx area 2
Installation in division 2 cFMus
Compliance with standards:
Directive EMC 2004/108/CE ............EN 61326-1
Directive LV 2014/35/UE ..................EN 61010-1
Standard for CSA electrical safety....CSA C22.2 14-13
..........................................................UL 508 17th ed.
ATEX 94/9/CE ..................................EN 60079-0, EN 60079-15
IECEx ...............................................IEC 60079-0, IEC 60079-15
Hazardous locations.........................CSA C22.2 213
..........................................................ANSI/ISA 12.12.01
Marking:
II 3 G Ex nA IIC T4 Gc
Class I, Div.2, Groups A, B, C, D T4
1.2 Features of the inputs
Logic input:
low level < 1.2V / high level > 2.1V / Umax 18V
NAMUR input:
Supply 8.3V ±0,5V / 15mA max
Input resistance 1kOhm
low level < 1.2mA / high level > 2.1mA
Detection of the sensor rupture: i<0.1mA
NPN or contact: Supply: 15V ±10% / 20mA max (*)
Input resistance 2.7k to the 11V (Imax : 4mA)
PNP: Supply: 15V ±10% / 20mA max (*)
Input resistance 20k to the GND (Imax : 1mA)
(*) Supply limited to 8,3V if one of the 2 inputs is configured as «namur»
• Filtering:
Programmable analog filter: allows to suppress any parasite
noises.

p4
2. CONFIGURATION OF THE NETWORK Possible measure number Type of measure
200 Status logic input 1
201 Status logic input 2
202 Logical result «or» between logic input 1
and logic input 2
203 Logical result «and» between logic input
1 and logic input 2
4) Then transfer the programming of all the instruments of the bus.
Important :
From the version 2.02 of the TPIs, it is possible to transfer the programming of
the TPIs directly from the master.
For this purpose, connect yourself on the master and click on «communication
with the devices» and then «communication through the master» and then «send
the configuration of all devices».
Then transfer the programming of the master.
5) Then validate the bus. For this purpose connect yourself on the master, click on
«validate network».
This will record the configuration of the bus in order to point out any error (loss of
a module for example).
The network must always be validated after adding / removing an instrument and
after the modification of all the links between instruments.
First start by launching the configuration software SlimSet.
The purpose is to define your network using the software.
1) Connect a USB cable on the first instrument of the bus (the most on the left
or the most on the right).
Click on «communication with the devices» and then on «add the connected
device to the architecture».
The instrument will be recognized, and the software will request its position
within the architecture. Enter it, and do the same for all the instruments of the
bus.
2) Then choose the instrument which will be the master (TPIs or TPIvM) and
programme it as master if it is a TPIs (the orange led becomes active).
Important:
From the version 2.02 of the TPIs it is possible to access the configuration of
the instruments of the bus directly from the master.
In this case first connect the instrument defined as master (TPIs or TPIvM),
programme it as master if it is a TPIs and click on «communication through the
master» and then «add or remove some devices».
The software will then take up all the instruments present on the bus and read
their configuration one by one.
For each instrument detected, the SlimSet will request its position on the archi-
tecture. This position can be determined by a specific blinking of the green led
of the concerned instrument (morse code blinking: twice on, once off).
3) Then programme each of the instruments, as well as the links between ins-
truments:
for each of the outputs of the output modules (TPIs 4R, TPIs 2A/4A ...) you
must define the converter associated with this output, as well as the measure
associated with this output.

p5
3. DIMENSIONS, MOUNTING
Dimensions:............................................ 7.2 x 114 x 114 mm
Housing: ................................................. self-extinguishing of PBT
Terminals: ............................................... screwed connections (2.5mm²,
flexible or rigid)
Screw thread .......................................... M3
Max. tightening torque............................ 0.5Nm / 4.5in.lbs
Min. solid/stranded conductor section .... 0.2mm2 / 26 AWG
Max. solid/stranded conductor section ... 2.5mm2 / 14 AWG
Protection: ..............................................
case / terminals: IP20
• Mounting in switchbox: latching on symmetrical DIN rail, with footing for
the distribution of the 24Vdc power supply and the communication signals.
Instructions for assembling on 35mm DIN rail according to EN 60715
Assembling of
the footings
on the rail
BEWARE:
The polarization
tongue is at the
bottom.
Assembling of
the footings
before mounting
on DIN rail
Mounting
Unmounting
The TPIs of the nework must be mounted one
after another.
1
2
3
4
2
1

p6
• INSTALLATION IN DIVISION 2 (cFMus)
Class I, Div.2, Groups A,B,C,D T4
(GB)
The product must be installed by qualified staff, competent on the directives
and the regulation applicable to the division 2.
It must be installed in an additional protecting enveloppe ensuring a protection
at least of the type IP54.
The USB cable must be inserted or withdrawn only if the instrument has been
set off tension or if the area is safe.
The converter must be disconnected from its DIN rail footing only if the
rail supply has been set off tension or if the area is safe.
The installation must be done according to the Canadian Electrical Code Part
1 (for Canada) and the National Electrical Code / NFPA 70 (for the USA).
(FR)
Le produit doit être installé par un personnel qualifié et compétent sur les
directives et la législation applicables à la division 2.
Il doit être installé dans une enveloppe protectrice additionnelle assurant une
protection au minimum de type IP54.
Le câble USB ne doit être inséré ou retiré que si l’appareil a été mis hors ten-
sion ou si la zone est sûre.
Le convertisseur ne doit être déconnecté de son embase rail DIN que
si l’alimentation du rail a été mise hors tension ou si la zone est sûre.
L’installation doit être réalisée selon le Canadian Electrical Code Partie 1 (pour
le Canada) et le National Electrical Code / NFPA 70 (pour les USA).
• INSTALLATION IN AREA 2 (IECEx, ATEX)
II3G Ex nA IIC T4 Gc
The product must be installed by qualified staff, competent on the directives
and the regulation applicable to the area 2.
It must be installed in a protecting enveloppe conform with the EN 60079-15.
The operator must ensure an external protection in order to prevent transient
disturbances on the supply of the modules higher than 40% of the nominal
voltage.
The USB cable must be inserted or withdrawn only if the instrument has been
set off tension or if the area is safe.
The converter must be disconnected from its DIN rail footing only if the
rail supply has been set off tension or if the area is safe.
The installation must be done according to the EN 60079-14 : 2014.

p7
4. CONNECTINGS
TPIs 2T
8765
A
B
C
D
E
+
-
communication
24VDC
±30%
}
1
2
3
4
contact 2
0V
+5V
logic 2
namur 2
contact 1
0V
+5V
logic 1
namur 1
NPN 1
(+)
NPN 2
(+)
(-)
PNP 1
(-) PNP 2
LED «master»
LED «voltage
presence»
Table of contents
Other ARDETEM Control Unit manuals
Popular Control Unit manuals by other brands

Tews Technologies
Tews Technologies TPMC866-TM-20 user manual

Weidmüller
Weidmüller DPA/AVX operating instructions

Leonard
Leonard MEGATRON 10N INSTALLATION ADJUSTMENT SERVICE

Dometic
Dometic MCS-CTRL Installation and operation manual

LOGICDATA
LOGICDATA CBX-1 user manual

Danfoss
Danfoss PVE 3 Series installation guide

CAME
CAME PXC2-32 Installer manual

Atkinson Electronics
Atkinson Electronics GSCM-MINI-D quick guide

Stem
Stem NC86 operating instructions

NXP Semiconductors
NXP Semiconductors Digital DNA MSC8102 User Guide and Hardware Detailed Design Description

Lenze
Lenze EMF2192IB Mounting instructions

Armstrong
Armstrong GP-2000 manual