
11
Installation Requirements
The DFSI water heater requires connections to adequate sources of low-pressure, saturated steam; electrical power (120VAC
/ 60 Hz /1 Ph., typ.); and clean (usually potable) cold water. Connections to a steam condensate return system, a recirculated
return water circuit, and to a system that will utilize, distribute, or store the mixed (heated), potable water are also required.
Although the physical construction of the heater incorporates highly corrosion-resistant materials and watertight control
enclosures, the device is intended to be located within a structure or protective enclosure furnished by the end user. The
enclosure should provide adequate free space around the heater for service and maintenance. In locations w/ severe climates,
means to protect the heater from low (freezing) and high ambient temperatures may also be required.
Proper installation usually requires mounting and securing the heater to a rigid base or foundation that can provide adequate
bearing support, prevent movement and tipping, and resist differential settling. The base or foundation material should be able
to withstand, without significant degradation, occasional exposure to moisture and wetting.
Support all steam and water piping connecting to the heater from a fixed structure capable of independently holding the
operational weight of the piping. Consider employing design features in the piping and supports to accommodate thermal
expansion and contraction of the piping during normal operation.
Plumbing:
A licensed plumber or pipe fitter familiar with local code requirements should install the DFSI water heater and they
should also oversee commissioning. Refer to the typical installation diagram that follows for a depiction of the location of
connection points.
1. Before beginning any installation or maintenance procedure, always ensure that all supply, return, and recirculation water
and steam lines are isolated, i.e. shutoff valves are closed.
2. Ensure any residual internal pressure in the system or connecting pipework is carefully relieved.
3. Allow hot parts to cool before commencing work, to avoid the risk of burns.
4. Always wear appropriate personal protective equipment (PPE) before carrying out any installation or maintenance work.
5. Place the DFSI water heater in the desired mounting location ensuring that there is adequate free space from adjacent
walls and other obstructions for service and maintenance access. If movement or tipping of the water heater could occur,
secure the heater stand or base to the floor.
6. Connect an appropriately-sized, boiler steam supply line to the heat exchanger steam connection.
Note: In the event the tube bundle must be extracted from the heat exchanger, allow sufficient clearance between
the removable head end of the heat exchanger and any obstructions to enable complete tube bundle removal from
the heater (refer to the “Dimensions” table for tube bundle lengths). Assure sufficient clearance distances on all
other sides of the heater assembly for service access.
Note: The water supply pressure must be controlled such that the maximum operating conditions (refer to page 8)
are not exceeded. Use a pressure reducing valve (PRV) to control pressure fluctuations or reduce line pressure where
necessary. Water pressure must exceed steam pressure at all times.
Note: The DRV is designed for continuous recirculation. A recirculation pump (not supplied) must be installed
on the recirculation line to the unit. The recirculation pump should operate continuously. Avoid switched power
sources, timer-controlled power sources, and power sources tied to energy conservation circuits.
7. Connect an appropriately-sized, condensate return line to the outlet of steam trap(s).
8. Connect inlet cold water supply to the inlet piping, isolation valve (tagged accordingly).
9. Connect outlet mixed water supply to the discharge piping, isolation valve (tagged accordingly).
10. Connect recirculation return line to the recirculation piping, isolation valve (tagged accordingly).
11. Pipe the outlet from the factory-supplied water, pressure relief valve to a sanitary drain to avoid contact with hot water
should a pressure release occur. The drain line should terminate over the drain with the open end exposed to atmospheric
pressure. The relief valve, drain line should slope downward toward the sanitary drain in a manner that allows all water to
completely flow from the line. Standard cracking pressure for the factory-supplied, pressure relief valve is 165 PSI.
Designs, materials, weights and performance ratings
are approximate and subject to change without notice.
Visit armstronginternational.com for up-to-date information.
Each DRV40 requires a minimum continuous recirculation of 5 gpm.
Each DRV50 or DRV80 requires a minimum continuous recirculation of 10 gpm.