
Armstrong International
221 Armstrong Blvd, Three Rivers, MI 49093 - U.S.A.
Tel: (269) 279-3602 Fax: (269) 279-3130
Designs, materials, weights, and performance ratings are
approximate and are subject to change without notice.
Visit armstronginternational.com for the most updated information.
Page 15 of 32
Preventative Maintenance, cont.
Clean-in-Place (CIP) Procedures for ReadiTemp®(RT)
1. Close the steam inlet following lockout/tagout procedures.
2. Close the condensate line.
3. Stop recirculation pump(s), close the cold water inlet and recirculation return line, depressurize the exchanger
(via blowdowns or HWO pressure gauge ball valve with hose to drain), then close the hot water outlet.
4. De-energize the RT control panel following lockout/tagout procedures.
5. Remove the 1” (25.4 mm) NPT pipe plug from the RT cold water inlet CIP connection and replace it with the
close pipe nipple supplied on union-end of the CIP hose. See CIP unit detail on following pages.
6. Connect a hose to the close pipe nipple and position to drain.
7. Open the cold water inlet to flow water through the heat exchanger, and through the garden hose to drain. Flush
for 10 minutes, or until the outside of the heat exchanger is cool to the touch.
8. While the heat exchanger is being flushed, prepare the Armstrong CIP unit for service: Connect CIP hoses –
with ball valves closed – to the pump discharge and tank inlet connections. Verify that the tank drain valve is
closed. Open the pump discharge and tank inlet valves. Fill the holding tank with Rite-Qwik™ (minimum of 10
gallons (37.8 liters). See CIP unit detail on following pages.
9. Close the RT cold water inlet, and allow flush-water to drain completely.
10. Disconnect garden hose.
11. Remove the 1” (25.4 mm) NPT pipe plug from the RT hot water outlet CIP connection and replace it with the
close pipe nipple supplied on union-end of the CIP hose.
12. Connect the CIP hose from the pump discharge outlet to the close pipe nipple installed on the hot water outlet.
Verify ball valve is closed.
13. Connect the CIP hose from the tank inlet to the close pipe nipple installed on the cold water inlet. Verify ball
valve is closed, and leave tank fill opening uncapped to allow venting.
14. Connect the Armstrong CIP unit power cord to a GFI protected circuit, verify the tank-to-pump valve is open,
and start the pump.
15. Slowly open the ball valve on CIP hose connected to hot water outlet.
16. Slowly open the ball valve on CIP hose connected to cold water inlet. The CIP unit will begin circulating
Rite-Qwik™ through the heat exchanger.
17. Fizzing and foaming in the CIP unit tank will indicate scale is being actively dissolved. Monitor level of foaming,
and be prepared to stop pump to prevent overflow.
18. When the Rite-Qwik™ is no longer fizzing or foaming, the cleaning process is complete. Note that the maximum
Rite-Qwik™ circulation time is three hours.
19. Stop the pump, close the CIP hose ball valve connected at the hot water outlet, and allow the heat exchanger
to drain to the CIP tank.
20. Close the CIP hose ball valve connected at the cold water inlet.
21. Disconnect the hose from the CIP tank inlet, and position to drain.
22. Open the cold water inlet to allow fresh water to flush through the heat exchanger, and through the CIP hose to
drain. Flush for 15 minutes.
23. Close the cold water inlet, and disconnect the CIP hoses from the ReadiTemp®.
24. Remove the close pipe nipples and replace the 1” (25.4 mm) NPT pipe plugs. Return the close pipe nipples to
the CIP hoses for safekeeping.
25. Recommission the ReadiTemp®following IMPORTANT instructions on page 12.
26. See Clean-in-Place unit maintenance details on following page.