Artidor AR-024 User manual

User Manual
Explosion-safe occupancy sensor
Type series AR-024
II 3 G Ex ec mc IIC T6 Gc
II 3 D Ex mc tc IIIC T80ºC Dc

User manual explosion-safe AR-024 occupancy sensor
Issue April 2020 2 / 8
1. Safety Instructions
The AR-024 occupancy sensor is an explosion-safe product suitable for use in hazardous areas with explosion hazard
from flammable gases, vapors, mist and dust, classified as Zone 2 or Zone 22.
This manual must be read and understood for safe use of the occupancy sensor. All warnings and instructions must be
followed.
Installation must be carried out by personnel trained and qualified in explosion safety taking the instructions
mentioned on the equipment and in this manual into consideration. Local regulations that apply to the installation
must be followed.
Connect this equipment to the supply voltage for which it is designed.
Isolate electrical power to the occupancy sensor before electrical installation.
The protection degree against ignition “Encapsulation”, “Increased safety” and “Protection by enclosure” have
been applied to the apparatus. The enclosure may not be opened if the occupancy sensor is energized.
Installation of cables may not invalidate the “Protection by enclosure”, therefore only IP65 cable glands with the a
clamping size meeting the cable diameter should be used.
All unused openings should be plugged off in a properly closed and tight way.
Either decommission the occupancy sensor or do not use it when it is damaged.
During installation of the occupancy sensor national safety regulations must be observed.
Only use the occupancy sensor under the environmental conditions for which it is specified. Deviating
environmental conditions can contribute to damage to the equipment and may lead to possible danger to the life
of the user.
Do not use the occupancy sensor at temperatures deviating from the specified ambient temperature range.
Follow all instructions written on the equipment and as mentioned in this manual.
Repairs may only be carried out by the manufacturer or by a person appointed by the manufacturer.
Modifications to the equipment or changes to the design are not permitted.
The product may only be used for the function for which it is designed and shall be maintained in a good and
clean condition.
If these instructions are not followed, the explosion safety of the equipment cannot be guaranteed. The equipment
could then endanger the life of the user and could cause the ignition of an explosive atmosphere. Consequently, Artidor
as the manufacturer will waive any responsibility.
2. Description
The explosion-safe occupancy sensor AR-024 is based on passive infrared technology and capable of detecting
movements of heat sources. Thanks to the wide opening angle and its 10 m range, this sensor is suitable for

User manual explosion-safe AR-024 occupancy sensor
Issue April 2020 3 / 8
monitoring large areas. The occupancy sensor is designed for use inside large buildings for example warehouses and
combines energy saving and the protection of the environment in addition to convenient lighting.
Motion sensors switch the light depending on movements and the ambient light. Lighting will be switched off. The
sensor itself does not emit any radiation and is therefore called “passive”. Unlike motion sensors, occupancy sensors
can also switch off lighting if there is sufficient daylight, because of their advanced mixed light measurement (the
principle on which occupancy sensors are based). Do not install sensors near heat sources like air-conditioning units,
lights or radiators. The sensor electronics offers an potential free contact for switching up to 1,150 VA load.
The occupancy sensor is mounted on top of a coated aluminum housing. The explosion safety to gas and dust is
arranged by the appliance of protection degrees against ignition “encapsulation”, “molding”and “protected by
enclosure”.
The Artidor AR-024 occupancy sensor is certified in accordance with European Directive 2014/34/EU (ATEX 114) for
use in gas or dust hazardous areas and is CE marked.

User manual explosion-safe AR-024 occupancy sensor
Issue April 2020 4 / 8
3. Characteristics
The characteristics of the occupancy sensor can be summarized as follows;
Extended range of detection.
Coated aluminum housing and adjustable stainless steel mounting bracket.
Provided with two Ex e cable glands.
Manufactured on the basis of the European Directive 2014/34/EU (ATEX 114).
Suitable for use in gas and dust hazardous areas classified as zone 2 and 22.
Explosion safety category and protection degree against ignition applied:
II 3 G Ex ec mc IIC T6 Gc
II 3 D Ex mc tc IIIC T80˚C Dc.
Protection degree against the ingress of water and dust IP 65.
Suitable for indoor use.
4. CE - Marking
The occupancy sensor complies to the European Directives for EMC and ATEX and implicit to the Low Voltage
Directive. With regard to explosion safety the occupancy sensor has been designed and manufactured on the basis of
the essential health and safety requirements of European Directive 2014/34/EU (ATEX 114) relating to Group II
Category 3GD. Harmonized European construction standards have been applied fulfilling the essential requirements of
the directives.
5. Application
The explosion-safe AR-024 occupancy sensor has been designed for and is suitable for use in hazardous classified
areas due to flammable gases, vapors, mist, fibers and dust. Because it is explosion-safe and certified on the basis of
Group II Category 3GD of the ATEX Directive it is suitable for use in the following types of zones in explosion
hazardous areas:
for combustible gases, vapors and mist: zone 2
for combustible fibers and dust: zone 22.
6. Technical data
Explosion safety category: ATEX II 3GD
Protection against ignition: Ex ec mc IIC T6 Gc, Ex mc tc IIIC T80˚C Dc
Conformity: European Directive 2014/34/EU (ATEX 114) and 2014/30/EU (EMC)
Standards applied: EN 60079-0:2018, EN 60079-7:2015 / A1:2018, EN 60079-18:2015 / A1:2017 and
EN 60079-31:2014
Sensor: Passive infrared; 0,8 W power consumption
Mounting height: 2 –10 m
Range of coverage: An oval area of 24 x 44 m
Registration angle: Circular 360°
Dimmer setting: 10 –2,000 Lux
Preset time: 15 seconds –30 minutes
Supply voltage: 230 VAC ± 10%

User manual explosion-safe AR-024 occupancy sensor
Issue April 2020 5 / 8
Switch power AC1: 1,150 VA (resistive and light inductive loads)
Output: Potential free contact
Electrical connections: Terminals 8 x 2,5 mm²
Material: Die cast aluminum housing (RAL 7015, slate grey), cable glands nickel plated
brass
Entries: M16 or M20 cable glands (2x)
Sealed against moisture and dust: IP 65 according to EN 60529
Mounting bracket: Stainless steel mounting bracket, mounting holes Ø 6,5 (4x), distance 60 x 60 mm
Ambient temperature: -20 ˚C to +50 ˚C
Housing dimensions (L x W x H): 120 x 120 x 195 mm (including mounting bracket, excluding cable glands)
Sensor dimensions 65 x Ø98 mm
Weight: 1,860 g (incl. mounting bracket)
7. Marking and warning on the equipment
The marking label as shown below will be attached to the occupancy sensor:
8. Installation instructions
Installation of explosion-safe equipment such as this product must be carried out by personnel specially trained
and qualified to do this, following the relevant requirements of the installation standard EN 60079-14.
For the installation and use of this product the relevant safety regulations and also the generally recognized latest
state of the technology apply.
During assembly, care must be taken that the framework, screws and surface are strong enough to take the
weight of the occupancy sensor.
Isolate power from the electrical supply cable prior to installation.
Install the connection cable and make sure that it is protected from mechanical and chemical influences.
OCCUPANCY SENSOR
II 3 G Ex ec mc IIC T6 Gc Type: AR-024
II 3 D Ex mc tc IIIC T80ºC Dc 230 VAC, IP65
Cert. ARTIDOR 20ATEX9999X Year: 2020
TF & Serial No.: AS123456 -20 °C < Ta < +50 °C
ARTIDOR Explosion Safety B.V.
Emopad 38, 5663 PB Geldrop, The Netherlands, www.artidor.com

User manual explosion-safe AR-024 occupancy sensor
Issue April 2020 6 / 8
The occupancy sensor offers 8 connection terminals:
Power supply: Potential free contact:
L 230 VAC NO connection 1
N Neutral NO connection 2
PE Protective earth
R Connection for slave
S Switch for semi-automatic mode
9. Operating instructions
All setting can be done by use of the infrared remote control. The settings are explained in the OEM manual that is
supplied with the product.
Mechanical alignment: The detection area is oval shaped. Install the unit in such a manner that the markings on the
housing are positioned in the longitudinal direction of the area to be monitored. Do not install sensors near heat
sources like air-conditioning units, lights or radiators.
10. Troubleshooting
The functional indicators in the case of the ARTIDOR AR-024 (red and green LED‘s) have several functions.
Red and green LED indicating self-checking mode (over a period of 60 seconds following mains‘-supply lock-on)
Flashing at intervals of 1 second
EEPROM / memory empty
Flashing rapidly
EEPROM / memory contains information

User manual explosion-safe AR-024 occupancy sensor
Issue April 2020 7 / 8
Red LED as an indicator of status
Flashing irregularly
Movements are detected within the area of coverage
Flashing regularly
Sensor identifies bright, light off (dependent upon operating mode)
Not illuminated
Sensor identifies dark, light on (dependent upon operating mode)
Flashing extremely rapidly
Too bright / Too dark / Undefined
Red LED as an acknowledgement of receipt for commands from the remote control
Illuminated for 1 seconds
Signal validly received
Illuminated for 0.25 seconds
Not-accepted command, sensor blocked
Flashing extremely rapidly
Not-accepted command, occurs, for example, when an attempt is made to set a twilight-value that is too high or
too low
Red LED as an acknowledgement of receipt for commands from the remote control
Red and green LEDs flash 3x briefly every 5 seconds
Indicates semi-automatic mode
Red and green LEDs light up alternately
Determining the light value for automatic shutdown with sufficient daylight. (This is only indicated with a set lag
time of 30 minutes.)
11. Maintenance
For the maintenance of the AR-024 occupancy sensor the requirements as stated in EN 60079-17 apply. If the
occupancy sensor or the connection cable is no longer in good condition, very dirty or damaged, it must be repaired or
cleaned immediately. The power supply to the occupancy sensor must be switched off and may only be restored after
the maintenance has been carried out and approved.
The advised maintenance cycle for this occupancy sensor depends on its specific use and must therefore be agreed
upon with the user for the expected use.
12. Repair
If repairs are carried out in an incompetent manner, the explosion-safety of the occupancy sensor can no longer be
guaranteed. Therefore it is preferred that the occupancy sensor is returned to the manufacturer for repair.
13. Removal / re-use
The equipment can be completely processed as electronic waste. For processing regarding disposal or reuse of the
product and its packaging, national disposal and environmental laws and legislation must be taken into consideration.

User manual explosion-safe AR-024 occupancy sensor
Issue April 2020 8 / 8
This document is subject to change without notice.
Other manuals for AR-024
1
Table of contents
Other Artidor Accessories manuals