ASENWARE AW-FP100 Series User manual

ASENWARE LTD.
ADDRESSABLE FIRE ALARM
CONTROL PANEL
1
July, 2017 Prepared By :AK

ASENWARE LTD.
6
CHAPTER 1
GENERAL INFORMATION
1.1 INTRODUCTION
Asenware AW-FP100 Series Fire Alarm Control Panel
are intelligent panel which are carefully designed to
make it suitable for most of applications. It can be
configured with other panels or control systems. It’s
user friendly functionality makes it suitable to program
and configure the devices. 7” touchscreen display
gives the information for fire alarm, trouble ,
supervisory and other related information all the time.
1.2 SYSTEM FEATURES
•7” Touchscreen LCD Color Display which gives
necessary and additional information as described
in EN:54-2
•Delay function for zones for Notification Appliance
Circuits (NACs)
•2 wire cable for all addressable devices
•Zone test and individual device testing
•Zone Disable and individual device isolation
•Delay, override and abort functionality
•User friendly : easily configurable windows using Panel itself
•250 intelligent detectors or modules for one loop circuit
•Up to 8 Loop cards can be installed and configured
•Interconnection of ….panels and other equipments
•2000* events can be stored in the history
•Mini- Printer to print the status of events
•Network with Central Control Panel
•Access Level entry to control and configure panel
•Integral power supply with charger
•Circuits can be configured as Class A or ClassB
•Fire Alarm, Fault (Trouble) and Supervisoryrelays
•Earth Fault detection
•CAN BUS Network System
•Network Available Options : GSM/IP/Cloud/ MobileAPPs

ASENWARE LTD.
7
1.3 DISPLAY AND FUNCTION KEYS
Large display screen makes the panel easily programmable,
below Figure 1.1 shows LED indicators and functions keys
available
1.3.1 Liquid Crystal Display
It displays all programming screens, as well as events, history,
device and other information. At normal condition it displays Fire,
Fault , Supervisory and general information. Mosts Recent
events are displayed on the 7” touchscreen LCD. Effortless
programming can be performed using alphanumeric keyboard.
1.3.2 Fixed Function Keys
Reset
Press RESET to eliminate all current alarms and reboot the system. The whole process takes 30-
60s.RESET clear all latched alarms and other events as well as turn off event LEDs. If alarms or
other off-normal events exist after reset, they will resound the system and relight the LEDs.
Evacuate
Press this key, holding it down for 2 seconds, to activate all silenceable fire output circuits.
Panel Buzzer Silence
By pressing this key, the panel sound will be silenced but LED will keep open.
Remote Sounder Silence
By pressing this key, it will silence all Notification Appliances.
Test
For Lamp Test, press this key to test the LED indicators on the left of the keypad, the panel circuit
LEDs.

ASENWARE LTD.
8
1.3.3 LED Indicators
Table 1.1 LED Indicators
LED INDICATOR
COLOR
FUNCTION
Power
Greeen
Illuminate when power supply is on
Fire Alarm
Red
Illuminates when at least one fire alarm event exists
General Fault
Yellow
Illuminates when at least one fault occurs
Evacuate
Yellow
Illuminates when evacuation or drill process occurs
System Fault
Yellow
Illuminates when any system is in fault or system is not working
as expected
Panel Buzzer Silence
Yellow
Illuminatewhenpanelissilencedandstayflashinguntilpanelis
reset
Supervisory
Yellow
Illuminates when at least one fire alarm event exists
Remote Sounder
Silence
Yellow
IlluminatewhenNotificationAppliances issilencedandstay
flashing until panel is reset
General Disable
Yellow
Illuminates when disable has been performed
Test
Yellow
Illuminate when the panel carries out Lamp test for all LEDs
1.4 SYSTEM COMPONENTS
AW FP 100 Series Fire Alarm Control Panel are composed of the following main parts
1.4.1 Main Control
The main control part is responsible for processing and analyzing the data transmitted from other
parts, and activating other parts of the system based on the result of data analysis, for example,
sounding the buzzer of the panel when a fire is detected.
1.4.2 Display Element
The display element provides main output interface for alarm signal, fault, supervisory and
interface for routine maintenance and query.

ASENWARE LTD.
9
1.4.3 Input Method
From the display, it is very convenient for the programmer to input and register the devices.
1.4.4 Power Supply
The power supply is designed to supply power to all devices in the system. The system adopts
the special firefighting equipment powered with DC 24V output, which can provide alarm or
feedback signals, such as main power fault, battery fault, battery under-voltage and battery
charging, and have a good capacity for interference.
Customer is recommended to do battery calculation for proper rating of batteries
1.4.5 Loop Card
The loop card is used as the driver of detector/module bus, which may drive 250 intelligent
detectors or intelligent modules and can be equipped with bus type fire indicating panel.
1.4.6 Interconnection with Devices
The system can get access to various intelligent smoke, heat or combination detectors
produced by the manufacturer, and the main types include detectors, modules, horn strobes ,
manual call point and so on.
The system can be interconnected to Modules, Manual Call Point, Relays, Deluge vale
and Gas System. The system can get access to multiple intelligent modules e.g. Input module
AW-D110 , Control Module AW-D112 , Supervisory Module and Isolator Module AW-D111 and
D114 respectively. Moreover, it can also get access to intelligent sounder visual indicator AW-
D106, and intelligent manual call point AW-D105. Panel can be configured with Gas
Extinguishing system, deluge system or other water based system and supervisory of various
types of valves.
1.4.7 Printer
The system is equipped with a special mini-printer as standard, which can print alarm,
supervisory and fault messages for future reference.
!

ASENWARE LTD.
10
1.4.8 Printed Circuit Board
The control panel electronics are contained on one printed circuit board that incorporates with
loop cards and the central processing unit (CPU). The built-in power supply includes an integral
battery charger. A display unit is connected over the PCB.

ASENWARE LTD.
11
1.5 TECHNICAL PARAMETERS
1.5.1 Power Rating
Mains power supply: AC 220V±20%/50Hz or DC24V;
Backup power supply: DC24V maintenance-free battery BAT12V/5AH
1.5.2 Environmental Condition
Ambient temperature: -10℃~+55℃
Ambient humidity: ≤95% (40℃±2℃, no condensation)
1.5.3 Terminals
Refer to product instructions for detailed technical parameters of the detector, module, sounder
visual indicator and so on

Other manuals for AW-FP100 Series
1
Table of contents
Popular Fire Alarm manuals by other brands

Pro-tec
Pro-tec Algo-Tec 6400 installation manual

SILENT KNIGHT
SILENT KNIGHT INTELLIKNIGHT 5808 Installation and operation manual

Simplex
Simplex 4010ES installation guide

Faraday
Faraday 15220A owner's manual

Ziton
Ziton ASWP-RF installation guide

Zeta Alarm Systems
Zeta Alarm Systems Premier Quatro QT/1 installation manual

Simplex
Simplex 4010 Installing and operating insructions

Mircom
Mircom FleX-Net BBX-1024DS Application guide

Hochiki
Hochiki FireNET FN-DAC Installation and operation manual

EMS
EMS FirePoint System 5000 maintenance

STI
STI Stopper II installation instructions

Incite Fire
Incite Fire Sigma-XT Installation and operation manual