Vighnaharta TSFC 24-2 User manual

TSFC 24-2 & 4 User Manual
Vighnaharta Technologies Pvt. Ltd. Page 1of 26
TSFC 24- 2 & 4
USER MA NUAL
Mfg. By:
Vighnaharta Technologies Pvt. Ltd.
2nd Floor,Karanjkar Estate,S.N.11/11,Nanded Gaon,Pune-411041
Contact no.: +919011033259 (Landline) Sales: +919011033260
Email: sales@vighnaharta.in | Website: http://www.vighnaharta.in
Vighnaharta Technologies Pvt. Ltd.
2nd Floor,Karanjkar Estate,
S.N.11/11,Nanded Gaon,
Pune-411041
Tel no.: +919011033259, Sales: +919011033260
Prepared By: SBK
Approved By: NMK
Doc No.: TSFC 24-2_4_UM_3_0
Rev.No.: 3_0
Eff.Date.: 20-12-2018

TSFC 24-2/4 User Manual
Vighnaharta Technologies Pvt. Ltd. Page 2of 26
Fire Alarm System Limitations
A fire alarm system—typically made up of
smoke detectors, heat detectors, manual pull
stations, audible warning devices, and a fire
alarm control panel with remote notification
capability—can provide early warning of a
developing fire. Such a system, however,
does not assure protection against property
damage or loss of life resulting from a fire.
The Manufacturer recommends that smoke
and/or heat detectors be located throughout
a protected premise following the
recommendations of the National Fire
Protection Association Standard 72 (NFPA
72), EN54 Standards, and manufacturer’s
recommendations.
Smoke detectors may not sense fire where
smoke cannot reach the detectors such as in
chimneys, in or behind walls, on roofs, or on
the other side of closed doors. Smoke
detectors also may not sense a fire on
another level or floor of a building. A
second-floor detector, for example, may not
sense a first-floor or basement fire.
Particles of combustion or “smoke” from a
developing fire may not reach the sensing
chambers of smoke detectors because:
• Barriers such as closed or partially closed
doors, walls, or chimneys may inhibit particle
or smoke flow.
• Smoke particles may become “cold,”
stratify, and not reach the ceiling or upper
walls where detectors are located.
• Smoke particles may be blown away from
detectors by air outlets.
• Smoke particles may be drawn into air
returns before reaching the detector. The
amount of “smoke” present may be
insufficient to alarm smoke detectors.
Smoke detectors are designed to alarm at
various levels of smoke density. If such
density levels are not created by developing
fire at the location of detectors, the detectors
will not go into alarm.
Heat detectors do not sense particles of
combustion and alarm only when heat on
their sensors increases at a predetermined
rate or reaches a predetermined level. Rate-
of-rise heat detectors may be subject to
reduced sensitivity over time for this reason,
the rate-of-rise feature of each detector
should be tested at least once per year by a
qualified fire protection specialist.
Audible warning devices such as bells may
not alert people if these devices are located
on the other side of closed or partly open
doors or are located on another floor of a
building. Any warning device may fail to alert
people with a disability or those who have
recently consumed drugs, alcohol or
medication. Please note that:
• Studies have shown that certain people,
even when they hear a fire alarm signal, do
not respond or comprehend the meaning of
the signal. It is the property owner's
responsibility to conduct fire drills and other
training exercise to make people aware of
fire alarm signals and instruct them on the
proper reaction to alarm signals.
A fire alarm system will not operate without
any Electrical power. If AC power fails, the
system will operate from standby batteries
only for a specified time and only if the
batteries have been properly maintained and
replaced regularly.
The most common cause of fire alarm
malfunction is inadequate maintenance. To
keep the entire fire alarm system in excellent
working order, ongoing maintenance is
required as per the manufacturer's
recommendations, and UL and NFPA
standards and EN54 standards. At a
minimum, the requirements of NFPA 72 or

TSFC 24-2/4 User Manual
Vighnaharta Technologies Pvt. Ltd. Page 3of 26
EN54 shall be followed. Environments with
large amounts of dust, dirt or high air
velocity require more frequent maintenance.
A maintenance agreement should be
arranged through the local manufacturer's
representative. Maintenance should be
scheduled monthly or as required by National
and/or local fire codes and should be
performed by authorized professional fire
alarm installers only. Adequate written
records of all inspections should be kept.
Installation Precautions
WARNING - Several different sources of
power can be connected to the fire alarm
control panel. Disconnect all sources of
power before servicing. Control unit and
associated equipment may be damaged by
removing and/or inserting cards, modules, or
interconnecting cables while the unit is
energized. Do not attempt to install, service,
or operate this unit until manuals are read
and understood.
CAUTION - System Re-acceptance Test after
Software Changes: To ensure proper system
operation, this product must be tested in
accordance with NFPA 72 after any
programming operation or change in site-
specific software. Reacceptance testing is
required after any change, addition or
deletion of system components, or after any
modification, repair or adjustment to system
hardware or wiring. All components, circuits,
system operations, or software functions
known to be affected by a change must be
100% tested.
This System meets NFPA & EN54
requirements for operation However, the
useful life of the system's standby batteries
and the electronic components may be
adversely affected by extreme temperature
ranges and humidity. Therefore, it is
recommended that this system and its
peripherals be installed in an environment
conditions specified.
Verify that wire sizes are adequate for all
initiating and indicating device loops.
Remove all electronic assemblies prior to any
drilling, filing, reaming, or punching of the
enclosure. When possible, make all cable
entries from the sides or rear. Before
making modifications, verify that they will
not interfere with battery, transformer, or
printed circuit board location.
This system contains static-sensitive
components. Always ground yourself with a
proper wrist strap before handling any
circuits so that static charges are removed
from the body. Use static suppressive
packaging to protect electronic assemblies
removed from the unit.
Like all solid state electronic devices, this
system may operate erratically or can be
damaged when subjected to lightning
induced transients. Due to such activity there
may be temporary degradation or damage
occurred. Although no system is completely
immune from lightning transients and
interference, proper grounding will reduce
susceptibility.
Follow the instructions in the installation,
operating, and programming manuals. These
instructions must be followed to avoid
damage to the control panel and associated
equipment. Fire Panel operation and
reliability is depend upon proper installation.

TSFC 24-2/4 User Manual
Vighnaharta Technologies Pvt. Ltd. Page 4of 26
RECORD OF REVISION
Rev
Date
Prepared
By
Reviewed
By
Approved
By
Description/Remarks on
Release
2_0
20-11-17
SBK
NMK
NMK
Initial draft
3_0
20-12-18
MDC
NMK
NMK
NAC Silence Time Menu
removed from Menu options

TSFC 24-2 & 4 User Manual
Vighnaharta Technologies Pvt. Ltd. Page 5of 26
Abbreviations
TSFC 24-2 & 4
TrueSafe Fire Cloud System with 2/4 Input Zones
IDC
Initiating Device Circuit
NAC
Notification Appliance Circuit
ACK
Acknowledge
MCP
Manual Call Point
PFC
Potential Free Contact

TSFC 24-2/4 User Manual
Vighnaharta Technologies Pvt. Ltd. Page 6of 26
Contents
Abbreviations................................................................................................................... 5
1. Introduction........................................................................................................ 7
1.1 Overview ................................................................................................................. 7
1.2 System Features ....................................................................................................... 7
1.3 Technical Specifications ............................................................................................. 8
1.4 Controls and Indications ............................................................................................ 9
1.4.1 Controls ..................................................................................................... 9
1.4.2 LED Indications ........................................................................................... 9
1.4.3 LCD Indication .......................................................................................... 10
1.4.4 Buzzer Indication ...................................................................................... 10
1.5 Components ........................................................................................................... 10
2. Installation ....................................................................................................... 11
2.1 Installation Precaution ............................................................................................. 11
2.2 Mounting Details ..................................................................................................... 11
2.3 Panel Wiring ........................................................................................................... 12
2.3.1 Field Wiring Diagram ................................................................................. 13
2.3.3 Initiating Device Circuit (IDC) ..................................................................... 13
2.3.4 Output Circuits ...................................................................................... 14
2.4 Maintenance........................................................................................................... 15
2.4.1 Walk Test ................................................................................................. 15
2.4.2 Servicing.................................................................................................. 15
2.4.3 Periodic inspection and test of system......................................................... 16
2.5 Do’s and Don’ts ...................................................................................................... 17
2.5.1 Do’s......................................................................................................... 17
2.5.2 Don’ts...................................................................................................... 18
3. System Programming .................................................................................................... 19
3.1 Menu Options ......................................................................................................... 19
3.1 Zone1......................................................................................................... 20
3.2 Zone 2........................................................................................................ 20
3.3 NAC 21
3.4 NAC Auto Silence ......................................................................................... 21
3.5 Auto Key Lock ........................................................................................................ 21
3.6 Password Change.................................................................................................... 21
3.7 WIFI Mode ............................................................................................................. 22
4. System Operation ........................................................................................................ 23
4.1 Function keys ......................................................................................................... 23
4.1.1 MENU key................................................................................................. 23
4.1.2 SILENCE key............................................................................................. 23
4.1.3 RESET Key ............................................................................................... 23
4.1.4 Enter Key ................................................................................................. 24
4.2 Normal Mode Operation ........................................................................................... 24
4.2.1 Fire Condition ........................................................................................... 24
4.2.2 Fault Condition.......................................................................................... 25
4.3 Factory Default...................................................................................... 25
4.4 Wi-Fi configuration ....................................................................................... 26

TSFC 24-2/4 User Manual
Vighnaharta Technologies Pvt. Ltd. Page 7of 26
1. Introduction
1.1 Overview
Fire can have an enormous impact on any institution or company, so to protect from these kinds of
incidences, this system can be helpful. This TrueSafe Fire alarm System (TSFC) is specially
designed for fire indications, early warnings facility. TSFC-24-2/4 is India’s first IoT (Internet
of Things) based Conventional Fire Alarm Panel. The TSFC-24-2/4 provides reliable fire
detection, signalling and protection for commercial, industrial and institutional buildings, small
offices etc.
The panel includes local buzzer, LEDs for indications and with LCD display, keypad for manual
operation and configuration and cloud connectivity through WiFi. It is compatible with almost all
makes of smoke detectors and heat detectors that can continuously monitor for trouble and fire
condition as well as send their status on Fire Cloud.
A user friendly Android Mobile application is available for Fire and Fault notification from the TSFC
panel.
1.2 System Features
•Operated on 24 V/1.2 Ah DC power supply with built-in charger.
•Battery low voltage 23 VDC and battery cut at 22 VDC.
•Stand by battery backup up to 8 hrs.
•16 x 2 alpha numeric LARGE LCD Display.
•LED indications for various modes on front panel.
•Local buzzer indication for fire, fault, and testing operation.
•6 Keys for configuration and program the system.
•Class B Initiating Device Circuits (IDCs) for smoke detectors & heat detectors, etc.
•Testing modes (Walk test)
•Zone bypass facility.
•NAC bypass facility.
•Three fixed PFC output for fire & fault
•Two level password protection for Admin and user.

TSFC 24-2/4 User Manual
Vighnaharta Technologies Pvt. Ltd. Page 8of 26
•Up to 15 scrolling events capacity
•Cloud Connectivity through WiFi
1.3 Technical Specifications
Power Supply
230V AC, 1.2A, 60/50 Hz. with 24 V Battery charger.
Input
Initiating Device Circuit (IDC)
•Voltage: 24 VDC
•End of Line: 4.7KΩ, 1 W
Indication
Front panel LED indications
•SYSTEM ON
•MAINS FAIL
•BATTERY FAULT
•NAC FAULT
•Siren SILENCE
•WiFi
•Zone Fault
•Walk Test Mode
•Zone Bypass
•Fire
•WALK TEST
16 x 2 Large LCD Display Indication
Zone fire status, fault status, configuration menus, Etc
Buzzer Indication
Fire, Fault, Walk Test Fire, Key press acknowledge
Output
NAC (Siren Output)
Voltage: 24 VDC, Current: 500mA
PFC Relay outputs: 3 (Two for Fire & one for Fault)
Dimensions
237 x 217 x 42 (LxHxW)
Operating
Temperature
00 C to +500C
Humidity
5 to 90% Rh
Weight
Approx. 3Kg
Enclosure
Metal Enclosure

TSFC 24-2/4 User Manual
Vighnaharta Technologies Pvt. Ltd. Page 9of 26
1.4 Controls and Indications
1.4.1 Controls
Key name
Password
protected?
Key function
MENU
OR
Num key ‘1’
Yes
•Enter main menu list
•Configures system as per requirements
•Use as a Esc
OR
•Enter numeric values ‘1’ during configuration
SILENCE
OR
Num key ‘2’
Yes
•Silence the NAC
OR
•Enter numeric values ‘2’ during configuration
ENTER
OR
Num key ‘3’
Yes
•Access the new menu.
•Saves configured data, mode or value of the
system.
OR
•Enter numeric values ‘3’ during configuration
‘<’
OR
Num Key ‘4’
Yes
•Scroll Left
OR
•Enter numeric values ‘4’ during configuration
RESET
OR
Num key ‘5’
Yes
•Reset the system
OR
•Enter numeric values ‘5’ during configuration
‘>’
OR
Num Key ‘0’
Yes
•Scroll Right
OR
•Enter numeric values ‘0’ during configuration
1.4.2 LED Indications
There are different LED indications given on front panel of TSFC panel to user to alert from different events
occurred. Name of events along with colour of corresponding LED with description are as follows.
No.
Indication
LED Colour
Description
1
System ON
Green
This indication shows system is Power ON
2
Mains Fail
Yellow
When Mains Fail Occurs, ON
3
Battery Fault
Yellow
When Battery is Low OR Battery missing, ON
4
NAC Fault
Yellow
NAC Fault has been occurred, ON
5
Silence
Yellow
System has been silenced, ON
6
WiFi
Blue
When Wi-Fi enabled, ON
7
NAC Fault
Yellow
NAC Fault has been occurred, ON
8
Twin Fire
Red
If any zone is in fire condition, ON

TSFC 24-2/4 User Manual
Vighnaharta Technologies Pvt. Ltd. Page 10 of 26
1.4.3 LCD Indication
The 16 x 2 Large LCD display is used in TSFC panel to display different system fault status, zone fire status,
configuration menus & so on. The LCD is mainly used Fire indications and for the programming of the panel listed
as below.
•Fire Indications
•Fault Indications
•Zone modes
•View history events
•Panel Configuration setting
•Change user / admin password
1.4.4 Buzzer Indication
A buzzer provides separate and distinct sounds for Fire, Faults and Walk Test Fire.
•Fire: Continuous Buzzer ON.
•Fault: 1 sec ON and 5 sec OFF.
•Walk Test Fire: 1 sec ON and 1 sec OFF.
1.5 Components
EOL Resistor:
•4.7K ohm 1 W Resistor is connected in parallel with each input zone for zone open/short/fire sensing purpose.
Hence 2 resistors are required for TSFC 24-2 & 4 resistors are require for TSFC24-4 model.
•4.7K ohm 1 W Resistor is connected in parallel with NAC output
9
Zone Fire
Red
If zone in fire condition, ON
10
Zone Fault/WT
Yellow
If zone in Fault/WT Mode, ON
11
Zone Bypass
Yellow
If zone disable, ON

TSFC 24-2/4 User Manual
Vighnaharta Technologies Pvt. Ltd. Page 11 of 26
2. Installation
2.1 Installation Precaution
WARNING:
Do not attempt to install, service, or operate this unit, until this manual is read and understood. Do not connect
other equipment to this unit.
CAUTION:
This system works at 0° C to +50° C and at a relative humidity of 90 ±2% RH.
However, the useful life of the system's standby batteries and the electronic
components may be adversely affected by extreme temperature ranges and
humidity.
2.2 Mounting Details
Backside of the panel
•Place the panel in its mounting position and fix the panel to the wall using the slots of the four screws.
•Ensure the enclosure and the inner parts of the panel are given sufficient protection during installation.
•Enter all external cables via preformed knockouts located at Top of the panel.
•When the installation of all the cables has been completed, clean the interior of the enclosure ensuring all
masonry debris and drilling swords are removed.
280mm
250mm
50mm
40mm
45mm
140mm

TSFC 24-2/4 User Manual
Vighnaharta Technologies Pvt. Ltd. Page 12 of 26
2.3 Panel Wiring
The following diagram shows basic components of Fire Panel System. It consists of various smoke and heat
detectors, AC power source, Notification devices like siren or sounder, etc
WARNING:
Several different sources of power can be connected to this panel. Disconnect all sources of power before
servicing. The panel and associated equipment may be damaged by removing and / or inserting cards, modules
or inter connecting while this unit is energized.
Primary Power source (AC) and Earth Ground Connection:
AC Power connections are made inside the control panel cabinet. A separate Earth Ground connection must be
made to ensure the proper panel operation and lightening and transient protection.
Standby Power Source (Batteries):
Use one 24V/1.2Ah sealed lead acid type Battery. Observe polarity when connecting the battery. Connect the
battery to the provided cable. The battery charger is current - limited and capable of recharging sealed lead acid
type batteries up to 8Ah.
Display
Keypad
Zone 1
Zone 4
Two/Four IDC
3 PFC Output
2 for Fire
1 for Fault
1 NAC
(Siren Output-500mA)
TSFC 24-2/4 Panel
WiFi
Connectivity
230VAC/50Hz
Supply With
Battery Backup

TSFC 24-2/4 User Manual
Vighnaharta Technologies Pvt. Ltd. Page 13 of 26
2.3.1 Field Wiring Diagram
The following diagram shows connector’s placement on Interface board.
2.3.3 Initiating Device Circuit (IDC)
•No. of Initiating circuit : 2/4 Zone
•Type : Class B
•Wire Size : 1.5sqmm armoured FRLS cable
•Operating Voltage : 24 VDC nominal max
•Connector : J3
•Total No. of Devices : Up to 20 smoke detectors per zone
•Monitoring Device : 4.7K Ohm, 1 W(EOL)
All zones may be configured for general fire alarm applications or supervisory alarm zones.

TSFC 24-2/4 User Manual
Vighnaharta Technologies Pvt. Ltd. Page 14 of 26
2.3.4 Output Circuits
The panel has three types of output circuits.
•Notification Appliance Circuit (NAC)
•Potential Free Contact Relay Outputs (PFC)
NAC
•No. of NAC : 1 circuits
•Type : Class B
•Output Voltage : 24V
•Current : 500 m A
•Terminals : J3
•Wire Size : 1.5sqmm armoured FRLS cable

TSFC 24-2/4 User Manual
Vighnaharta Technologies Pvt. Ltd. Page 15 of 26
Fixed Output (PFC)
Three PFC outputs:
1. Fire1 status output
2. Fire2 status output
3. Fault status output
Resettable 12VDC output
12VDC Resettable output for four wire detectors (24VDC/500mA)
2.4 Maintenance
2.4.1 Walk Test
It is maintenance purpose mode. When any zone is set as a Walk test that time Walk Test LED starts blinking
according to zone. This mode is used to test smoke detector and siren but RAC is not released.
Walk Test Procedure
•First particular zone is set as Walk Test.
•Then give smoke to the sensor.
•The sensor will detect smoke and the NAC will be ON and LCD will display show fire to the particular zone.
•The sensor will reset automatically and will come back to normal condition.
•In this way multiple sensors in a single loop can be tested.
Note: Repeat Walk test after every 3 months.
2.4.2 Servicing
Following are the servicing check list of FSS panel. Maintenance / servicing is required twice a year for each panel.
Sr.
No.
Check point or maintenance point
OK/Not
OK
Remark
1
Clean each smoke detector using soft cloth.
2
Check panel operation on battery backup mode (mains
OFF).

TSFC 24-2/4 User Manual
Vighnaharta Technologies Pvt. Ltd. Page 16 of 26
3
Check panel operation on mains supply (Battery
disconnected).
4
Check all connection of panel.
5
Perform WALK TEST mode of panel.
6
Check Smoke Detector.
7
Check siren output.
8
Check battery supply.
9
Check panel mounting screw.
Note: Please send above servicing report after every 6 months.
2.4.3 Periodic inspection and test of system
For additional information on control panel faults, regular checking of the functionality of the control panel and fire
detection system by a person responsible for fire prevention in the company must ensure the availability of the fire
detection system. Perform the Supervisory & Walk test regularly.
Weekly Testing By The User
▪Ensure that all indicators are showing correctly.
▪Check that the internal buzzer are operating correctly.
▪LCD Display shows messages from the system.
▪Each week, choose different manual check points so that the manual check points in the building
are tested in rotation over a prolonged period.
▪Check all detectors and ensure that none are obstructed in any way. Enter results of tests into the
log book.
Quarterly Test
Perform Walk Test / Supervisory Test to check the healthy condition of all zones. After every 3-4
months Walk test must be carried out.
Annual Test
Additionally, test all detectors, check points and check for correct operation.
Every 2 - 3 Years
Clean smoke detectors to ensure correct operation and freedom from false alarms. Special equipment
is required for cleaning smoke detectors.
Every 4 years
Replace sealed lead acid batteries. If the operating temperature exceeds 25o C continuously, then the
battery may need to be replaced sooner.

TSFC 24-2/4 User Manual
Vighnaharta Technologies Pvt. Ltd. Page 17 of 26
Pre Check list for call:
▪Check mains supply of system.
▪Check supply voltage of panel.
▪Check panel operation on battery backup mode.
▪Check all Indicators are showing results as per action are taking place in the Panel. Mainly check out for the
system ON indicator is glowing.
▪LCD display shows messages, buzzer operates.
▪Check all the cables are connected in proper manner.
▪Smoke detectors can detect the smoke.
▪Perform Walk test to ensure all zone are healthy.
2.5 Do’s and Don’ts
2.5.1 Do’s
1. DO take responsibility for your fire systems
Taking responsibility means being proactive and intentional about managing the programme and knowing what it
takes to maintain a high level of reliability your fire systems.
2. DO understand how your fire system works
Do you know the difference between the Trouble signal and the Supervisory signal in your Fire Alarm system?
What’s the correct response to these different signals? What button should you press? It’s important that you find
ways to learn how the system operates so that you are prepared to interact with the equipment in the case of an
emergency. I encourage you to make an effort to understand how your particular fire systems are designed to
operate.
3. DO know the inspection, testing and maintenance requirements
Testing must be performed on a periodic basis to verify the functionality of the fire system including simulating the
events and conditions that are to be expected during an emergency situation. One must also remember those
maintenance tasks are necessary to keep the system in good operating condition. These tasks include both
periodic preventative maintenance activities and making the required repairs revealed by the inspection or testing
of the system components like DSPA, siren.
4. DO train your people
Certain people must receive varying degrees of training depending upon their role. Some must understand how to
operate the system so they can interact with the system when something happens. Others must simply be ready
to react appropriately when an event happens. If you decide that more training is needed, don’t forget to turn to
your fire system service provider for help.
5. DO pay attention to record keeping
There are several different types of records that are important to maintain. Every Fire Alarm System should have
what is called a “Record of Completion” document that is maintained up-to-date with any and all system changes

TSFC 24-2/4 User Manual
Vighnaharta Technologies Pvt. Ltd. Page 18 of 26
made over the life of the system. Other important records include built drawings, user manuals, written sequence
of operation and servicing charts.
2.5.2 Don’ts
1. DON’T ignore reoccurring problems
Some fire systems are plagued by reoccurring trouble conditions that just don’t seem to go away on their own.
Common intermittent troubles include ground faults, circuit problems, battery faults and device failures. An
experienced fire system service technician can track down the root cause of the problem and know how to make
the necessary repairs. Resist the temptation to ignore these problems because of their sporadic nature. You may
have a bigger problem than you think and your system may be rendered ineffective because of it.
2. DON’T let building occupants become apathetic to fire alarms
May be you have noticed this, but most people hesitate to respond when they hear the fire alarm evacuation
signals in a building. Unfortunately, most of us have experienced more than one “false alarm” from a fire system
in our lifetime and this has led many to be apathetic about evacuating. Facility Managers must do what they can to
avoid false alarms, but when they do happen take steps to make whatever changes are necessary to prevent them
in the future. When possible, inform occupants about the source of each false alarm in hopes of maintaining their
future confidence in the system.
3. DON’T cause an accidental discharge
Many facilities may have one or more spaces protected by an automatic fire extinguishing system. Unfortunately,
too many system owners have had to deal with an accidental discharge of a system. Facility Managers must take
steps to avoid this at all costs. Without question, the most common reason for a false discharge is human error.
It’s important to put in place and enforce procedures and policies that will minimize the chance for this sort of
error. The single biggest contributor to the prevention of accidental discharges is training the personnel who work
in and around these spaces.
4. DON’T allow unqualified personnel to service your fire system
Facilities Managers must ensure those who are performing these tasks are trained on the equipment they are
servicing. The person working on FSS unit, must have through knowledge of Fire Sprinkler, Fire Alarm and Special
Hazard Fire Suppression. Facility Managers must not hesitate to ask not only the service provider, but also the
specific technician about their level of experience in the type of work they are performing. The reliability of your
life safety and business continuity depends upon this person.
5. DON’T forget to consider the fire system when your facility changes
One thing is for certain, your building will eventually change and each time it does the Facility Manager must not
forget to evaluate the impact those changes will have on the fire systems protecting the building. Other types of
fire systems and components will no doubt be impacted including detector placement, notification appliance
location, sprinkler coverage and obstructions to manual pull stations. When you realize your building will be
undergoing a change, begin planning up-front for the necessary changes to the fire systems.

TSFC 24-2/4 User Manual
Vighnaharta Technologies Pvt. Ltd. Page 19 of 26
3. System Programming
The fire panel system is completely programmable at site with the help of panel keypad and LCD. It does not
require software skills OR any special software for Programming.
When panel is in normal state, the screen displays as below. Normal state means all zone of panel are in Enable
and panel is in fault free condiation.
TrueSafe
SYSTEM OK
To enter the programming mode, panel must be in normal condition as above. If any fault or alarm condition
exists, make sure that it is cleared and panel returns to normal condition. Users having Key lock passwords.
Without key lock password user cannot enter in MENU function. Factory default panel do not have any password if
user will enable “Auto Key Lock” function only that time panel will ask password. (Factory default password is
“1111”)
To enter into Programming mode do following steps,
1. Press MENU key, it will ask for password (If “Auto Key Lock” function is enable system will ask password)
2. Enter FOUR digit numeric password.
3. After entering the password user can access all MENU functions
4. If password is correct, the LCD displays will show below screen,
Password Invalid
****
3.1 Menu Options
There are total 9 programming menu options as listed below.
❖Use and keys to show the next menu options.
❖Press ENTER key to entering sub menu OR
“enable/disable” function
❖Press key to return to previous menu OR Exit menu
ZONE1 Configuration
ZONE2 Configuration
ZONE3 Configuration
ZONE4 Configuration
NAC Mode
NAC Auto Silence
Auto Key Lock
Password Configuration
WiFi Configuration

TSFC 24-2/4 User Manual
Vighnaharta Technologies Pvt. Ltd. Page 20 of 26
3.1 Zone1
After entering in the Zone 1 menu, LCD displays as shown below.
Use LEFT and RIGHT keys to sub menu of ZONE 1 configuration. After changing the modes,
press ENTER key to save the changes.
Each zone can be configured for any one of the THREE modes namely,
1. ENABLE: This is default mode in which system scans the input signal from smoke detectors, heat
detectors, etc. If fire is detected, then system indicates alarm condition. If any zone is detected as open /
short, system indicates fault condition.
2. Walk Test: This mode is used for system walk test. Before walk test, the zone must be configured as
Walk Test mode. If fire alarm condition occurs, then the system indicates as a WT fire alarm. If any zone
is open / short, then system indicates WT OPEN/WT SHORT. (WT means Walk Test)
3. Disabled: This mode is used to disable the zone. The system does not scan the input signal from smoke
detectors, heat detectors, etc.
3.2 Zone 2
After entering in the Zone 2 menu, LCD displays as shown below.
Use LEFT and RIGHT keys to sub menu of ZONE 2 configuration. After changing the mode,
press ENTER key to save the changes.
Each zone can be configured for any one of the THREE modes namely,
1. ENABLE: This is default mode in which system scans the input signal from smoke detectors, heat
detectors, etc. If fire is detected, then system indicates alarm condition. If any zone is detected as open /
short, system indicates fault condition.
2. Walk Test: This mode is used for system walk test. Before walk test, the zone must be configured as
Walk Test mode. If fire alarm condition occurs, then the system indicates as a WT fire alarm. If any zone
is open / short, then system indicates WT OPEN/WT SHORT. (WT means Walk Test).
This mode is use for testing IDC zones. Walk test fire is show as a “WT Fire”.
ZONE 1
< ENABLE >
ZONE 2
< ENABLE >
This manual suits for next models
1
Table of contents
Other Vighnaharta Fire Alarm manuals
Popular Fire Alarm manuals by other brands

Tecnoalarm
Tecnoalarm Tecnofire TFA2-596 Installation

Silent Call Communications
Silent Call Communications FA41-MC Installation and operating instructions

Firehawk
Firehawk FHB10-RF Pairing guide

E2S
E2S STExJ2 instruction manual

Honeywell
Honeywell ESSER 761694 Installation instructions manual

Vigilant
Vigilant MX1 installation guide