Instruction Manual
ShenZhen Asenware Test and Control Technology Co.,Ltd.
Address: 701,Bd 8, Dongfangming Industry Zone,
Dabao Rd.,Baoan,Shenzhen,China-518101
Tel: 27663815
Fax:27663815
Postal Code:518000

Page 2 Of 8
N
o
t
i
c
e
Thank you for using the product from ShenZhen Asenware Test.Ltd.. Make sure to read this
operating guide carefully before installing,operating or maintaining the device.
This manual describes the use of scope, installation and operation of IR3 series flame
detectors in detail. Also it contains the related notes for using the flame detector safety. Before
designing, installing, using, operating and maintaining the flame detector, make sure that you have
read and understood the content of the manual clearly, which prevents the quality of product from
damaging or hurts the person.
Special Caution and Notice:
The installation process and operation must comply with the relevant national
standards.
Any operation on the interior detector must be implemented by trainedpersonnel.
I
n
f
o
r
m
a
t
i
o
n
The following types of notices are used throughout this Operating Manual:
Warning: Identifies a hazardous or unsafe practice which could result in severe injury or
death to personnel.
Caution: Identifies a hazardous or unsafe practice which could result in minor injury to
personnel, or product or property damage.
Note: Identifies useful/additional information.
Copyright
All rights reserved by Shanghai Anysafe Technologies Corporation. Any part of this
publication may be reproduced, translated, stored in a database or retrieval system or transmitted
in any form, be it electronically, or by any other means such as photocopying, recording or
otherwise, without the prior written permission.
For any information is not mentioned in this document or any content that need to be added
or corrected, please contact us.
In the principal of devoting to progress and innovation, Shanghai Anysafe Technologies
Corporation has always been improving product performance. We would greatly appreciate being
informed of any errors or omissions that may be found in the content of this document.

Page 3 Of 8
Contents
1.
S
u
mm
a
r
y
.......................................................................................................................
4
2.
M
a
i
n
F
ea
t
u
r
e
s
...........................................................................................................
4
3.
T
e
c
hn
i
c
a
l
p
a
r
a
m
e
t
e
r
s
...............................................................................................
5
4.
S
t
r
u
c
t
u
r
e
a
nd
i
n
s
t
a
ll
a
t
i
on
.....................................................................................
5
5.
W
i
r
i
n
g
.........................................................................................................................
7
6.
P
a
c
k
age
,
t
r
a
n
s
po
r
t
a
nd
s
t
o
r
age
...........................................................................
7
7.
Test...................................................................................................................7
8.
M
a
i
n
t
a
i
n
i
n
g
................................................................................................................
8
9.
App
e
nd
i
x
.....................................................................................................................
8

Page 4 Of 8
1.
Su
mm
a
r
y
AW-FD704E-IR3
IR3 series
IR3 Series flame detectors (short-called the flame detector as follows) provide a new generation of
fire detection capability and technical standards.The flame detectors which adopt a specially
designed pieces of narrow-band infrared sensors and Blind type solar daylight UV sensors can
distinguish the real flame radiation and interference sources effectively and reduce the impact of
environmental factors on detector extremely by means of the built-in 16-bit microprocessor and
proprietary signal algorithm processing .The detector can set 5 different Sensitivity levels in order
to meet more needs in different location.We collected a large number of experimental data through
market research and customers’ feedback. We have made a big improvement based on its existing
in the hardware circuitry and software algorithms .
IR3 Series flame detectors contain the following two kinds:
IR3/IR3 three-wavelength infrared flamedetector
IR3/UVIR3double infrared and single ultraviolet flame detector
2.
M
a
i
n
Fe
a
t
u
r
e
s
Built-in16-bit high-speed, low-power, high-performance, high-precision data processing chip.
Adopt narrow-band infrared sensors and patented solar-blind UV sensor.
It has multi-level sensitivity in order to meet more occasions. Also they can detect flammule
earlier.
Detection angle can be able to reach to 110 Degree/IR2.
Detection range can be able to reach to 50m/IR3.
The perfect algorithm combines optimally the flame detection and false alarm capabilities.

Page 5 Of 8
Detector is fit to a variety of fuels.
Apply to heavy industry applications.
Explosion-proof designs can be used in hazardous area of industrial sites.
Low maintenance cost, easy to update and improve.
3.
T
e
c
h
n
i
c
a
l
p
a
r
a
m
e
t
e
r
s
Operating voltage: DC24V (range DC18V~30V)
Operating Current: Monitor≤25mA , Alarm≤35mA(relay)
Angle
range
:
110
°
Sensitivity level:1~3 level adjusted
Detection range ≤50m
Output:
Delay, Alarm relay, normally open contact output, 1A@30VDC.
Operating
Temperature:
-10
°
C
~
55
°
C.
Operating Humidity: 0~95%RH.
Storage
temperature:
-40
°
C
~
85
°
C.
Explosion proof level: Exd IIC T6(Explosion proof)
Protection level:IP66.
Weight:1KG.
Housing material: Aluminium alloy, painted surfaces.
4.
S
t
r
u
c
t
u
r
e
a
nd
i
n
s
t
a
ll
a
t
i
o
n
Caution: Before installing detector, please cut off the power supply ofit.
Notice: All wiring must comply with relevant standards andregulations.
Notice: Detectors are installed in Explosion proof areas, the wiring of detector should be
connected by power limit and be controlled. The setting of flame detector is subject to 《automatic
fire alarm design standards 》(GB50116-98) 。
Check whether the external cable is open circuit, short circuit fault or not.
Install the detector according to the drawing as follows, adjust appropriately the detector
view angle in terms of the scope of protection.
Notice: All connections adopt more than 1.0 square wire, the end of connections cut about
6mm Isolation jacket, then connect to the terminal blocks of IR3 series flame detectors.
Warning: expose lead wire too much or too less may cause wrong connection.

Page 6 Of 8
The shape of detector(UV/IR3 as follow:
Installation as follows:
Wall surface mounting Flip down mounting

Page 7 Of 8
5.
W
i
r
i
n
g
+24V/GND: DC 24V supply;
+24V/GDN/MA:Three wire 4mA-20mA current loop signal output;
FRJD/FRJK: Normally opened contact output of the alarm relay ;
FLJD/FLJB: Normally closed contact output of the fault relay ;
6.
P
a
c
k
ag
e
,
t
r
a
n
s
p
o
r
t
a
nd
s
t
o
r
ag
e
The flame detector packages with carton in whose interior fills with damping foam. Flame
detectors can be transported by rail, road or air transport, but should pay attention to handling,
prohibit using the handling tools to hit the upper surface of the box, in order to avoid damaging to
the panel of device.
7.
Test
Before testing, announce the related management department that fire detector system is
testing that need to cut off the maintenance area or the systemic logic control functions in order to
avoid unnecessary alarm linkage. The flame detector must be tested after installation and
maintenance each time.
Detector executes initializing setting after powering on, the green lamp is always on, then
ends after 30 seconds. Normal operation, the number of flashes from green light represents the
current sensitivity level.
Before testing, examine whether the LED flashes or not, if not flash, the detector is not
powered on (check the connections), or damaged (return to repair).
Field test tool is alcohol lamp or flame simulator. Simulate fire situation until the detector
alarms. After the test, announce the related management department that the system returns to
normal. If the detector can’t pass these tests, you should be returned to repair.
Note: The flame detector does not have any internal parts which user can debug. Replacing
any components or adjusting circuits are likely to damage the performance of the device without
the manufacturer’s agreement.

Page 8 Of 8
8.
M
a
i
n
t
a
i
n
i
n
g
Important matters: Flame detector must be regular testing and maintenance in accordance
with the national standards and the related regulations. Each detector must be cleaned at least once
a year and be tested and maintained each month.
Before cleaning, announce the related management department that the system of
flame detector will stop working temporarily for maintenance.
Cut off the area which will be maintained or the systemic logic control functions in order to
avoid unnecessary alarm linkage.
Clean dust and impurities on the front of the detector by vacuum suction or compressed air.
If the lens has dirt, use the alcoholic cotton to wipe the lens, prohibit scratching the lens by
hard object.
Follow the above procedure to test the detector after the cleaning of the detectors.
9.
A
pp
e
nd
i
x
IR3 Series flame detectors insidethe package one;
Instruction one;
Packing list one;
Accessories a pocket.
Table of contents
Other ASENWARE Security Sensor manuals