Simons Voss Technologies 3061 VdS User manual

Digital Locking Cylinder 3061 VdS
State of: June 2006

Digital Locking Cylinder 3061 VdS
Page 2
1.0 Method of Operation __________________________________3
1.1 General Information ______________________________________ 3
1.2 Opening and Locking From Outside_________________________ 3
1.3 Opening and Locking From Inside __________________________ 3
2.0 Special Models _______________________________________4
2.1 FH Version______________________________________________ 4
2.2 Overview _______________________________________________ 4
3.0 Additional Functions __________________________________4
3.1 OMRON ________________________________________________ 4
3.2 Extending the Coupling Time ______________________________ 4
3.3 Logging Unauthorized Access Attempts _____________________ 5
3.4 No Acoustic Programmer Acknowledge _____________________ 5
4.0 Battery Warnings _____________________________________5
4.1 Locking Cylinder_________________________________________ 5
4.2 Transponder ____________________________________________ 6
5.0 Battery Replacement __________________________________6
6.0 Installation Instructions________________________________7
6.1 General Information ______________________________________ 7
6.2 Programming the Locking Cylinder _________________________ 7
6.3 Removing the Outer Knob _________________________________ 7
6.4 Inserting the Digital Cylinder Into the Lock ___________________ 8
6.5 Screw On the Outer Knob _________________________________ 8
6.6 Perform Function Test ____________________________________ 8
7.0 Potential Applications _________________________________8
7.1 General Information ______________________________________ 8
7.2 Fire Protection Doors _____________________________________ 8
7.3 SLP Locks ______________________________________________ 8
8.0 Data Sheet___________________________________________9

Digital Locking Cylinder 3061 VdS
Page 3
Drilling protection
1.0 Method of Operation
1.1 General Information
The Digital Locking Cylinder 3061 VdS meets the requirements of VdS (Association
of German Property Insurers) Class B and its outer dimensions exactly match those
of a standard mechanical cylinder. In comparison to mechanical systems, it excels
because it is very easy to install, provides greater security, is more flexible and costs
less to operate. It can quickly and easily replace existing mechanical cylinders in "old
systems".
Inner knob
Outer knob
1.2 Opening and Locking From Outside
When not activated, the outer knob turns freely. It is not possible to open the door or
to lock it. Hold the transponder at a distance of approximately 10 to 40 cm (4 to 16
inches) from the digital locking cylinder and briefly press the transponder button once.
If this is an authorised transponder, a double signal tone sounds and the cylinder
couples. Now turn the outer knob in the locking or opening direction. You have ap-
proximately five seconds for this process. You can use the software to adjust the
coupling time. The longer the coupling time, however, the shorter the service life of
the battery. Then a single signal tone sounds and the outer knob turns freely again.
Make sure that the outer knob of the locking cylinder turns freely again after the cou-
pling process.
& If this transponder is not authorised at this time because of the time zone plan,
a single signal tone sounds. The cylinder does not couple, however, and you
cannot open the door.
1.3 Opening and Locking From Inside
It is always possible to open doors with Digital Locking Cylinder 3061 VdS devices
from the inside without operating the transponder

Digital Locking Cylinder 3061 VdS
Page 4
2.0 Special Models
The standard Digital Locking Cylinder 3061 VdS is equipped as a PLUS version,
which means that the following functions are always included:
Access logging The locking cylinder stores the last 128 accesses with date, time
and the user name of the transponder. You can read out the
data with the PalmCD2 or over the network.
Time zone control You can program locking cylinders in such a way that authorised
transponders are authorised for access only at certain times.
The Digital Locking Cylinder 3061 VdS is also available in the following optional
versions:
2.1 FH Version
For doors with thick metal inserts (such as fire protection doors) or with a large
screening effect. This version is also used in areas with strong interference fields,
such as in server rooms.
2.2 Overview
Locking Cylinder (PLUS) Locking Cylinder FH (PLUS)
¾ Entrance doors ¾ Fire protection doors
¾ Residential doors ¾ Aluminium doors
¾ Office doors
¾ Interconnecting doors
3.0 Additional Functions
You can activate the following functions with the software settings:
3.1 OMRON
All product versions can be operated in OMRON mode. You will find a detailed
description in the Smart Relay manual.
3.2 Extending the Coupling Time
The default time for the coupling of the cylinder is approximately 5 seconds. You can
use the software to extend this time to approximately 10 seconds. This shortens the
lifetime of the battery, however.

Digital Locking Cylinder 3061 VdS
Page 5
3.3 Logging Unauthorised Access Attempts
For cylinder version 10.2 and later and in combination with the LDG Version 1.40, it is
possible to log unauthorised access attempts, as well as authorised accesses. This
includes both access attempts without authorisation and access attempts outside the
specified time zone. In this connection, however, only transponders from the locking
system are logged, which means that the transponder must have the same locking
system ID (SID).
3.4 No Acoustic Programmer Acknowledge
When programming over the network, it can be advantageous to deactivate the
acoustic programmer acknowledge. You can do that with this function.
4.0 Battery Warnings
4.1 Locking Cylinder
Warning level 1 for main battery
If the main battery of the locking cylinder goes empty, eight short signal tones, coming
quickly one after another, sound after you operate the transponder and before the
cylinder couples. You must replace both batteries now.
Warning level 2 for backup battery (SW Version 10.0 & SW Version 10.1)
In addition to the main battery warning, an additional eight short signal tones, coming
quickly one after another, now sound for the backup battery warning. The cylinder
does not couple until after the signals. From now on, the backup battery is active. You
must replace both batteries as soon as possible.
Warning level 2 for backup battery (SW Version 10.2 and later)
Now the signal tones of the backup battery warning sound for only approximately 30
seconds (without the main battery warning). The cylinder does not couple until after
the signals. From now on, the backup battery is active. You must replace both bat-
teries as soon as possible.
Warning level 3 (SW Version 10.2 and later)
If you continue to ignore this backup battery warning, either the door can be used 50
more times or the cylinder switches off after 4-5 weeks if there is no further operation.
In both cases, the cylinder switches into the so-called storage mode. After this, you
can only open the cylinder with the programming device.

Digital Locking Cylinder 3061 VdS
Page 6
4.2 Transponder
If the transponder battery voltage is coming to an end, eight short signal tones,
coming quickly one after another, sound each time the transponder is operated on the
locking cylinder after the uncoupling.
& Attention: Do not take out the transponder battery because this will probably
result in the loss of data. See the “Transponder 3064” manual for more
information.
5.0 Battery Replacement
Only authorised personnel are permitted to replace the battery. Use only batteries
that are supplied by SimonsVoss.
Fig. 1 Fig.2 Fig.3
Use the special tool to loosen the locknut (Fig. 1) on the inner knob (long knob) ap-
proximately one rotation (only loosen slightly, do not unscrew completely). Carefully
push the inner knob back and forth so that the sealing cone loosens and then un-
screw the inner knob completely (Fig. 2).
Note: Only push the inner knob to the side very lightly because otherwise you may
damage the electronics.
&When changing batteries, always change both batteries.
Insert the main battery into the holding device with the positive pole toward the door
and the backup battery in the opposite direction (Fig. 3).
& Reversing the polarity can result in damage to the locking cylinder. Incorrect
handling of the batteries used in this device can result in the risk of fire or
burns. Do not charge, open, heat to more than 100 C (212 C) or burn. Replace
the batteries only with original batteries supplied by SimonsVoss.
& Please dispose of lithium batteries immediately when discharged. Store away
from children, do not open and do not throw into fire.
& Never operate the cylinder without a main battery because otherwise the en-
tire power consumption of the cylinder runs over the backup battery.

Digital Locking Cylinder 3061 VdS
Page 7
Fix the lock nut in position with the special tool and press it against the flange. Now
turn the inner knob onto the screw thread until the stop and tighten the locknut firmly.
Now operate an authorised transponder and test the function.
& Please dispose of discharged lithium batteries immediately. Store away from
children, do not open and do not throw into fire.
& You must reset the time of day after the battery change because the clock
does not work without current (Software Operating Instructions: Programming
Æ Setting the Clock on the Locking).
6.0 Installation Instructions
6.1 General Information
When installing the Digital Locking Cylinder, make sure that there are no sources of
interference in the vicinity. You should install locking cylinders at least 0.5 m
(approximately 1.5 feet) from one another and control units or SmartRelays at a dis-
tance of at least 1.5 m (approximately 5 feet). The PC housing of the half cylinder is
not allowed to stick out into the exterior area more than 3 mm. If necessary, attach a
profile cylinder rosette. Furthermore, you must ensure that no water can penetrate the
cylinder in the area of the catch
6.2 Programming the Locking Cylinder
You must program the Digital Locking Cylinder and accompanying transponders in
the locking plan before you install them. Please refer to the Software Operating
Instructions for more detailed information.
& The locking cylinders are delivered in so-called storage mode, which means
that no communication is possible with the transponder (exception: program-
ming transponder). You can also use software and the programming device to
remove the storage mode. Please refer to the Software Operating Instructions
for more detailed information.
6.3 Removing the Outer Knob
Loosen the setscrew on the outer knob (short knob) with a
1.5 mm Allan key (do not screw the whole way off). Operate an
authorised transponder and hold the inner knob still. The
locking cylinder couples and you can unscrew the outer knob
by turning it counterclockwise.

Digital Locking Cylinder 3061 VdS
Page 8
6.4 Inserting the Digital Cylinder Into the Lock
First turn the lock pin until it is pointing straight down. Then insert the Digital Locking
Cylinder through the lock so that the inner knob (long knob) points toward the inside
of the door. Fasten the cylinder with the lock screw included in the delivery
Never hit against the knobs during installation. Do not bring the cylinder into contact
with oil, paint or acid.
6.5 Screw On the Outer Knob
Screw the outer knob on the screw thread, fixing it in position with your fingers if nec-
essary. Then operate the transponder. Hold the inner knob still and tighten the outer
knob solidly. Finally, tightly screw the setscrew with the Allan key.
6.6 Perform Function Test
1. With the door open, turn the inner knob in the locking and opening directions.
The knob must turn easily.
2. Close the door and repeat the process. If the locking cylinder is stiff, you must
align the door or correct the edge plate.
3. Then perform the same test on the outer knob. To do this, operate an author-
ised transponder near the cylinder.
7.0 Potential Applications
7.1 General Information
The Digital Locking Cylinder fits locks for Euro Profile Cylinders that meet DIN 18254
specifications.
7.2 Fire Protection Doors
It is possible to install the locking cylinder in fire protection doors. In this case, use the
Locking Cylinder Version FH. The approval for a fire protection door is always unaf-
fected by the locking cylinder.
7.3 SLP Locks
The Digital Locking Cylinder 3061 FD is used for applications of this type. The Digital
Locking Cylinder 3061 VdS does not have approval for SLP doors at this time. See
the “Digital Locking Cylinder 3061” manual Æ “Possible Applications.

Digital Locking Cylinder 3061 VdS
Page 9
8.0 Data Sheet
Knobs Material Stainless steel
Colours Brushed stainless steel
Brass
Diameter 30 mm
FH cylinder knobs Material Outer knob stainless steel, inner knob
plastic
Colour Black
Diameter 30 mm
Profile cylinders Standard length Outside 30 mm, inside 30 mm
Construction length In 5 mm increments (no kit) up to a total
length of 140 mm, where one side of
the cylinder can have a max. length of
90 mm. Other lengths upon request.
Battery Type
Service life
Lithium 3.6 V, 1/2 AA
Lithium 3 V, CR1220
Use only original replacement batteries
from SimonsVoss
Approx. 60,000 operations
or approx. 4 years
Environmental
Conditions
Operating
temperature
Storage temperature
Degree of protection
-20°C to +50°C (-4° F to +122° F)
-35°C to +50°C (-31°F to +122°F)
IP54 (when installed)
Table of contents
Popular Security Sensor manuals by other brands

GJD
GJD Dual Tech GJD360 installation manual

PCB Piezotronics
PCB Piezotronics ICP 113A22 Installation and operating manual

IFM Electronic
IFM Electronic efector300 SI0104 operating instructions

Milwaukee
Milwaukee 48-35-1211 Operator's manual

Visonic
Visonic NEXT PG2 - datasheet

Hugo Müller
Hugo Müller TS 31.10 knx instruction manual