Installation and Maintenance Instructions for
V02 Monoflange
© Ashcroft Inc. 2020, 250 East Main Street, Stratford, CT 06614-5145, USA, Tel: 203-378-8281, Fax: 203-385-0357, www.ashcroft.com
All sales subject to standard terms and conditions of sale. v02_monoflange_i&m_ (I&M008-10282)_RevA_09-24-20
of 22
Instrument-Monoflanges: All valves are needle valve type.
Process-and Instrument-Monoflanges are available in three
different types BLOCK, BLOCK & BLEED and DOUBLE
BLOCK & BLEED.
2 TRANSPORTATION AND STORAGE
The monoflange must be depressurized before removal from
system and before storage or transportation. It should be
stored in its original packaging to avoid contamination or
damage. Upon receipt, anti-tamper keys are unattached to the
valve head unit.
3 ASSEMBLY
3.1 Installation requirements
The following installation conditions apply to the monoflanges:
Monoflanges are to be installed in such a way that employees
or third parties are not endangered.
The safety distances required by the relevant national statutory
provisions applicable in the country
of installation are to be observed.
Monoflanges must be installed or mounted in such a way:
- they are accessible for any necessary inspection and are
clearly visible;
- the labeling is clearly legible;
- operation of the monoflanges is possible from a safe
distance.
Monoflange must be protected from outside mechanical
influences to protect it from damage. Monoflange must be
protected from tampering by unauthorized persons.
3.2 Connecting the monoflange
Monoflanges must be connected via the inlets and outlets
provided. Additional introduction of forces or bending
moments applied to the connection pieces via piping
connections can damage the assembly and connection fittings
and must be avoided. Both form and cleanliness of threads
must be checked before assembly. Piping or fitting
connections must be made up tight. A thread tape or sealant
should be used for threaded pipe joints.
Weld seams on connections must be welded and tested
in compliance with valid approved welding methods. Steel
welded connections must be painted after welding in order to
avoid corrosion. Mating flanges should be checked to ensure
correct size and rating for flanged connection. Flanges should
be assembled using correct gasket or seal ring and bolted as
specified in ASME B16.5.
4 PRIOR TO OPERATION
Commissioning should not be carried out until the monoflanges
- have been correctly installed in the system and
- have been checked for correct assembly, installation
conditions and safe function.
The test before commissioning is provided by the system
operator to arrange. In the list countries
applicable national regulations are to be observed.
5 OPERATION
5.1 General information
Monoflanges with OS&Y Needle Valve and Needle
Valve are used to shut off media that can be
poisonous, explosive, irritating, very hot or very
cold. Any assembly and maintenance work must be
carried out by experienced and trained personal.
The generally valid regulations on health and safety as well
as accident prevention must be observed in addition to this
operating manual and the operating instructions for the system
and measuring instruments that are used.
For example oxygen operation.
The valve must only be operated by competent and authorized
personal.
5.2 Operating conditions
Refer to the monoflange drawing for the permissible operating
conditions.
5.3 Operation
Valves on the monoflange are actuated with
T-handle or socket wrench. Valves are closed
clockwise. The closing torque is approximately
3 Nm (2.2 foot-pounds).
Valves are fitted with a metal back seal between the
needle and the bonnet. This means that the valve head units
must always be completely open. This back seal is pressure-
supported. The higher the system pressure, the greater the
force with which the needle is pressed into the back seat.
Do not apply any increased closing torque when the needle is
in the back seat position. This is unnecessary and could cause
damage to the stem-needle connection.