Assa Abloy Orion User manual

1
ASSA ABLOY Hospitality 66 8003 015-3
User Manual
Orion High Voltage Thermostat
DRAFT

2
ASSA ABLOY Hospitality 66 8003 015-3
Copyrights
The information in this document is subject to change at the sole discretion of
ASSA ABLOY without notice.
Any use, operation or repair in contravention of this document is at your own risk.
ASSA ABLOY does not assume any responsibility for incidental or consequential
damages arising from the use of this manual.
All information and drawings in this document are the property of ASSA ABLOY.
Unauthorized use and reproduction is prohibited.
VingCard and Elsafe are registered trademarks of ASSA ABLOY.

3
ASSA ABLOY Hospitality 66 8003 015-3
Table of contents
.................................................................................................5
FCC and ISED (IC) statements
........................................................................................................................ 5FCC statements
........................................................................................................................ 6ISED (IC) statements
................................................................................................................................................ 6
End product labeling
.................................................................................................7
1. Introduction
........................................................................................................................ 81.1 Orion EMS devices
........................................................................................................................ 91.2 Terminology
........................................................................................................................ 111.3 General about Orion Service
........................................................................................................................ 111.4 General about alarms
........................................................................................................................ 121.5 Events and commands
................................................................................................................................................ 13
1.5.1 Thermostat event report
........................................................................................................................ 141.6 Basic EMS logic
................................................................................................................................................ 14
1.6.1 Room occupied
................................................................................................................................................ 14
1.6.2 Room unoccupied
....................................................................................................................................... 15
1.6.2.1 Door open in 'room unoccupied' mode
................................................................................................................................................ 15
1.6.3 Room unsold
....................................................................................................................................... 15
1.6.3.1 Door open in 'room unsold' mode
................................................................................................................................................ 16
1.6.4 Staff entry
....................................................................................................................................... 16
1.6.4.1 Door monitored by RF door switch
....................................................................................................................................... 16
1.6.4.2 Door monitored by electronic lock
................................................................................................................................................ 16
1.6.5 Operating states
....................................................................................................................................... 16
1.6.5.1 One interior door
....................................................................................................................................... 17
1.6.5.2 One exterior door
....................................................................................................................................... 17
1.6.5.3 One exterior and one interior door
................................................................................................................................................ 18
1.6.6 Thermostat control chart
........................................................................................................................ 191.7 Orion EMS parameters
........................................................................................................................ 231.8 Operator templates
................................................................................................................................................ 24
1.8.1 Operator template X-reference
........................................................................................................................ 251.9 Setback override
.................................................................................................27
2. Thermostat buttons and display
........................................................................................................................ 272.1 Thermostat buttons
........................................................................................................................ 282.2 Thermostat display
.................................................................................................29
3. Energy management summary
and alarm list
........................................................................................................................ 293.1 Energy management summary
........................................................................................................................ 313.2 Alarm list
.................................................................................................31
4. Real time room status
.................................................................................................32
5. Thermostats list

4
ASSA ABLOY Hospitality 66 8003 015-3
.................................................................................................37
6. Occupancy report
.................................................................................................38
7. Energy statistics report
.................................................................................................39
8. Tools/Options
........................................................................................................................ 398.1 General
........................................................................................................................ 408.2 Maintenance
........................................................................................................................ 418.3 Housekeeping
.................................................................................................42
9. Orion EMS in SysMon
........................................................................................................................ 439.1 Thermostats
........................................................................................................................ 449.2 Online commands
........................................................................................................................ 459.3 Broadcasts
........................................................................................................................ 469.4 Room events
.................................................................................................47
10. Maintenance
........................................................................................................................ 4710.1 To disassemble a thermostat
........................................................................................................................ 4810.2 To replace a fuse
.................................................................................................49
Appendix A: Quick reference of
technical data
.................................................................................................51
Appendix B: Troubleshooting
........................................................................................................................ 51A/C unit not blowing hot/cold air
........................................................................................................................ 51Fan speed not working
........................................................................................................................ 52Thermostat has no power
........................................................................................................................ 52Room is not going into Occupied state
........................................................................................................................ 53A/C unit cooling when calling for heat (and vice versa)
........................................................................................................................ 53Fan continues to run even when the thermostat is turned off
.................................................................................................54
Appendix C: Read more
.................................................................................................54
Revision history

5
ASSA ABLOY Hospitality 66 8003 015-3
FCC and ISED (IC) statements
FCC (Federal Communications Commission) statements
These devices comply with Part 15 of the FCC Rules. Operation is subject to the following
two conditions:
(1) these devices may not cause harmful interference, and
(2) these devices must accept any interference received, including interference that may
cause undesired operation.
Important note: To maintain compliance with FCC´s RF exposure guidelines, this equipment
should be installed and operated with minimum distance 20 cm between the radiator and your
body. Use only the supplied antenna.
This equipment complies with FCC radiation exposure limits set forth for an uncontrolled environment.
These transmitters must not be co-located or operating in conjunction with any other antennas
or transmitters.
Changes or modifications not expressly approved by the party responsible for compliance could
void the user's authority to operate the equipment.
Note: This equipment has been tested and found to comply with the limits for a Class B digital
device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable
protection against harmful interference in a residential installation. This equipment generates,
uses and can radiate radio frequency energy and, if not installed and used in accordance with
the instructions, may cause harmful interference to radio communications. However, there is
no guarantee that interference will not occur in a particular installation. If this equipment does
cause harmful interference to radio or television reception, which can be determined by turning
the equipment off and on, the user is encouraged to try to correct the interference by one or
more of the following measures:
- Reorient or relocate the receiving antenna.
- Increase the separation between the equipment and receiver.
- Connect the equipment into an outlet on a circuit different from that to which the
receiver is connected.
- Consult the dealer or an experienced radio/TV technician for help.
The concerned end product must be labeled to say 'Contains FCC ID: Y7V-683081118C1'.
The concerned end product must be labeled to say 'FCC ID: Y7V-TZENHV'.

6
ASSA ABLOY Hospitality 66 8003 015-3
ISED (IC) statements
These devices comply with Industry Canada licence-exempt RSS standard CAN ICES-3 (B)/NMB-3(B) B.
Operation is subject to the following two conditions:
(1) these devices may not cause interference, and
(2) these devices must accept any interference, including interference that may cause undesired
operation of the devices.
Les présents appareils sont conformes aux CNR d’Industrie Canada applicables aux appareils radio
exempts de licence. L’exploitation est autorisée aux deux conditions suivantes:
(1) les appareils ne doivent pas produire de brouillage, et
(2) l’utilisateur des appareils doit accepter tout brouillage radioélectrique subi,
même si le brouillage est susceptible d’en compromettre le fonctionnement.
Important note: To comply with Industry Canada RF radiation exposure limits for general population,
the antennas used for these transmitters must be installed such that a minimum separation distance
of 20 cm is maintained between the radiator (antenna) and all persons at all times and must not be
co-located or operating in conjunction with any other antenna or transmitter.
Under Industry Canada regulations, these radio transmitters may only operate using an antenna of a type
and maximum (or lesser) gain approved for the transmitter by Industry Canada. To reduce potential radio
interference to other users, the antenna type and its gain should be so chosen that the equivalent
isotropically radiated power (e.i.r.p.) is not more than that necessary for successful communication.
These radio transmitters IC9514A-683081118C1 and IC9514A-TZENHV have been approved by Industry
Canada to operate with the antenna types listed below with the maximum permissible gain and required
antenna impedance for each antenna type indicated. Antenna types not included in this list, having
a gain greater than the maximum gain indicated for that type, are strictly prohibited for use with
these devices.
Name/Model
Gain
Impedance
Inverted F-antenna
3.0 dBi
50 ohm
The term "IC" before the equipment certification number only signifies that the Industry Canada technical
specifications were met.
Le terme "IC" devant le numéro de certification signifie seulement que les specifications techniques
Industrie Canada ont été respectées.
End product labeling
The radio module is labeled with its own IC Certification Number. If the IC Certification Number is not visible
when a module is installed inside another device, then the outside of the device into which the module is
installed must also display a label referring to the enclosed module. In that case, the final end product must
be labeled in a visible area with the following:
'Contains IC: 9514A-683081118C1'
'IC: 9514A-TZENHV'

7
ASSA ABLOY Hospitality 66 8003 015-3
1. Introduction
Energy is a large cost for hotels, and an EMS (Energy Management System) is a way
of achieving energy savings in guest rooms. With the Orion EMS software option to
Visionline it is possible to
view the Orion EMS status of different rooms
modify the configurable parameters for a room (or group of rooms/
the entire property)
provide alarm conditions
provide energy savings reports
provide preventative maintenance reports
Note: For mounting of Orion EMS devices, installation of the software option etc,
see Installation manual Orion High VoltageThermostat.
Note: This thermostat is an independently mounted control for surface mounting.
A main task for Orion EMS is to determine whether or not a guest room is physically
occupied. When a room is not occupied, Orion EMS controls the HVAC (Heating
Ventilation and Air Conditioning) systems based on the configurable settings of the
system.
Note: For information about what firmware to use in different Orion EMS
configurations, see the document Upgrading an RFID lock for an Orion EMS offline
scenario.
Note: The best conditions for Orion EMS are obtained if also the locks are online and
commissioned to the same ZigBee network as the thermostat and the motion sensor.
Certain Orion EMS operations cause alarms; see chapter Energy management
summary and Alarm list for details. Occupancy status is included in all alarms. This
allows the staff to fix the problem that caused the alarm without bothering the guest.

8
ASSA ABLOY Hospitality 66 8003 015-3
1.1 Orion EMS devices
The devices used together with Orion EMS are:
digital thermostat Orion High Voltage Thermostat; from now on in this document
simply called 'thermostat'
Note: The thermostat has a built-in motion sensor, but in some cases (depending
on the location of the thermostat in the room)
it can be necessary to use an external motion sensor in addition.
door monitoring device; lock, RF door switch
Note: It is also possible to use a wired door switch without radio, but this
manual mainly describes the RF door switch. For more information about wired
door switches, see Installation manual Orion High Voltage Thermostat.
gateway (the same as is used for online doors; requires the Online option)
Note: The gateway is not used in offline scenarios.
Figure 1: Orion EMS example configuration
The thermostat has a built-in ZigBee router via which it communicates to the software
and the devices within the room. The thermostat stores all parameters needed for Orion
EMS; if the thermostat controller is used as well, the parameters (with a few exceptions;
see Installation manual Orion High Voltage Thermostat for details) are instead stored in
the thermostat controller. The parameters are either transferred online from the software
or from the Orion Service software; see Quick reference guide Orion Service for more
information about the latter.
Note: For each room number, it is possible to have either
one wired thermostat
up to five motion sensors
up to five door switches
OR one thermostat controller
up to five battery thermostats
up to five motion sensors
up to five door switches

9
ASSA ABLOY Hospitality 66 8003 015-3
1.2 Terminology
Deadband
The range the temperature is allowed to drift before heating or
cooling is activated.
Default setpoint
Default setpoint is the temperature which the thermostat is set to
until a guest changes the temperature. The thermostat will also
return to the default setpoint after guest check-out.
Dynamic setback
The dynamic setback temperatures are configured as
a set number of degrees above or below the guest setting.
For example, if the guest setting is 68 ºF (20 ºC) and the
unoccupied setback is configured to 7 ºF (4 ºC) above the
guest setting, the system will allow the temperature to drift
to 75 ºF (24 ºC) when the room is unoccupied.
EMS
Energy Management System
Exterior door
timeout
The time that will pass before the HVAC is turned off after
an exterior door is left open.
FCU
Fan Coil Unit
Freeze guard
If the temperature in any room with a thermostat goes
below 39 ºF (4 ºC), there will be an alarm and the HVAC
will start heating.
HVAC
Heating Ventilation and Air Conditioning
Intelligent switch
The intelligent switch is an output for lighting control which works
according to the occupancy status. The available alternatives for
intelligent switch are:
disabled; default
use RV output
use G2 output
If intelligent switch is applicable, normally 'Use RV output' should
be marked unless the air handler is a heat pump. In the latter
case, mark 'Use G2 output' instead.
Motion sensor
A device that detects a person's movement in an area.
Occupied
Someone is physically in the room; see section Room occupied
for more information.
Occupied limits
Limits the Set temperature range, i.e. the temperature
which the guest can set the thermostat to.
PTAC
(Package Terminal
Air Conditioner)
A PTAC is a fully self contained system that is typically
located on the exterior wall of a hotel room. These units
come in standard control or heat pump models.
Pre-condition time
Note: This
parameter
requires that the
Online option has
been set in
Visionline.
Number of hours the thermostat shall run at the default
setpoint after check-in. If no entry has been done when
this time expires, the unoccupied setback will be assumed.
The pre- condition time can be 1-12 hours or 'disabled';
default is 2 hours.

10
ASSA ABLOY Hospitality 66 8003 015-3
Pulse length
The welcome scene can be set up to have a pulse length:
0 = welcome scene always off
chosen length in the interval 1-255 seconds
Refresh cycle
The Orion EMS system can, in setback control, run the A/C unit
every 25 minutes for a period of 2 minutes to re-circulate the
air in the room; the optional function is only for cooling mode.
Setback
The temperature the room is allowed to drift to when the room
is unoccupied. Also see dynamic setback and static setback.
Setback override
The Orion EMS features can be overridden until the room is
unsold again, or until a certain time. If desired, the time can
be set far ahead so that the setback override is in practice
until further notice.
Setpoint
The temperature which the guest has set on the thermostat.
Static setback
The static setback temperatures are configured in the system
and do not change based on the guest settings. For example,
if the unoccupied upper setback temperature is 79 ºF (26 ºC),
the system will allow the temperature to drift to 79 ºF (26 ºC)
when the room is unoccupied regardless of the thermostat
setting (this example assumes that it is summertime) when
the room becomes unoccupied. As soon as the guest returns
to the room, the temperature is returned to the guest setting.
Unoccupied
No one is physically in the room although the room
may be currently rented; see section Room unoccupied
for more information.
Unsold
The room is not currently rented and no one is in the room.
In this case, a deeper setback is implemented for greater
energy savings. See section Room unsold for more information.
Welcome scene
If desired, it is possible to have a welcome scene which it is
activated when the occupancy state for a room changes from
unsold to unoccupied. The available alternatives for welcome
scene are (default is 'disabled'):
disabled
use RV output
use G2 output
use solid state relay
Table 1

11
ASSA ABLOY Hospitality 66 8003 015-3
1.3 General about Orion Service
A service device and the Orion Service software are used for:
initializing thermostats (setting room number and loading configurable
parameters)
commissioning the thermostat and the motion sensor in the network so
the messages are routed correctly
retrieving and displaying the event log from the thermostat
upgrading module firmware in thermostat and motion sensor
performing diagnostic operations, e.g.
-simulating inputs - e.g. door switch, motion/temperature
-reading out status of thermostat (the status of the motion sensor is
also shown)
-showing the output to the HVAC
-making a functionality test including fast clock mode; the thermostat
will raise the time one minute per second to test e.g. the room not
occupied timer
See Quick reference guide Orion Service for more information about how the above
operations are performed.
1.4 General about alarms
All Orion EMS alarms are shown in the dialog Energy management summary; see
chapter 3 for more information. In addition, they are shown in the alarm list. Unless
Orion EMS is installed as a separate client, the alarm list will also show other types
of alarms not related to Orion EMS, e.g. housekeeping failed.
If the Communication option is set in the software, notifications about Orion EMS
alarms can be sent via e-mail or SMS and reports can be sent by e-mail. The reports
that can be sent concern e.g.
energy savings
preventative maintenance schedules
occupancy (the report shows the number of occupied rooms each night; a room is
regarded as occupied for the night if it is physically occupied and there is at least
four hours of occupancy between 8 PM and 6 AM)
occupancy trend (the report is combined with the energy savings report and
shows occupancy during each time of the day; it is also possible to make as
an average for a longer period)
battery warnings
events for a selected room
offline rooms
These reports are sent via e-mail at the selected period to users that have been set
up in the user notification list of the software to receive the reports; see Installation
instruction Communication option for further information.

12
ASSA ABLOY Hospitality 66 8003 015-3
1.5 Events and commands
To the guest, the thermostat appears and operates as a standard digital thermostat;
however, this device also receives entry and exit information from the door lock or
switch as well as motion detected information from the motion sensor. This information
is used to determine the occupancy status of the room and implement energy savings
strategy based on this information.
In order for the locks to send door events to the thermostats, EMI events must
be enabled. This is achieved by presenting an Enable EMI events card at each lock.
The card is one of the ZigBee configuration cards that can be issued in Visionline;
see Installation manual Orion High Voltage Thermostat for details. The following
events are sent to the thermostat from the motion sensor:
motion detected
battery status
If the lock is online, the following events are sent to the thermostat from the lock:
door open – staff card
door open – guest card; includes check-out date/time, suite rooms and
first time use
door open from inside
door closed
deadbolt thrown/released
The thermostat stores the 75 latest events in a log.
Note: In addition to the relevant events from the lock to the thermostat, additional
events are sent from the lock to
the hotel system.
There are also commands sent from the thermostat to the lock (if online) and the
motion sensor:
to the lock: the optional auto-DND, which functions as privacy; no staff cards
will be able to open the door (only guest cards and emergency cards will open)
to the motion sensor: to turn off the motion sensor when the room is occupied
and the door is closed, and to turn on the motion sensor again when the door
is opened
Note: The commands from the thermostat to lock and motion sensor are not logged
as events.

13
ASSA ABLOY Hospitality 66 8003 015-3
1.5.1 Thermostat event report
The thermostat event report shows all events that have been sent online from the
thermostats or been transferred to the server via Orion Service; see Quick reference
guide Orion Service for details. The housekeeping function keeps the list size limited
by removing events that are older than a user defined number of days; default is
7 days. To look at a thermostat event report:
1. Double click on Thermostat events under the Reports tab in the
navigation window.
2. Enter the applicable search filter(s) under the tabs Events, Door or Miscellaneous
(see more information below) before pressing the Enter key or clicking OK.
Note: At least one of the following requirements must be met:
- a room is selected
- one or two event sub groups are selected
3. It is also possible to reload a previous search filter: click the Load… button in
the Events - Search filter dialog, browse to the desired file, mark it and click
Open. If you want to save a search filter for future searches: click the Save…
button, browse to where you want to save the file, give it a name and click Save.
If the filter should be shown under Custom in the Reports tab, it must be saved
in any of the following locations:
- the folder ’Custom Reports’ in the software installation folder
- the public documents folder
- the documents folder
The search filters that can be applied on thermostat events are:
Events –with this filter you can pick
out a specific event, or certain types
of events. The main types are Status
Changed and Alert. Within each main
type, there are event sub groups
which can be divided further into
specific events. If needed, use the
Check all/Uncheck all buttons at
the bottom of the dialog.
Figure 2
Door –with this filter you can pick
out events for a certain room. Click
the plus sign to expand a door area
and mark the applicable door.
Figure 3
Miscellaneous – with this filter
you can pick out events from certain
event dates.
Figure 4

14
ASSA ABLOY Hospitality 66 8003 015-3
1.6 Basic EMS logic
The thermostat along with the motion sensor, lock and/or RF door switches, monitors
the occupancy state of the room and operates based on this information. When the
room is occupied, the guest is given control and can set the desired temperature.
The thermostat will then heat or cool the room as necessary to meet the guest setting.
When the room is not occupied, the thermostat will operate based on the configurable
parameters of the system. The three occupancy states are occupied, unoccupied
and unsold. The following events are considered as in-room events:
motion
deadbolt engaged
thermostat key pressed
1.6.1 Room occupied
When the room is occupied, control of the HVAC system is given to the guest.
The guest sets the desired temperature and the HVAC system will control the room
based on this setting. The Orion thermostat will enter the occupied state only when
the door is closed and in-room events are detected (motion, deadbolt engaged,
thermostat key pressed). At this point, the guest has full control of the room
temperature.
Note: 'Occupied limits' may be used to restrict the guest setting limits.
1.6.2 Room unoccupied
When the room is not occupied, the energy management logic takes control of the
room based on the configurable parameters of the system. The system will set back
the temperature to the unoccupied setting. The system has both an upper setback and
a lower setback. The unoccupied setbacks may be static or dynamic; for unsold rooms,
only a static setback is used. See section Terminology for more information about static
and dynamic setback.
The thermostat will enter the unoccupied state upon the door opening or closing. If no
in-room event such as motion is detected, the thermostat will remain in the unoccupied
mode. The thermostat will continue to operate at the guest setting for the duration of
the configurable 'Room not occupied' timer, at which point it maintains the room
temperature based on the unoccupied setback temperatures.

15
ASSA ABLOY Hospitality 66 8003 015-3
1.6.2.1 Door open in 'room unoccupied' mode
If the door is left open, the occupancy state will remain as unoccupied regardless of
whether or not motion or another in-room event is detected. There is however also
a run state in the thermostat which is based on the set-point/guest setting. The run
state works differently depending on whether the open door is interior or exterior,
see details below.
If the open door is configured as an interior door (i.e., opens to another air conditioned
space), the thermostat will operate based on the guest setting as long as motion
or another in-room event is detected. Each time an in-room event is detected, the
‘Room not occupied’ timer will restart. If the ‘Room not occupied’ timer elapses without
motion or another in-room event being detected, the thermostat will maintain the room
temperature based on the unoccupied setback temperatures.
If the open door is an exterior door (i.e., opens to a non-climate controlled space),
the thermostat will turn off after the ‘Room not occupied’ timer expires regardless
of whether or not motion is detected.
Note: If the exterior door timeout is set to ‘Short’, the thermostat will turn off the
air handler after 20 seconds. See chapter 4 Thermostat profiles list, section Under
the Timeout tab, for details about setting the exterior door timeout.
1.6.3 Room unsold
To achieve more energy savings when the room is not rented, the setback is deeper
than when the room is rented but unoccupied. The system will enter the unsold setting
when the room has been unoccupied for the duration of the configurable ’Room not
sold’ timer. In the unsold mode, the temperature is based on the unsold setback
temperatures.
Note: If using an online system, the room will immediately enter the unsold mode upon
receiving a check-out command from the property management system (PMS) or at
guest card expiration.
Note: The unsold mode gives the greatest potential for energy savings. For this reason,
the online system allows for maximum energy savings as the room does not need to
wait until the ‘Room not sold’ timer elapses to enter the deep setback mode.
1.6.3.1 Door open in 'room unsold' mode
Similar to the door open condition in the unoccupied state, the thermostat will control
the temperature based on the guest setting when an interior door is open and motion
(or any other in-room event) is detected for a period of time equal to the ‘Room not
occupied’ timer. If the timer elapses with no further detection of in-room events,
the thermostat will revert to maintaining the room temperature at the unsold setback.
If an exterior door is left open, the thermostat will turn the air handler off.

16
ASSA ABLOY Hospitality 66 8003 015-3
1.6.4 Staff entry
In order to maximize energy savings, certain considerations must be taken into
account when staff members enter the room.
1.6.4.1 Door monitored by RF door switch
If the position of the door is monitored by an RF door switch, the staff member
must leave the door open to avoid interrupting the ‘Room not sold’ timer. If the staff
member allows the door to close, the room will enter the occupied state upon motion
detection. As long as the door is left open, the ‘Room not sold’ timer will not be reset.
1.6.4.2 Door monitored by electronic lock
If the door position is monitored by the electronic lock and a staff key unlocks the door,
the room will not enter the occupied state even if motion is detected while the door is
closed. However, if a thermostat key is pressed or the deadbolt is engaged while the
door is closed, the room will enter the occupied state.
Note: If a staff member lets a guest into a room with the door position monitored by
an electronic lock, the room will remain unoccupied until the deadbolt is engaged or a
button on the thermostat is pressed.
1.6.5 Operating states
The following series of tables shows the operation of the system in various scenarios.
Note: The scenarios consider that the unoccupied (or exterior door open) timers have
expired if applicable.
1.6.5.1 One interior door
Door
In-room Event
(Motion/
Thermostat Key Pressed/
Deadbolt Engaged)
HVAC
State
Closed
Yes
Per guest setting
Occupied
Open
Yes
Per guest setting if opened by guest.
Setback if opened by staff.
If no lock interface, per guest setting.
Unoccupied or Unsold
Closed
No
Setback
Unoccupied or Unsold
Open
No
Setback
Unoccupied or Unsold
Table 2

17
ASSA ABLOY Hospitality 66 8003 015-3
1.6.5.2 One exterior door
Door
In-room Event
(Motion/
Thermostat Key Pressed/
Deadbolt Engaged)
HVAC
State
Closed
Yes
Per guest setting
Occupied
Open
Yes
OFF (20 seconds or
standard unoccupied
time)
Unoccupied or Unsold
Closed
No
Setback
Unoccupied or Unsold
Open
No
OFF (20 seconds or
standard unoccupied
time)
Unoccupied or Unsold
Table 3
1.6.5.3 One exterior and one interior door
Interior Door
Exterior Door
Motion
HVAC
State
Closed
Closed
Yes
Per guest setting
Occupied
Open
Closed
Yes
Per guest setting
Unoccupied or Unsold
Closed
Open
Yes
OFF
Unoccupied or unsold
Open
Open
Yes
OFF
Unoccupied or Unsold
Closed
Closed
No
Setback
Unoccupied or Unsold
Open
Closed
No
Setback
Unoccupied or Unsold
Closed
Open
No
OFF
Unoccupied or Unsold
Open
Open
No
OFF
Unoccupied or Unsold
Table 4

18
ASSA ABLOY Hospitality 66 8003 015-3
1.6.6 Thermostat control chart
Figure 5
The thermostat control can be illustrated in a control chart, see example above.
If the temperature drifts above the setpoint or setback (depending on occupancy
mode), the HVAC starts in cooling mode.
The thermostat deadband is in this case 2 ºF, so when the temperature is within
2 ºF from the setpoint the HVAC is off (from 0 to 2 in the picture).
If the temperature continues to rise, the thermostat output for ‘Fan 1/Low’
is triggered, then the output for ‘Fan 2/Medium’ and finally the output for
‘Fan 3/High’.
If the temperature starts dropping, the HVAC then switches to heating mode.
There is however a heat/cool switch deadband which in this example is 3 ºF,
so the temperature is allowed to drift 3 ºF from the setpoint before the HVAC
switches from cooling mode to heating mode. From 0 to -3 in the picture the
HVAC is off; the output for ‘Fan 1/Low’ is therefore not triggered, since this
would have been at -2.
If the temperature continues to drop, first the output for ‘Fan 2/Medium’ is
triggered and then the output for ‘Fan 3/High’.
The Orion EMS devices strive towards different temperatures depending on if the
room is occupied, unoccupied or unsold.
For ‘occupied mode’ the goal is the setpoint, i.e. the temperature which the
guest has set on the thermostat.
For ‘unoccupied mode’ the temperature drifts to the unoccupied setback,
which can be static or dynamic.
For ‘unsold mode’ the temperature drifts to the unsold setback.

19
ASSA ABLOY Hospitality 66 8003 015-3
1.7 Orion EMS parameters
There are a number of Orion EMS parameters whose values can be modified in the
software. Different operator templates can be given different authorities to modify
the parameters. Some parameters are considered as basic and some as advanced.
Note: In the parameter column below, it is also stated in what software dialog the
parameter is found.
Note: The parameter dwell-off time is a setting that will guard against short-cycling
and its value is 5 minutes. The parameter is not visible in the software and cannot be
changed, not even by the distributor. Default is that the dwell-off time is off; it is only
applicable when 'heat pump' is chosen as HVAC type. In the 'heat pump' case, the
thermostat will automatically force the dwell-off time to be on.
Parameter
Description
Available choices
Default setting
Default set point
(Thermostat profile
details dialog, Misc tab)
The temperature which the
thermostat is set to until a guest
changes it. The thermostat will
also return to the Default set point
after check-out.
64-75 ºF
70 ºF
Enable lights during
pre-condition time
(Thermostat profile
details dialog, Misc tab)
Note: This parameter
requires that the Online
option has been set in
Visionline.
The lights are enabled according to
the chosen intelligent switch setting
during the pre-condition time.
Disabled
Enabled
Enabled
Exterior door timeout
(Thermostat profile
details dialog,
Timeout tab)
If the exterior door is open and the
default 'Normal' is used, the HVAC
will - regardless of room occupancy
status - turn off after the number
of minutes entered at 'Room not
occupied'. Default is 8 minutes; see
Room not occupied timer in Table 6.
If the exterior door is open and
'Short' is used, the HVAC will turn
off after 20 seconds.
Normal/short
Normal
Exterior input behaves
as window
(Thermostat profile
details dialog, Misc tab)
The HVAC will be shut off after a
configured time (short or normal),
but the thermostat does not change
the occupancy status. The exterior
door timeout is triggered by the
wired input for exterior door open
(EX1) on the thermostat.
Disabled
Enabled
Disabled
Fan control
(Thermostat profile
details dialog, Fan tab)
The thermostat has a button which
allows the user to select from up
to three fan speeds, or to choose
‘Automatic’ (AUTO) if the thermostat
Auto/manual
Max fan cool
(low, mid, high)
Manual
High
High

20
ASSA ABLOY Hospitality 66 8003 015-3
should determine the appropriate
fan setting.
Note: The ability to control fan
speeds depends on the capability
of the air handler, as some systems
do not have three fan speeds.
Max fan heat
(low, mid, high)
Fan on when satisfied
(Thermostat profile
details dialog, Fan tab)
When enabled, the low fan speed
will continue to run even when the
setpoint has been reached. This
only applies to an occupied room.
Disabled
Enabled
Disabled
Freeze guard
(Thermostat profile
details dialog, Misc tab)
There will be an alarm and the
HVAC will start heating if the
temperature in any room with
thermostat goes below 39 ºF (4 ºC).
Disabled
Enabled
Enabled
Heat/cool switch
deadband
(Thermostat profile
details dialog,
Deadband tab)
This parameter is only applicable
if auto switching mode has been
chosen under the HVAC tab in the
Thermostat profile details dialog.
The heat/cool switch deadband is
the range the temperature is allowed
to drift before switching from heat to
cool or cool to heat.
2-4 ºF
3 ºF
Humidity control
(Thermostat profile
details dialog, Misc tab)
When the humidity control option
is checked, the thermostat will
implement control measures if the
humidity in the room gets too high.
Note: The control measures will
only be implemented when the
room is unoccupied or unsold.
Disabled
Enabled
Disabled
HVAC control
(Thermostat profile
details dialog, HVAC tab)
See available choices to the right.
'Heat pump reversed valve (Type B)'
means that the reversing valve
output is on when heating.
'Heat pump reversed valve (Type O)'
means that the reversing valve
output is off when heating.
For 'HVAC heating'
and 'HVAC cooling':
n/a
4-pipe fan coil
2-pipe fan coil
2-pipe fan coil with
automatic switching
Proportional
Floating valve
For 'HVAC heating' only:
Heat pump reversed
valve (Type B)
For 'HVAC cooling' only:
Heat pump reversed
valve (Type O)
n/a
Intelligent switch
(Thermostat profile
details dialog, Misc tab)
The intelligent switch is an output
for lighting control which works
according to the occupancy status.
The intelligent switch is an output
for lighting control which works
according to the occupancy status.
Disabled
Use RV output
Use G2 output
Disabled
Other manuals for Orion
1
Table of contents
Other Assa Abloy Thermostat manuals
Popular Thermostat manuals by other brands

Ariston
Ariston 3319483 Installation and operating instructions

Honeywell
Honeywell THX9000 Prestige HD installation guide

Kegco
Kegco RTC-2 instruction manual

Stelpro
Stelpro SHUT1 Series Installation

Aprilaire
Aprilaire 8532 operating instructions

Digital Monitoring Products
Digital Monitoring Products SecureCom Smart Z-5010T Installation and programming guide