Features
Provides Temporal Code 4 (TC4) NAC
(Notification Appliance Circuit) control for
Carbon Monoxide (CO) gas warning:
•The TC4 CO gas warning is a repeated sequence of
four cycles of 100 msec on with 100 msec off,
followed by 5 seconds off per NFPA 720, Standard
for the Installation of Carbon Monoxide (CO)
Warning Equipment in Dwelling Units
•Compatible appliances includes: CO Sounder Bases
4098-9771 and 4098-9798, 4901-9820 Horn (set for
free-run), 49CMT Series multi-tone horns (set for
free-run horn tones), and 4903 Series 4-wire A/V
appliances horn input (not compatible with SmartSync
horn control appliances)
Compatible equipment NAC sources:
•AUTOPULSE Z20
•Simplex 4007ES Hybrid, 4010ES, 4100ES, and
4100U NAC outputs
•4009 IDNet NAC Extender NAC outputs
•Each module requires an input NAC that powers the
3A rated output NAC for control of compatible
audible notification appliances only (not for strobes)
Three selectable operation modes:
•Synchronized operation allows a separate and
dedicated control NAC to both activate and
synchronize the Temporal Code 4 output timing of up
to 20, 4905-9835 modules
•Unsynchronized operation also allows the separate
and dedicated control NAC to activate the Temporal
Code 4 output timing of up to 20, 4905-9835 modules,
but without synchronization between the modules
•Stand-Alone operation allows the input NAC in
alarm to activate Temporal Code 4 timing for NACs
dedicated for CO gas alarm; no fire alarm signals are
available, no control NAC is used
•For both Synchronized and Unsynchronized modes,
when the control NAC is off, the module output NACs
will follow the fire alarm signals of the input NAC
•NOTE: For TC4 output, both the input NACs and the
control NACs requires a Steady On signal
Compact, sealed construction:
•Mounts in standard 4” square electrical box
•Compatible with Adapter Plate 4090-9813 to fit
4 11⁄16” (119 mm) square electrical boxes
•Screw terminals for wiring connections
Listed to UL 864 and ULC S527
Description
CO gas alarm warnings are required to be different from
fire alarm warnings. In the event of a CO gas alarm, the
presence of a Temporal Code 4 audible signal pattern
identifies the type of condition to the responders to assist in
determining the proper actions to be taken.
ON
1 2
4905-9835 Temporal Code 4 Module
(shown approximately 1/2 size)
Description (Continued)
CO gas alarm, or fire alarm. Use of the 4905-9835
Temporal Code 4 Module allows the NFPA 720 Temporal
Code 4 signal to be generated using a standard Steady On
audible appliance NAC input. Under the fire alarm panel’s
control, the audible notification signal can be selected for a
conventional fire pulse pattern for a fire alarm condition, or
the Temporal Code 4 pattern can be activated for a CO gas
alarm condition.
Specifications
NAC Control
For 24 VDC NACs, up to 3 A
maximum, limited by input NAC
rating; for control of audible
notification appliances compatible
with TC4 code pulse duty cycle
Input NAC Current
Requirements Supervisory current = 0.18 mA
Alarm current = 15 mA
Control NAC Current
Requirements Supervisory current = 0 mA
Alarm current = 3 mA
Mounting Distance
to input NAC Source Mount close-nippled, 20 ft (6 m)
maximum distance
Wire Connections Screw terminals for in/out wiring,
18 to 12 AWG wire
(0.82 to 3.31 mm
2
)
Dimensions 4” x 4 ⅛” x 1 ⅜” D
(102 mm x 105 mm x 35 mm)
Mounting Plate
Material Sheet metal, galvanized
Temperature Range 32° to 120° F (0° to 49° C),
intended for indoor operation
Humidity Range Up to 93% RH at 100° F (38° C)
* This product has been approved by the California State Fire Marshal (CSFM) pursuant to
Section 13144.1 of the California Health and Safety Code. See CSFM Listing 7300-0026:328
for allowable values and/or conditions concerning material presented in this document. This
product was not accepted by MEA (NYC) as of document revision date. Additional listings
may be applicable; contact your local Simplex product supplier for the latest status. Listings
and approvals under Simplex Time Recorder Co. are the property of Tyco Fire Protection
Products.
Non-Addressable Peripherals
UL, ULC, CSFM Listed; 4905-9835 Temporal Code 4
FM Approved* Module for CO Gas Alarm Notification
T-2016293-1 10/2016
T-2016293-1 10/2016
© 2016 Tyco Fire Protection Products. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice.
TYCO, AUTOPULSE, SIMPLEX, and the product names listed in this material are marks and/or registered marks. Unauthorized use is strictly prohibited. NFPA is a trademark of
the National Fire Protection Association.
4" square cover plate, RACO 752
or equal (supplied separately)
Mounting Box (supplied separately), 4" square
(102 mm), minimum depth = 2-1/8" (54 mm),
RACO 232 or equal
PO W ER
BEFO RE
SERVI CING
CAUTI O N
DISCO NNECT
4009 IDNetNAC EXTENDER
TM
Dedicated control NAC to the next Temporal
Code 4 Module, up to 20 total maximum; requires
end-of-line resistor per source NAC requirements
Z20 Fire Alarm Control Panel
4009 IDNet NAC Extender (shown, uses IDNet
communications) or Remote 4100ES MINIPLEX
transponder with NACs (uses RUI communications)
Dedicated control NAC
CO Sensor
Sounder Base*
NAC input to TC4
Module, 3 A maximum
IDNet or RUI Communications
per system requirements
ON
1 2
ON
1 2
4905-9835 Temporal Code 4 (TC4) Module
TC4 NAC output, 3 A maximum
4901-9820 Horn, 4903 Series 4-wire A/V horn,
or other compatible (not SmartSync control)
24 VDC audible notification appliances
Appliance NACs require
end-of-line resistor per
source NAC requirements
* Note: IDNet communications wiring
(not shown) is required to connect
to each CO Sensor Sounder Base
Product
Data Sheet
Product
Data Sheet
AUTOPULSE Z-20 Detection System Agent
Release Fire Control Panel
T-2016171
AUTOPULSE 4090-9116 Addressable IDNet
Communications Isolator
T-2016178
AUTOPULSE TrueAlarm Analog Sensors –
Photoelectric and Heat; Standard Bases and
Accessories
T-2016183
AUTOPULSE E-Series Analog Heat Sensor 4098-
9733E and Bases for Extended Exposure to High
Humidity
T-2016186
AUTOPULSE Dual Address Bases for Multi-
Sensor 4098-9754, Standard and Sounder
T-2016185
AUTOPULSE IDNet or MAPNET II Communicating
Devices; Addressable Manual Stations for
Releasing Applications
T-2016190
AUTOPULSE IDNet Addressable Devices,
Model 4090-9007 Signal IAM (Individual
Addressable Module)
T-2016191
Mounting Reference
System Connection Reference
Additional Reference

Popular Security Sensor manuals by other brands

Profort PirSpot manual

Profort

Profort PirSpot manual

National Instruments SCC-RTD01 user guide

National Instruments

National Instruments SCC-RTD01 user guide

Banner EZ-SCREEN LS instruction manual

Banner

Banner EZ-SCREEN LS instruction manual

Silverline 288659 operating instructions

Silverline

Silverline 288659 operating instructions

Omron K8AC-H2 manual

Omron

Omron K8AC-H2 manual

Aleph XC-1XTEU manual

Aleph

Aleph XC-1XTEU manual

eTIGER ES-D2A user manual

eTIGER

eTIGER ES-D2A user manual

CPS Leak-Seeker I Operation manual

CPS

CPS Leak-Seeker I Operation manual

Inficon HLD6000 installation manual

Inficon

Inficon HLD6000 installation manual

Grasslin talis PFSL 360-8-1 operating manual

Grasslin

Grasslin talis PFSL 360-8-1 operating manual

aci SPID2 user manual

aci

aci SPID2 user manual

BBC Bircher AirMission 2.W2 Translation of the original operating instruction

BBC Bircher

BBC Bircher AirMission 2.W2 Translation of the original operating instruction

Nice LP21 User, installation and safety instructions

Nice

Nice LP21 User, installation and safety instructions

SharpEye 40I user guide

SharpEye

SharpEye 40I user guide

EINHELL TC-MD 50 Original operating instructions

EINHELL

EINHELL TC-MD 50 Original operating instructions

WATERGUARD Solo installation guide

WATERGUARD

WATERGUARD Solo installation guide

ELRO FC451011 instruction manual

ELRO

ELRO FC451011 instruction manual

Babolat PIQ Fuel Battery Bank user guide

Babolat

Babolat PIQ Fuel Battery Bank user guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.