Axema UDR-Plus User manual

Axema Access Control AB | Box 90215 | 120 23 Stockholm, Sweden | 08-722 34 40 | info@axema.se | www.axema.se
UDR-Plus
Universal door alarm
Manual
Updated 2018-11-17

UDR-Plus
Description 3
Connections and configuration 3
Terminals 4
Dip switch 4
Jumpers for alarm trigger 5
DL 12 LED Status 5
Programming 5
Settings 5
Installation examples 7
The alarm is set of by a closing magnet contact and is reset when the door
is shut. 8
NC relay when the door is closed 8
NO relay when the door is closed 9
UDR-plus with code lock and electric lock 10
VAKA with UDR-plus 12
UDR with extended flash. 14
UDR-plus with ASSA evacuation lock 16
Accessories 17
Technical Data 17
2 (17) Manual UDR Plus

Description
UDR-plus is a compact door alarm for all types of doors. UDR-plus can signal
when a valid pass is made (optional function) and activates the internal siren when
an invalid pass is made. The functions are programmed using a DIP switches
and duration times are programmed using the P1 and P2 buttons.
Connections and configuration
3 (17) Manual UDR Plus

Terminals
1, 2 Alarm trigger
Controlled by connection or voltage (10-30 V DC).
Delay 0-5 sec.
Activates siren, 1 sec. - 60 min. and flash.
Volume, 65-90 dB. 0, deactivates sound signal.
3, 4 Reset
Resets the alarm if the door is closed
5, 6 Bypass
Allows the door to be open 1 sec. - 5 min. before the alarm is
activated
DL14 lights up when bypass and relay 1 is activated.
Bypasses the alarm when the door is open and reset the alarm if
the door is closed.
7, 8 Signal
Activates signal, 45-77 dB, and flash. 0, deactivates sound sig-
nal.
Follows the status of the input, no duration control.
9, 10 Supply voltage
10-30 V DC.
9, +
10, GND
Tamper
output
Vandal protection
Indicates both wall removal and opening of housing. Normally
closed.
The contact is closed the shell is shut
11 - 13 Potential free relay output for alarm by pass
Follows the by pass input. Used for lock or by pass.
14 -16 Potential free relay output for alarm
Activates by trigger input.
Dip switch
1. Alarm trigger
2. Signal
3. Reset
4. By pass
4 (17) Manual UDR Plus

Jumpers for alarm trigger
DL 12 LED Status
Flashes during operation.
Rapid flash during trigger or delay.
Programming
Press and hold
P1
for approximately 2 seconds. The status LED should shut of and
configuration LED 1 should turn on. The display will show the preset delay before
the alarm is activated. The red dot by the display indicates that the delay is in
minutes
lA short press on
P1
moves to the next setting.
lA long press on
P1
until Status LED 13 changes switches the function of
P2
,
see below.
l
P2
is used to increase or decrease the value. If status LED13 is lit,
P2
is
used to decrease the value, otherwise
P2
is used to increade the value.
Settings
1. Delat before the alarm is activated
Configuration LED 3 is lit up.
0 sec. to 5 min., factory set to 0 sec.
5 (17) Manual UDR Plus

2. Siren duration
Configuration LED 2 is lit up.
1 sec. to 60 min., factory set to 30 sec.
3. Alarm bypass
Configuration LED 2 and 3 are lit.
1 sec. to 5 min., factory set to 30 sec
4. Siren volume
Configuration LED 1 is lit.
1 to 99 (65-90 dB/m), 0 turns off the siren. Factory set to 50.
5. Signal volume
Configuration LED 1 and 3 are lit.
1 to 99 (45-77 dB/m), 0 turns of signal. Factory set to 50.
When the settings are made, press
P1
until two lines are shown in the display and
all three configuration LEDs are flashing. Therafter, press and hold
P1
until six lines
are shown in the display and all configuration LEDs turn off.
6 (17) Manual UDR Plus

Installation examples
7 (17) Manual UDR Plus

The alarm is set of by a closing magnet contact and is reset
when the door is shut.
lReset by connecting terminal 3 and 4.
If the alarm should not reset, connect terminal 3 to C2 and NC6. The alarm
has to be reset manually using the reset input.
lDuration of siren and any delay has to be set. See Programming.
NC relay when the door is closed
Terminal on UDR-Plus Connects to
1 Terminal 3 on UDR-Plus.
1 C on magnet contact
9 +10 - 30 VDC
10 GND
8 (17) Manual UDR Plus

NO relay when the door is closed
Terminal on UDR-Plus Connects to
1 NO on magnet contact
2 C on magnet contact
3 NC on magnet contact
9 +10 - 30 VDC
10 GND
9 (17) Manual UDR Plus

UDR-plus with code lock and electric lock
The example shows a door where the code lock allows an entry duration equal to
the sum of the relay time on the code lock and alarm bypass time. If possible, use
only the relay time on the code lock to prevent bypassing the alarm when the door
has been closed again.
lMagnet NO when the door is shut.
lThe alarm is reset using code.
lGiven that the alarm has not been activated, UDR is reset when the door is
shut if switching magnetic contact is used. If the alarm has been activated, it
has to be reset using code.
lIf the alarm is set of while the door is opened and a valid code is entered, the
alarm is reset and will remain bypassed until the door is closed again. When
the door is closed, UDR return to normal operation mode.
lIf A66 is used, another door monitor can be connected to deactivate the
relay immediately when the door is shut. The magnet contact is connected
directly to the reset input, not via C2-NC2.
10 (17) Manual UDR Plus

Terminal on UDR-Plus Connects to
1 NO on magnet contact
2 C on magnet contact
3 Terminal 15 on UDR-Plus
5 NO on code lock
6 C on code lock
9 +10 - 30 VDC
10 GND (Also connects to electric lock)
11 Electric lock
13 +10 - 30 VDC
16 NC on magnet contact
11 (17) Manual UDR Plus

VAKA with UDR-plus
lSet siren duration. See Programming.
lRequires door monitoring to be mounted and connected to the door
controller.
lBy pass duration should be set to 1 second.
lIf the door is forced open, the alarm will be set off.
lThe alarm is reset when a valid pass is made,
lThe lock is connected to UDR.
lIf B16 or 17 is used, connect the door monitoring directly to UDR-Plus
according to the top example.
Terminal on the door controller Connects to
3 Terminal 6 on UDR-Plus
4 Terminal 5 on UDR-Plus
12 Terminal 9 and 13 on UDR-Plus
13 Terminal 10 on UDR-Plus
13 Electric lock
21 (Only B26/27) Terminal 2 on UDR-Plus
22 (Only B26/27) Terminal 1 on UDR-Plus
12 (17) Manual UDR Plus

Terminal on UDR-Plus
11 Electric lock
13 (17) Manual UDR Plus

UDR with extended flash.
lRequires switching door contact.
lThe alarm is set off immediately with sound and flash if an invalid pass is
made. After the door has been closed, the flash continues for the set siren
duration.
lReset by connecting terminal 5 and 6.
1. Alarm trigger
0 sec., cannot be changed.
2. Siren duration
1 sec. to 60 min.
3. By pass
1 sec., cannot be changed.
4. Siren volume
0, cannot be changed.
5. Signal volume
0-99.
14 (17) Manual UDR Plus

Terminal on UDR-Plus Connects to
1 C on magnet contact
2 NC on magnet contact
5 Reset
6 Reset
7 NO on magnet contact
9 +10 - 30 VDC
10 GND
15 (17) Manual UDR Plus

UDR-plus with ASSA evacuation lock
lWhen the evacuation handle is pulled, a connection is made that triggers
the alarm.
lIf the evacuation handle is reset, (the connection between terminal 1 and 2
disappears) and the lock bolt is extended (connection between terminal 3
and 4), the alarm will be reset.
lThe lock bolt causes a connection between C and NO when the bolt is
retracted, which generates a warning signal. The warning can be removed
by disconnecting the cable to terminal 7.
Terminal on UDR-Plus Connects to
1 NO on magnet contact
2 C on magnet contact
3 NC on magnet contact
4 C on magnet contact
7 NO on magnet contact
9 +10 - 30 VDC
10 GND
16 (17) Manual UDR Plus

Accessories
Green, 1-9033-7
Black, 1-9033-8
Technical Data
Attributes UDR Plus
Power Supply 10 - 30 V DC
IP classification IP40
IK classification IK07
Temperature -20° to + 50°C
17 (17) Manual UDR Plus