AX-ET-6
Electronic Thermostat – Six stage
Product overview
The Axio AX-ET-6 is a six stage electronic thermostat with a two
line LCD display to simplify setting p. The nit controls
temperat re between -10°C to +110°C sing config rable heating
and cooling stages. The set point can be adj sted locally sing
p sh b ttons or remotely with a 1-11kΩ potentiometer. A setback
inp t is provided for se with an external switch. The minim m
and maxim m temperat res val es are stored for display via the
men . The AX-ET-6 is provided in a DIN rail carrier and is
available as 24Vac/dc or 230Vac powered versions.
Features
● Setpoint range -10°C to +110°C ● Adj stable stage on/off delay time
● Adj stable differential per stage ● 24Vac/dc or 230Vac versions
● LCD display of temperat re, setpoint etc ● DIN rail carrier as standard
● Setback inp t ● High q ality rising clamp terminals
Product specifications
Power S pply AX-ET-6-24 24Vac 280mA or 24Vdc 110mA ±15%
AX-ET-6-230 230Vac ±15%
Inp ts Sensor, 10K3A1 ( See Axio temperat re sensor range )
Remote Setpoint, 1-11kΩ ( For ± 4°C or ±20°C )
Setback, volt free timer inp t (Close contact to activate setback)
LCD Display 2 lines by 8 characters
Temperat re Range -20°C to +120°C
Stage Selection CCCCCC, CCCCCH, CCCCHH, CCCHHH, CCHHHH, CHHHHH, HHHHHH
(C=cooling, H=heating)
Setpoint -10°C to +110°C
Offset 0 to 50°C
Differential 0 to 12°C
Setback Range 0 to 30°C
On/Off delay Time 1 to 250 seconds
O tp t Contacts 6 SPNO volt free relays, rated at 10A, 250Vac, resistive load
Terminals Rising clamp for 0.5-2.5mm2 cable
Dimensions & Weight AX-ET-6-24 103(W) x 82(H) x 48(D) mm / 125 gms
AX-ET-6-230 160(W) x 82(H) x 55(D) mm / 365 gms
Ambient temperat re range 0 to 50°C
Co ntry of origin United Kingdom
Order codes Order online at:
www.annicom.com
Email orders and enq iries to:
[email protected]
AX-ET-6-24
AX-ET-6-230
Six Stage Electronic Thermostat - 24Vac/dc
Six Stage Electronic Thermostat - 230Vac
1 of 4
Iss e 1.1 (1/05/12) Annicom Ltd
Unit 21, Highview, Bordon,Hampshire. GU35 0AX.
Tel: +44(0)1420 487788 Fax: +44(0)1420 487799
Email: [email protected]
www.annicom.com
© Copyright Annicom 2012. All rights reserved.
1 of 4
AX-ET-6
Electronic Thermostat – Six stage
Installation
The AX-ET-6 sho ld be installed by a s itably q alified technician in conj nction with any g idelines for the eq ipment it is to be
connected to. Field wiring sho ld be installed to satisfy the req irements set o t by the man fact rer of the eq ipment that the mod le
is being connected to.
Description and Connections
2 of 4
Menu
Repeatedly press to scroll thro gh the Act al, Min-max,
Setpoint, On Delay and Off Delay displays.
Setpoint
The setpoint can be adj sted between -10°C and 110°C sing the
and switches. When connected a remote pot can
be sed to adj st the setpoint val e by either ±4°C or ±20°C from
the val e set. All the stage offsets are fixed to the setpoint and
track changes in the setpoint val e. It is possible to provide the
same switching actions with different setpoint and offset
combinations. The only limitation on the setpoint location is that
all cooling offsets are above the setpoint and all heating offsets
are below the setpoint.
Setpoint adjust ent
When the Act al temperat re display is visible press or
to select the Setpoint display then press or
to adj st the setpoint.
Stage offset
The stage offset sets the centre point of the heating or cooling
stage. If the stage is set for heating the offset is taken away from
the setpoint. If the stage is set for cooling the offset is added to
the setpoint.
Stage differential
This sets the total differential for the stage. The differential is
centred on the stage offset, therefore a differential of 4°C will set
the stage relay switching points to 2°C above the offset and 2°C
below the offset.
MENU
I NC DEC
I NC
DEC I NC
DEC
Stage switching
If the stage is set for cooling the relay will switch on when the
temperat re rises above the pper switching point and will
switch off when the temperat re falls below the lower switching
point. If the stage is set for heating the relay will switch on when
the temperat re falls below the lower switching point and will
switch off when the temperat re rises above the pper switching
point. An example of these val es is given on the next page.
Setback
To activate the setback close the contact across the setback
terminals, the display will show Act al Sb. When Setback is
active it will increase all the offsets by the set amo nt. This will
red ce the heating stage switching points and increase the
cooling stage switching points.
Remote Setpoint (External potentiometer)
Select the req ired range, ±4°C, ±20°C sing the set- p mode and
connect a 1-11kΩ potentiometer across the External Pot
terminals. The setpoint display will show SP with EP and will
show the adj sted setpoint val e.
Minimum and maximum temperature
The minim m and maxim m sensor temperat re val es are
stored by the AX-ET-6 ntil power is removed. When the Act al
temperat re display is visible press to display the Min
Max O tp t display. Press to display the minim m
val e. Press to toggle between the minim m and
maxim m val es. Hold down for 2 seconds to reset the
minim m and maxim m val es.
MENU
I NC
I NC
I NC
MENU
0V Common
24Vac/dc
Stage
1
Sensor External
Pot
Set
Back
AX ET6 24
Actual
25.0°C
DEC
INC
Stage
2
Stage
3
Stage
4
230Vac
L N
Stage
5
Stage
6
MENU
Stage
1
Sensor External
Pot
Set
Back
AX ET6
230
Actual
25.0°C
DEC
INC
Stage
2
Stage
3
Stage
4
Stage
5
Stage
6
AX-ET-6
Electronic Thermostat – Six stage
3 of 4
Setup mode
When the Act al temperat re display is visible press and hold
for 10 seconds to gain access to the set- p mode.
S bseq ent presses of scroll thro gh the options shown
in the table.
Selection Option/Range Description
Stage select CCCCCC to HHHHHH Set stage action
S1 Offset 0 to 50°C Stage 1 offset
S1 Differential 0 to 12°C Stage 1 differential
S2 Offset 0 to 50°C Stage 2 offset
S2 Differential 0 to 12°C Stage 2 differential
S3 Offset 0 to 50°C Stage 3 offset
S3 Differential 0 to 12°C Stage 3 differential
S4 Offset 0 to 50°C Stage 4 offset
S4 Differential 0 to 12°C Stage 4 differential
S5 Offset 0 to 50°C Stage 5 offset
S5 Differential 0 to 12°C Stage 5 differential
S6 Offset 0 to 50°C Stage 6 offset
S6 Differential 0 to 12°C Stage 6 differential
Setback 0 to 30°C Setback val e
External Pot None, ±4°C, 20°C Ext pot range
When the display shows the item to be modified
press or to adj st the parameter. Refer to Set p
diagram below for the complete men seq ence.
Exit setup and saving
The nit will exit set- p mode when no b tton presses have been
detected for 5 seconds, the display will revert to the act al
temperat re reading and saves the new settings.
Output display
The c rrent state of the relays can be checked sing the O tp t
display. When the Act al temperat re display is visible press
to display the Min Max O tp t display. Press to
display the c rrent o tp t state. An H or C is shown when the
stage relay is on whilst a dash is shown when the stage relay is
off.
Minimum On and Off times
This f nction prevents over-cycling of the o tp t. For example
setting the minim m on time to 5 seconds will ens re any o tp t
stage is in on for a minim m of 5 seconds. The Off time works
in a similar way. When the Act al temperat re display is visible
press three times to display the On val e. Press
or to adj st the parameter. Press once more to
display the Off val e. Press or to adj st the
parameter.
ack-light
The back-light on the LCD display switches on when any of the
b ttons are pressed and remains on for 10 seconds after the last
b tton has been pressed. The back-light will switch off if it has
been contin o sly on for 2 min tes.
Fault indication
If the sensor or external potentiometer, when selected, are open
or short circ it the display will show a fa lt message and the
back-light will flash.
I NC DEC
MENU
MENU
MENU I NC
DEC MENU
I NC DEC
MENU D EC
`
Hold for 10 seconds
to enter setup menu
Min Max
Outputs On Del
5 Sec
Off Del
5 Sec
MENU MENU MENU
Actual
25.0oC
StgeSlct
CCCHHH
S1 Offst
5.0oC
S1 Diff
1.0oC
MENU MENU MENU MENU S2 Offst
5.0oCMENU S2 Diff
1.0oC
INC DEC INC DEC INC DEC INC DEC INC DEC
INC
DEC
Select Cooling,
Heating stages
0 to 50 °C 0 to 12 °C
Setpoint
25.0oC
INC
DEC -10 to 110°C
Setpoint
25.0oC
INC DEC
-10 to 110°C
MENU
Minimum
25.0oC
Outputs
H-----
INC Maximum
25.0oC
Hold for 2 seconds
Resets Min & Max
INC INC DEC
1 to 250 Sec 1 to 250 Sec
S Offst
5.0oC
MENU MENU S Diff
1.0oCMENU Setback
10.0oC
INC DEC INC DEC INC DEC
MENU Ext Pot
None
INC DEC
None, ±4°C
or ±20°C
0 to 12 °C
0 to 12 °C
0 to 50 °C
0 to 50 °C 0 to 30 °C
DEC
Stages 3,4 and 5
have been omitted
from this diagram
AX-ET-6
Electronic Thermostat – Six stage
4 of 4
Every effort has been taken in the prod ction of this data sheet to ens re acc racy. Axio do not accept responsibility for any damage,
expense, inj ry, loss or conseq ential loss res lting from any errors or omissions. Axio has a policy of contin o s improvement and
reserves the right to change this specification witho t notice.
4 of 4
Setup strategy
The example below shows the relationship between the setpoint,
offset and differentials. For this example the setpoint will be set
to 20°C and the stage switching req irements are as shown in the
table below.
Stage Action Switch On Switch Off Mid point
1 Cooling > 28°C < 24°C 26°C
2 Cooling > 24°C < 22°C 23°C
3 Heating < 18°C > 20°C 19°C
4 Heating < 16°C > 18°C 17°C
5 Heating < 14°C > 16°C 15°C
6 Heating < 10°C > 14°C 12°C
Once the setpoint and switching req irements have been defined
the stage offsets and stage differentials can be calc lated.
For Stage 1 Cooling
Stage Offset = Stage mid point - Setpoint
= 26 - 20
= 6
Stage Differential = Switch on - Switch off
= 28 - 24
= 4
The calc lated val es, listed below, sho ld be entered sing the
set- p men .
Set p option Req ired val e
Stage select CCHHHH
S1 Offset 6°C
S1 Differential 4°C
S2 Offset 3°C
S2 Differential 2°C
S3 Offset 1°C
S3 Differential 2°C
S4 Offset 3°C
S4 Differential 2°C
S5 Offset 5°C
S5 Differential 2°C
S6 Offset 8°C
S6 Differential 4°C
Setback Off
External Pot None
The diagram below ill strates the relationship
between the val es set for the example.
12 14 16 18 20 22 24 26
S1 Diff = 4
S3 Diff = 2
Setpoint = 20
Temperature
S2 Diff = 2
S4 Diff = 2
28
S4 ON
S4 OFF
S3 OFF
S3 ON
S2 ON
S1 ON
S2 OFF
S1 OFF
10
Stage 4
Stage 3
Stage 2
Stage 1
S2 Offset = 3
S1 Offset = 6
S3 Offset = 1
S4 Offset = 3
S5 Diff = 2
S5 ON
S5 OFF
Stage 5
S5 Offset = 5
S6 Diff = 4
S6 ON
S6 OFF
Stage 6
S6 Offset = 8
8

Popular Thermostat manuals by other brands

LHZ 25312 manual

LHZ

LHZ 25312 manual

Honeywell TRADELINE Q7100A installation instructions

Honeywell

Honeywell TRADELINE Q7100A installation instructions

Max BC-RT-TRX-CyG-4 operating manual

Max

Max BC-RT-TRX-CyG-4 operating manual

Heat IQ HIQ 424 instructions

Heat IQ

Heat IQ HIQ 424 instructions

Aube Technologies TH110A-DP-P owner's manual

Aube Technologies

Aube Technologies TH110A-DP-P owner's manual

Robertshaw 8600 user manual

Robertshaw

Robertshaw 8600 user manual

Honeywell RLV450 user guide

Honeywell

Honeywell RLV450 user guide

Gewiss Chorus GW 16 974CB installation manual

Gewiss

Gewiss Chorus GW 16 974CB installation manual

Energotech EnergoControl T60-EH Installation instruction

Energotech

Energotech EnergoControl T60-EH Installation instruction

RCS Technology TBZ500 installation guide

RCS Technology

RCS Technology TBZ500 installation guide

tado° tado Welcome guide

tado°

tado° tado Welcome guide

ICM Controls SC 2300 Installation, operation & application guide

ICM Controls

ICM Controls SC 2300 Installation, operation & application guide

Eurotronic SPARmatic comet User's manual and guarantee

Eurotronic

Eurotronic SPARmatic comet User's manual and guarantee

Siemens RDG100KN manual

Siemens

Siemens RDG100KN manual

AMX ViewStat installation guide

AMX

AMX ViewStat installation guide

Honeywell CT230-GA installation guide

Honeywell

Honeywell CT230-GA installation guide

OJ Microline OTN Series instructions

OJ

OJ Microline OTN Series instructions

Observer TSTAT0201CW owner's manual

Observer

Observer TSTAT0201CW owner's manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.