Axiom ZEUS User manual

Axiom Technologies ZEUS Dual Compressor Manual
255 Pennbright Dr, Suite 220, Houston, Texas 77090 Phone 281 931 0907
Dual-Solar-Powered-Air-Compressor-Manual-2022.docx 1
Axiom Technologies L.L.C
Telephone: 281 931 0907
255 Pennbright Dr, Suite 220 Fax: 281 231 6562
Houston, Texas 77090 www.axiomsafety.com
ZEUS Dual Compressor
USER’S MANUAL
Programmable
Solar Powered
Air Compressor

Axiom Technologies ZEUS Dual Compressor Manual
255 Pennbright Dr, Suite 220, Houston, Texas 77090 Phone 281 931 0907
Dual-Solar-Powered-Air-Compressor-Manual-2022.docx 2
INTRODUCTION
This document addresses operation of the ZEUS with application program version
“Charger7P.rgd”. Note that for this version to operate correctly you must first install Axiom OS
version 149 or later (see instructions near the end of this document).
GENERAL OPERATION
Upon power application, the charger unit will immediately begin measuring pressure on
compressor #1 & #2 and controlling the compressor drivers output to maintain pressures between
the call and off setpoints. It will also begin monitoring battery voltage, solar panel voltage and
charging current and controlling battery charging.
WARNING – EXPLOSION HAZARD
ONLY INSTALL THE ZEUS IN AREAS KNOW
TO BE NON-HAZARDOUS

Axiom Technologies ZEUS Dual Compressor Manual
255 Pennbright Dr, Suite 220, Houston, Texas 77090 Phone 281 931 0907
Dual-Solar-Powered-Air-Compressor-Manual-2022.docx 3
ACCESSING MENUS
Charger operation is controlled by employing a series of setpoints using the onboard keyboard and
LCD display. In order to access the main menu, press the minus (-) key on the unit’s keyboard.
The following menu will appear:
*** SYSTEM MENU ***
1 Display 5 Set Clk
2 Setpts 7 Contrast
3 Logon 8 Show I/O
Pressing the down arrow key from the System menu will show the installed OS version, programs
version and time of program installation.
*** VERSIONS NOW ***
OS rev 149 (operating system version)
Charger7P.rgd (program version)
5/4/2022 4:42:48 PM (when the program was loaded to the controller)
Pressing the up arrow key will return the display to the System Menu.
From the System Menu, pressing the appropriate key will transfer the display to a menu that
addresses the specific selection. Below discusses the displays, setpoints and logon/logoff as these
are specific to this application.
LOGGING ON/OFF
You will need to log on for some of the operations below so the logon/logoff process is described
first. If the main menu indicates ‘3 logon’, then you are not logged on and will be blocked from
changing setpoints and some values directly accessible on the displays. To logon, press key ‘3’
from the main menu. You will get the following prompt:
Logon code?
=
You will need to type in the correct numeric logon code (factory default is “0”) followed by the
ENTER key. The system menu will now be the following:
*** SYSTEM MENU ***
1 Display 5 Set Clk
2 Setpts 7 Contrast
4 Logoff 8 Show I/O
To log off, press key “4” from this menu. Also, if you do not alter a setpoint for 30 minutes, the
system will automatically log off.

Axiom Technologies ZEUS Dual Compressor Manual
255 Pennbright Dr, Suite 220, Houston, Texas 77090 Phone 281 931 0907
Dual-Solar-Powered-Air-Compressor-Manual-2022.docx 4
SETPOINTS
Note: Setpoints are system parameters that typically remain constant and are not normally altered
in the field. Values that are typically field-application specific are found under the Display menu.
From the System menu, pressing key “2”, will bring up the setpoint menu. Be sure to log on if
you wish to change any setpoints. The setpoints in this system and the default values are as
follows:
Coul eff(0 to 1.0)= 0.85
Batt capacity, AHr=200.0
Compr1CyclesToDrain=50.0
Compr1DrainSec=1.0
Compr2CyclesToDrain=50.0
Compr2DrainSec=1.0
Drain holdoff tempF=45.
Drain restore, Hr:6.
Dump OFF delay Sec=30.
Level Steady Sec=5.
Max address to poll=0.
Sol 1 Off delay sec=3.
Sol 1 On delay sec =3.
Sol 2 Off delay sec=3.
Sol 2 On delay sec =3.
Sol 3 Off delay sec=3.
Sol 3 On delay sec =3.
Sol 4 Off delay sec=3.
Sol 4 On delay sec =3.
Sol 5 Off delay sec=3.
Sol 5 On delay sec =3.
Sol 6 Off delay sec=3.
Sol 6 On delay sec =3.
BatV (12 or 24)= 12.
Slave Address= 1.
TempF now=68.0 (see description below before changing)
Logon code:0
When you press key “2” from the main menu, you will be presented with the first setpoint in the
list as shown below:
*** SETPOINT ***
Coul eff (0 to 1.0)=
0.85
Hit CLR to change…
To move to the next setpoint in the list, press the down arrow or the ENTER key. If you wish to
change this setpoint, press the CLR key and the “Hit CLR to change…” line will blank out and

Axiom Technologies ZEUS Dual Compressor Manual
255 Pennbright Dr, Suite 220, Houston, Texas 77090 Phone 281 931 0907
Dual-Solar-Powered-Air-Compressor-Manual-2022.docx 5
you may begin typing a new value. Your entry will appear on that line. Press ENTER after your
entry to install the new value.
HOW THE SETPOINTS ARE USED
The setpoints are used as follows in this application:
Coul eff: The ratio between the energy removed from a battery during discharge compared with
the energy used during charging to restore the original capacity. This is used in the calculation of
remaining charge. Default is 0.85
Batt capacity, AHr: sets the assumed battery capacity for calculations of remaining charge. Note:
for 24V systems, the value entered should be half of the 12V cumulative battery ratings since the
batteries are installed in series pairs.
Compr 1 Cycles To Drain: this sets the number of cycles between tank water dumps for tank 1.
Compr 1 Drain Sec: this sets the duration of each dumping cycle for tank 1.
Compr 2 Cycles To Drain: this sets the number of cycles between water dumps for tank 2.
Compr 2 Drain Sec: this sets the duration of each dumping cycle for tank 2.
Drain holdoff tempF: temperature below which drain cycles are paused. This is to prevent
attempted operation during freezing temperatures.
Drain restore, Hr: time after temperature rises above “Drain holdoff tempF” before drain cycles
are resumed.
Dump OFF delay Sec: when using the ZEUS to control a tank dump valve, this controls the
amount of time the valve dumps in response to a float “high level” signal.
Level Steady Sec: when using the ZEUS to control a tank dump valve, this is used to filter false
“high level” signals due to tank sloshing. The controller will ignore “high level” signals that are
shorter in duration than the value entered.
Max address to poll: used only with the auxiliary dump control board – Should be Set to 0
Sol 1-6 Off delay sec: used only with the auxiliary dump control board – Default values 3
Sol 1-6 On delay sec: used only with the auxiliary dump control board – Default values 3
BatV (12 or 24): Specifies 12 or 24 volt compressor, battery configuration and solar panel voltage
Slave Address: Sets address for MODBUS communication with user’s SCADA system. Note:
Controller must be restarted for new address to activate.
TempF now: sets temperature for temperature transducer calibration. This controls the maximum
and minimum charge voltages. To complete the calibration, the new value must be installed under
the Housekeeping display (See Housekeeping).
Logon code: Allows the user to change the logon code.
ACCESSING DISPLAYS
Pressing key “1” from the main menu will open the Displays menu. The following displays are
available with this version (7P) of the charger application program:
Summary
Charger
Compressor #1
Compressor #2
ComprStats
Housekeeping

Axiom Technologies ZEUS Dual Compressor Manual
255 Pennbright Dr, Suite 220, Houston, Texas 77090 Phone 281 931 0907
Dual-Solar-Powered-Air-Compressor-Manual-2022.docx 6
Cal pressure XD
Station 2 (Not used for the ZEUS Compressor)
Station 3 (Not used for the ZEUS Compressor)
Station 4 (Not used for the ZEUS Compressor)
Station 5 (Not used for the ZEUS Compressor)
Dump Function
Since the LCD has only four lines, only four lines at a time can be shown. Therefore, when first
accessed, the display menu will appear as below showing the first four displays available:
0 Summary
1 Charger
2 Compressor #1
3 Compressor #2
If you press the down arrow or ENTER key, the menu will shift down to present two more display
choices as shown below:
0 Compressor #1
1 Compressor #2
2 ComprStats
3 Housekeeping
If you keep pressing the down arrow or ENTER key the display list will rotate until it rotates back
to the top of the list. The specific displays will be discussed below.
Some displays will contain keystroke prompts to indicate that pressing one of the numeric keys
will result in some action. These are always presented as a numeral followed by a right parenthesis.
For example, in the following hypothetical display, keys 1, 3, 4 and 9 will result in the listed
actions:
Hypothetical Display
.
1)Lamp test
3)Setpt A=12.34
4)Setpt B=56.78
9)Alarm ACK
key 1 will cause the alarm lamps to turn on for 2 seconds
key 3 will enable you to change setpoint A
key 4 will enable you to change setpoint B
key 9 will acknowledge alarms
If you press key 1 or key 9 in the above example, the indicated action will be taken with no change
in the display. However, if you press a key associated with a settable value such as key 3 or key
4 in the above example, the display will blank and you will be prompted for a new value. After

Axiom Technologies ZEUS Dual Compressor Manual
255 Pennbright Dr, Suite 220, Houston, Texas 77090 Phone 281 931 0907
Dual-Solar-Powered-Air-Compressor-Manual-2022.docx 7
entering the new value followed by the ENTER key, the new value will take effect and the display
will return to normal.
SUMMARY DISPLAY
The summary display provides an overview of unit condition as well as options related to the
cyclical operation options. Use the arrow key to display lines 5-12.
*** SUMMARY ***
PV=13.5 BV=12.4
PSI#1=96 PSI#2=35
No alarms
1)Lamp test
9)Alarm ACK
2)Cycle mode now=OFF
5)Clr cycle timer
3)Cycle min. = 60 (Default=120)
4)Enable min. = 5 (Default=30)
Timer now = 20
Compres. Enable = OFF
PV presents the measured solar panel voltage.
BV presents the measured battery voltage.
PSI #1 displays the measured pressure from compressors #1 in PSI.
PSI #2 displays the measured pressure from compressors #2 in PSI.
Line 4 summarizes alarms presently active. If there are no alarms, then ‘No alarms’ will be
shown on line 4. If one or more alarms exist then the alarm messages will be shown in rotation
once per second on line 4.
The functionality of the last 8 lines are described below.
1)Lamp test: temporarily turns on the indicating lamp outputs shown in the connection diagram.
9)Alarm ACK: clears the alarms shown on line 4 of the Summary Display.
2)Cycle mode now: toggles the cycle mode between “OFF” and “ON”.*
5)Clr cycle timer: resets the cycle timer back to “1”.
3)Cycle min: defines the duration of a cycle in minutes.
4)Enable min: defines how long the compressor is permitted to run during each cycle.
Timer now: shows how many minutes the counter is in to a cycle.
Compres. Enable: shows if the compressor is enabled “ON” or disabled “OFF” by the cycle timer.
*The cycle mode is used if the operator wishes to limit the duration the compressor is allowed to
run. One example of this is when the compressor is used for soil reclamation duty. In this example,
the runtime could be limited to ensure that the batteries are not depleted during each day’s
operation. Another situation where the operator may wish to limit cycle duration is when filling

Axiom Technologies ZEUS Dual Compressor Manual
255 Pennbright Dr, Suite 220, Houston, Texas 77090 Phone 281 931 0907
Dual-Solar-Powered-Air-Compressor-Manual-2022.docx 8
large accumulators. Using the cycle mode, the duty cycle of the compressor can be limited to
reduce peak temperatures of the compressor head which will extend compressor life.
CHARGER DISPLAY
The Charger display presents information regarding battery charging and the solar panel output.
*CHARGER* SHNT=OFF
Pan V=13.5 I=3.4
Bat V=12.4 I=1.4
No Alarms
Shunt ON at BV=14.0
Shunt OFF at BV=13.6
Bat charg %=71.2
On line 1, SHNT=OFF indicates that the shunt is off and battery charging is enabled. If battery
terminal voltage exceeds the shunt ON setpoint, then the shunt will be turned on, shorting the
panel to ground and prohibiting charging. If battery terminal voltage falls below the shunt OFF
setpoint, then the shunt will be turned off allowing the panel to charge the battery.
Lines 2 and 3 present panel and battery voltage and current, respectively. For currents, positive
current indicates current from the panel and to the battery. A negative current (battery only)
indicates battery discharge current.
Line 4 presents any alarms involving the charger. Possible alarms are:
Low Batt alarm
Low Batt Cutoff ON
Shunt ON at BV=14.0 indicates that at a battery voltage of 14.0 volts or above, the shunt will turn
on to suspend charging.
Shunt OFF at BV=13.6 indicates that at a battery voltage of 13.6 volts or below, the shunt will turn
off to allow charging. The values shown here to indicate the shunt thresholds after temperature
compensation.
Bat charg %=71.2 indicates the calculated state of battery charge as a percentage of amp hour
capacity.
COMPRESSOR DISPLAYS
The next two displays present information relating to the two compressors and are identical, except
that the header will read “Compressor #2” for the second compressor control.
** COMPRESSOR #1 **
PSI=96 Amps=21.0
1)Call=90 2)Off=97
3)HOA=AUTO NOW=ON
4)Hi alarm PSI=150 (Default=150)
5)Lo alarm PSI=0 (Default=0)
6)Overcurrent A=75 (Default=75)

Axiom Technologies ZEUS Dual Compressor Manual
255 Pennbright Dr, Suite 220, Houston, Texas 77090 Phone 281 931 0907
Dual-Solar-Powered-Air-Compressor-Manual-2022.docx 9
7)Reset fail now=0
8)PSI now=Xducer#1
9)Max run min. = 60.0 (Default=60)
This run min. = 0.0
Line 2 presents pressure in PSI being measured and current in amps being supplied to the
compressor.
The next 8 lines present seven setpoints related to compressor #1 that can be altered while
viewing the compressor display:
1)Call=90: indicates that the present compressor call setpoint (pressure below which the
compressor will be turned on) is presently 90 PSI and pressing key ‘1’ will enable you to change
the call pressure. If you press key ‘1’, the display will change to:
Call PSI=
=
You may now type in a new value followed by the ENTER key to alter the setpoint. If you do
not want to change the setpoint, press the ENTER key to return to the compressor display. Other
setpoints that you can change:
2)Off=97: indicates the pressure above which the compressor will be turned off. Press key ‘2’ to
change it.
3)HOA=AUTO NOW ON: indicates that pressing key ‘3’ enables you to change the HOA
(Hand/Off/Auto) state of control of the compressor and that it is presently set to AUTO and the
compressor is presently called (ON). If you press key ‘3’ you will get a prompt:
0=Off, 1=On, 2=Auto
=
This indicates that entering a value of 0 will turn off the compressor, a value of 1 will turn on
the compressor, and a value of 2 will set the compressor for AUTO operation wherein the
measured pressure will govern the on/off call to the compressor.
4)Hi alarm PSI=100: indicates that key ‘4’ allows you to set the pressure high alarm setpoint
which is presently set to 150 PSI.
5)Lo alarm PSI=0: indicates that key ‘5’ allows you to set the pressure low alarm setpoint which
is presently set to 0 PSI.
6)Overcurrent A=75: indicates that key ‘6’ allows you to set the overcurrent setpoint. If the
compressor draws more than this current for more than 10 seconds, the compressor will be shut
down for 20 seconds then retried. After 3 tries, the overcurrent alarm will be declared and the
compressor held off until manually reset.
7)Reset fail now=0: indicates that compressor overcurrent alarm is 0 (off) and pressing key ‘7’
will clear the alarm if it was on.
8)PSI now=Xducer#1: indicates that the pressure reading used to control the current compressor
(#1 or #2) is being taken from transducer #1. Pressing the “8” key switches the reading to the
other transducer. This feature is useful when the two tanks are plumbed together and it is desired

Axiom Technologies ZEUS Dual Compressor Manual
255 Pennbright Dr, Suite 220, Houston, Texas 77090 Phone 281 931 0907
Dual-Solar-Powered-Air-Compressor-Manual-2022.docx 10
that both compressors share runtime. In that scenario, both compressors would be set to
transducer #1 (or transducer #2). This option should only be used if the outputs of both tanks
are teed together upstream of any check valves.
9)Max run min.=60.0: is a user set value that limits how long the specific compressor (1 or 2) is
allowed to run before shutting down and initiating an alarm. The purpose of this function is to
prevent significant leaks from discharging the battery bank.
This run min. =0.0: shows how long the compressor has currently been continuously running
COMPRESSOR STATISTICS DISPLAY
The compressor statistics display presents total compressor run hours and starts for today (since
midnight), for yesterday, and since the last preset event (manual presets). Here’s the display:
*Compressor Stats *
1Hr=125.3 Cyc=1234 (Compr1 Tot run hrs and cycles since preset)
2Hr=45.9 Cyc=343 (Compr2 Tot run hrs and cycles since preset)
9)Preset stats
1)#1 Hr Preset=0 (Default=0)
2)#2 Hr Preset=0 (Default=0)
3)#1 Cy Preset=0 (Default=0)
4)#2 Cy Preset=0 (Default=0)
Today:
1Hr=3.88 Cyc=17
2Hr=1.45 Cyc=7
Yesterday:
1Hr=5.52 Cyc=33
2Hr=2.97 Cyc=12
Key [9] installs the four preset values that follow into the time and cycle counters. The specific
preset values should be entered beforehand using keys [1] through [4].
HOUSEKEEPING DISPLAY
The housekeeping display is the following:
*** HOUSEKEEPING ***
09/28/2015 21:05:49
TmpF=70.5 C=21.4
Scans/sec=89
Items logged=949
5)=Clear com fails
6)=Dump log nxt=0
7)=Clear log
8)=install tempF cal
9)=install defaults
0)=install PSI defaults

Axiom Technologies ZEUS Dual Compressor Manual
255 Pennbright Dr, Suite 220, Houston, Texas 77090 Phone 281 931 0907
Dual-Solar-Powered-Air-Compressor-Manual-2022.docx 11
Line 2 presents the present date and time of the real-time clock. It is used to time tag logged data.
Line 3 presents onboard temperature in degrees F and C. Temperature is used to temperature
compensate battery charge completion.
Line 4 indicates the processor scan rate in complete program scans per second.
Line 5 indicates number of lines logged. The onboard logger samples an array of data once per
minute and can store 1000 records.
5)=Clear com fails: clears Station 2 – Station 5 communication failure alarms
6)=Dump log nxt=0: indicates that pressing key ‘6’ will send the entire log out the programming
port. The dump has the following form. Each line presents: Date Time, BattV, BattAmps,
TempF, Compr#1Amps, Compr#2Amps, Compr#1PSI, …Compr#2PSI, PanelAmps,
PanelV,Bat%Charge
LOG! DUMP
09/28/2012 21:15:38,12.31,-0.15,72.64,4.74,5.09,35.09,0.00,0.00,0.00,0.00
7)=Clear log: pressing key ‘7’ will erase the logged data.
8)=install temp F cal: pressing key ‘8’ will calibrate the temperature transducer to the temperature
contained in the setpoint list.
9)=install defaults: pressing key ‘9’ will install default values to all setpoints.
0)=install PSI defaults: installs default calibrations for the two pressure transducers and installs
values typical to a 160 psi 0.5-4.5V transducer. These settings can subsequently be overridden
by performing the pressure transducer calibrating procedure.
CALIBRATING PRESSURE TRANSDUCER
The display below is the gateway to the pressure calibration procedure. You must be logged on to
perform this procedure. This program revision relies on calibration constants stored in flash
memory to provide proper offset and span for the transducers. This will be done before the
compressors leave the factory, but would need to be repeated if a transducer was replaced in the
field. The procedure will start by asking the user to identify which channel they wish to calibrate
(for the ZEUS Jr., this will always be channel 1. Then it will ask the user to apply a high pressure
to the transducer and type in the pressure that was applied. Usually this will be a pressure near the
expected operating point for that channel. The actual pressure you use is not important; only that
it is accurately measured and typed in correctly. It will then ask the user to apply a low pressure
to the selected channel and then type in the pressure applied. Usually, the air tank would be vented
and 0.0 would be entered. Then the user will be asked to press a key to save the calibration. After
that, the pressure measurement will be accurate.
*** Press XD Cal ***
Key 2=START
Must be logged on
If this display is not presented, press key 1 to back up the procedure until it appears. From this
display, pressing key 2 will start the procedure and present the following display:
Key 3=toggle channel

Axiom Technologies ZEUS Dual Compressor Manual
255 Pennbright Dr, Suite 220, Houston, Texas 77090 Phone 281 931 0907
Dual-Solar-Powered-Air-Compressor-Manual-2022.docx 12
Channel=1
Key1=Back, Key2=Next
Here, key ‘3’ will toggle between channels 1 and 2. Once the channel to be calibrated is selected,
press key ‘2’ to proceed to the next display:
Apply high PSI
To channel=1
Then hit key 4
Key1=Back, Key2=Next
Here the user must apply a known high pressure to the transducer and then press key ‘4’. After
that a prompt will appear to enter the pressure applied:
High PSI applied=
=
Now type in the pressure you applied followed by the ENTER key. The display will transition to
the next step:
Apply low PSI
To channel=1
Then hit key 5
Key1=Back, Key2=Next
Now apply a known low pressure to the transducer (usually open the transducer to atmospheric
pressure) and press key ‘5’. After that a prompt will appear to enter the pressure applied:
Low PSI applied=
=
Now type in the pressure you applied followed by the ENTER key. The display will transition to
the next step:
Hit key 6 to save
New calibration
Channel=1
Key1=Back, Key2=Next
Now press key ‘6’ to save the new calibration. End of procedure; the transducer should now
accurately measure pressure.

Axiom Technologies ZEUS Dual Compressor Manual
255 Pennbright Dr, Suite 220, Houston, Texas 77090 Phone 281 931 0907
Dual-Solar-Powered-Air-Compressor-Manual-2022.docx 13
CALIBRATING ONBOARD TEMPERATURE
The onboard temperature measurement is used to offset the battery charge completion voltage so
as to neither over-charge nor under-charge the lead acid battery whose terminal voltage is
dependent upon temperature. To set the temperature calibration takes two steps:
1) Log on and access the setpoint list (key 2 from the main menu) and use the down arrow to
traverse down to the setpoint labeled “TempF now=”. Then press the CLR key and type
in the present temperature in degrees F at the site followed by the ENTER key.
2) Press the minus key to exit the setpoint screen and get the main menu. Press key “1” to
access the display list and traverse over to access the Housekeeping display. On the
Housekeeping display, press key “8”. This will install the temperature that you entered as
the present calibration for the temperature channel
DUMP FUNCTION DISPLAY
The dump function display shows the statuses of the separator drain control input and output.
**DUMP FUNCTION**
DI2=0
Steady Timer=50 0
Delay Timer 0 0
Line 2 presents the status of the level switch signal (OFF or ON). When tripped, the DI2 value
will change from “0” to “1”.
Line 3 presents the status of the delay timer used to prevent false trips (due to sloshing). The first
value show will initially be the delay entered (in tenths of a second) in Setpoints under the Level
Steady setting. When the controller receives a signal from the tank level switch, the timer will
begin counting down. When the counter reaches “0”, it will call the solenoid driver to initiate
the dump function. The second value will change from “0” to “1” to indicate that the call is
being made.
Line 4 indicates the status of the solenoid driver output. When the call is made by the Steady
Timer, the first value will change from “0” to the value entered (in tenths of a second) in
Setpoints under Dump OFF delay. The second value will change from “0” to “1” to indicate that
the solenoid driver is energized. When the Steady Timer call is cancelled, the first value will
count down to “0”. When it reaches “0”, the second value will change from “1” to “0” to indicate
that the solenoid driver output has been de-energized, ending the dump operation.
ALARM and AUDIO OUTPUTS
The charger has AUDIO, FAIL, OK and STROBE outputs. These are pull to ground outputs
capable of sinking up to 100 ma. Whenever a new alarm is detected after no alarms have been
present both the AUDIO and FAIL outputs will begin flashing ON/OFF once per second and the
OK output will turn off. This will continue even if the alarm condition goes away. To
acknowledge the alarm(s), access the Summary display and press key “9”. The flashing will stop
and the audible turn off. If an alarm is still present, the FAIL output will stay on and the OK output

Axiom Technologies ZEUS Dual Compressor Manual
255 Pennbright Dr, Suite 220, Houston, Texas 77090 Phone 281 931 0907
Dual-Solar-Powered-Air-Compressor-Manual-2022.docx 14
will stay off. Once the alarms are all corrected, then the FAIL output will turn off and the OK
output will turn on. The STROBE output is presently unused.

Axiom Technologies ZEUS Dual Compressor Manual
255 Pennbright Dr, Suite 220, Houston, Texas 77090 Phone 281 931 0907
Dual-Solar-Powered-Air-Compressor-Manual-2022.docx 15

Axiom Technologies ZEUS Dual Compressor Manual
255 Pennbright Dr, Suite 220, Houston, Texas 77090 Phone 281 931 0907
Dual-Solar-Powered-Air-Compressor-Manual-2022.docx 15

Axiom Technologies ZEUS Dual Compressor Manual
255 Pennbright Dr, Suite 220, Houston, Texas 77090 Phone 281 931 0907
Dual-Solar-Powered-Air-Compressor-Manual-2022.docx 16

Axiom Technologies ZEUS Dual Compressor Manual
255 Pennbright Dr, Suite 220, Houston, Texas 77090 Phone 281 931 0907
Dual-Solar-Powered-Air-Compressor-Manual-2022.docx 17

CHARGER MODBUS INTERFACE
The unit is programmed to respond as a slave to modbus RTU polls on RS485 serial port 4. Port serial
parameters are: baud 9600, no parity, 8 bit word, 1 stop bit. Slave address is 1.
The tag list for reading statuses using message types 1 or 2 is the following:
Word1: (Charger local alarms)
Bit 1 Low battery voltage alarm
Bit 2 Low battery cutoff alarm
Bit 3 Compr1ThisRunLongAlarm
Bit 4 Compr2ThisRunLongAlarm
Word2: (Remote 1)
Bit 1 RunLong alarm
Bit2 Hall fail
Bit3 RunTooLongWarning
Word3: (Remote 2)
Bit 1 RunLong alarm
Bit2 Hall fail
Bit3 RunTooLongWarning
Word4: (Remote 3)
Bit 1 RunLong alarm
Bit2 Hall fail
Bit3 RunTooLongWarning
Word5: (Remote 4)
Bit 1 RunLong alarm
Bit2 Hall fail
Bit3 RunTooLongWarning
Word6: (Remote 5)
Bit 1 RunLong alarm
Bit2 Hall fail
Bit3 RunTooLongWarning
Word7: (Remote 6)
Bit 1 RunLong alarm
Bit2 Hall fail
Bit3 RunTooLongWarning
The tag list for data available in response to message type 3 or 4 is the following. All registers are signed integers:
Register 10 Battery voltage *10
Register 11 Panel voltage *10
Register 12 Temperature, deg. F *10
Register 13 Compressor #1 PSI
Register 14 Compressor #2 PSI
Register 15 Compressor #1 total cycles, LS
Register 16 Compressor #1 total cycles, MS (/1000)
Register 17 Compressor #2 total cycles, LS

Register 18 Compressor #2 total cycles, MS (/1000)
Register 19 Compressor #1 cycles so far today (since midnight)
Register 20 Compressor #1 cycles yesterday
Register 21 Compressor #2 cycles so far today (since midnight)
Register 22 Compressor #2 cycles yesterday
Register 23 Compressor #1 total running hours, LS
Register 24 Compressor #1 total running hours, MS (/1000)
Register 25 Compressor #2 total running hours, LS
Register 26 Compressor #2 total running hours, MS (/1000)
Register 27 Compressor #1 running hours so far today *10 (since midnight)
Register 28 Compressor #1 running hours yesterday *10
Register 29 Compressor #2 running hours so far today *10 (since midnight)
Register 30 Compressor #2 running hours yesterday *10
Register 31 Battery percent charge *10
Register 32 Compressor #1 CALL setpoint, PSI
Register 33 Compressor #1 OFF setpoint, PSI
Register 34 Compressor #1 high alarm setpoint, PSI
Register 35 Compressor #1 low alarm setpoint, PSI
Register 36 Compressor #1 over current setpoint, amps
Register 37 Compressor #1 HOA setting (0=off, 1=on, 2=auto)
Register 38 Compressor #2 CALL setpoint, PSI
Register 39 Compressor #2 OFF setpoint, PSI
Register 40 Compressor #2 high alarm setpoint, PSI
Register 41 Compressor #2 low alarm setpoint, PSI
Register 42 Compressor #2 over current setpoint, amps
Register 43 Compressor #2 HOA setting (0=off, 1=on, 2=auto)
Register 44 Compressor #1 overcurrent event count
Register 45 Compressor #2 overcurrent event count
The tag list for writable control bits using message type 5 is the following. These bits are automatically cleared
after reception and action has been taken:
Word1:
Coil 1 Reset compressor #1 overcurrent alarm count
Coil 2 Reset compressor #2 overcurrent alarm count
Coil 3 Reset OnTooLong alarms
Coil 4 Install Compressor 1 call PSI (below)
Coil 4 Install Compressor 1 off PSI (below)
Coil 4 Install Compressor 2 call PSI (below)
Coil 4 Install Compressor 1 off PSI (below)
The tag list for writable control registers using message types 6 or 16 to the charger receive array are the
following signed integers:
Register 3 Compressor 1 call PSI
Register 4 Compressor 1 off PSI
Register 5 Compressor 2 call PSI
Register 6 Compressor 2 off PSI